23
Fig. 11
Cleaning and replacing the detection photoresistor
To clean/replace the photoresistive detector, remove it from its slot. To clean the photoresistor, use a clean cloth, not
cleaning sprays.
Check the detection current
To measure the detection current, refer to the diagram in Fig. 12. If
the signal doesn’t suit the suggested value, verify the electric
terminals, the cleaning of the combustion head and the position of
the photoelectric cell and replace it if required.
Fig. 12
LOA24 LMO24 LMO44
Minimum current intensity with flame:
45µA
Maximun current intensity without flame
5.5µA
Maximum possible current intensity with flame
45µA 100µA
100µA
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
turn the burner main switch to 0 (Off position)
disconnect the power mains
close the fuel valve of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.