background image

 

 

29

SIEMENS OIL BURNERS AUTOMATIC CONTROLLER 
SIEMENS LMO14 - LMO24 - LMO44 

The LMO... burner controls are designed for the start-up and 
supervision of single- or 2-stage forced draught oil burners in 
intermittent operation. Yellow-burning flames are supervised with 
photoresistive detectors QRB..., blue-burning flames with blue-
flame detectors QRC... 
In terms of housing dimensions, electrical connections and flame 
detectors, the LMO... are identical to the LOA... oil burner controls. 

Preconditions for startup 

Burner control is reset 
All contacts in the line are closed 
No undervoltage 
Flame detector is darkened, no extraneous light 

Undervoltage 

Safety shut-down in the operating position takes place should the 
mains voltage drop below about AC 165 V 
Restart is initiated when the mains voltage exceeds about 
AC 175 V 

Time supervision oil pre-heater 

If the oil pre-heater’s release contact does not close within 10 
minutes, the burner control will initiate lock-out. 

Controlled intermittent operation 

After no more than 24 hours of continuous operation, the burner 
control will initiate an automatic safety shut-down followed by a 
restart. 

Control sequence in the event of fault 

If lock-out occurs, the outputs for the fuel valves and the ignition will 
immediately be deactivated (< 1 second). 

 

Cause Response 

After a mains failure 

Restart 

After voltage has fallen below the 
undervoltage threshold 

Restart 

In the event of a premature, faulty 
flame signal during «t1» 

Lock-out at the end of «t1» 

In the event of a premature, faulty 
flame signal during «tw» 

Prevention of start-up, lock-
out after no more than 40 
seconds 

If the burner does not ignite during 
«TSA» 

Lock-out at the end of TSA 

In the event the flame is lost during 
operation 

Max. 3 repetitions, followed 
by lock-out 

Oil pre-heater’s release contact does 
not close within 10 min. 

Lock-out 

Lock-out 

In the event of lock-out, the LMO... remains locked (lock-out 
cannot be changed), and the red signal lamp will light up. This 
status is also maintained in the case of a mains failure. 

Resetting the burner 

Whenever lock-out occurs, the burner control can immediately 
be reset. To do this, keep control     the lock-out reset button 
depressed for about 1 second (< 3 seconds). 

Ignition program with LMO24.113A2 

If the flame is lost during «TSA», the burner will be reignited, 
but not later than at the end of «TSAmax.». This means that 
several ignition attempts can be made during TSA (refer to 
«Program sequence»). 

Limitation of repetitions 

If the flame is lost during operation, a maximum of 3 repetitions 
can be made. If the flame is lost for the 4th time during 
operation, the burner will initiate lock-out. The repetition count 
is restarted each time controlled switching on by «R-W-SB» 
takes place. 

 
Operation 

 Lock-out reset button «EK...» is the key operating 
element for resetting the burner control and for 
activating / deactivating the diagnostic functions. 

 

The multicolour «LED» is the key indicating element 

for both visual diagnosis and interface diagnosis. 
s red 
l yellow 

o green 

Colour code table 

Status Colour 

code 

Colour 

Oil pre-heater heats, 
waiting time «tw»  

lllllllllll Yellow 

Ignition phase, ignition 
controlled 

lmlmlmlmlml Yellow-off 

Operation, flame o.k. 

oooooooooooo 

Green 

Operation, flame not o.k. omomomomomo 

Green-off 

Undervoltage lslslslslsl 

Yellow-red 

Fault, alarm 

sssssssssss 

Red 

Output of fault code 
(refer to Fault code table)

smsmsmsmsm Red-off 

Extraneous light prior to 
burner start-up 

osososososo Green-red 

Interface diagnosis 

ssssssssssssss 

Red flicker light

Key 

m Off 
l Yellow 
o Green 
s Red 

Diagnosis of cause of fault 

After lock-out, the red fault signal lamp remains steady on. 
In that condition, the visual diagnosis of the cause of fault 
according to the error code table can be activated by pressing 
the lock-out reset button for more than 3 seconds. 

 

Error code table 

Blink code 

Possible cause 

2 blinks ** 

No establishment of flame at the end of TSA 
l  Faulty or soiled fuel valves 
l  Faulty or soiled flame detector 
l  Poor adjustment of burner, no fuel 
l Faulty 

ignition 

3 blinks *** 

Free 

4 blinks **** 

Extraneous light on burner startup 

5 blinks ***** 

Free 

6 blinks ****** 

Free 

7 blinks ******* 

Too manny losses of fleme during operation 
(limitattion og the number of repetitions) 
l  Faulty or soiled fuel valves 
l  Faulty or soiled flame detector 
l  Poor adjustment of burner 

8 blinks ******** 

Time supervision oil pre-heater 

9 blinks ********* 

Free 

10 blinks ********** 

Wiring error or internal error, output contacts 

 

During the time the cause of fault is diagnosed, the control 
outputs are deactivated. 
Burner remains shut down 
Fault status signal «AL» at terminal 10 is activated 
The diagnosis of the cause of fault is quit and the burner 
switched on again by resetting the burner control. 
Press lock-out reset button for about 1 second (< 3 seconds). 

Содержание LO140 G-.TN Series

Страница 1: ...LO140 LO200 Light oil burners MANUAL OF INSTALLATION USE AND MAINTENANCE BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES ГОРЕЛКИ M039154CE Rel 4 2 01 2013 ...

Страница 2: ...nnecting the burner make sure that the unit rating is the same as delivery mains electricity gas oil or other fuel Observe caution with hot burner components These are usually near to the flame and the fuel pre heating system they become hot during the unit operation and will remain hot for some time after the burner has stopped When the decision is made to discontinue the use of the burner the us...

Страница 3: ...ances are installed to avoid dangerous conditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directive 2004 108 EC on electromagnetic compatibility Harmonised standards UNI EN 676 Gas Burners CEI EN 60335 1 Household and similar electrical appliances Safety ...

Страница 4: ...Actuator double stage burners 14 Air inlet The fuel coming from the supply line is pushed by the pump 11 to the nozzle and then into the combustion chamber where the mixture between fuel and air takes place and consequently the flame In the burners the mixture bertween fuel and air to perform clean and efficient combustion is activated by atomisation of oil into very small particles This process i...

Страница 5: ...ble on the boiler s ID plate or in the user s manual Example Furnace input kW 600 Backpressure mbar 4 In the Performance curve diagram Fig 2 draw a vertical line matching the furnace input value and an horizontal line matching the backpressure value The burner is suitable if the intersection point A is inside the performance curve Fig 1 Data are referred to standard conditions atmospheric pressure...

Страница 6: ...7 4 Pressure at the oil train inlet bar 1 Power supply 230V 50Hz Motor kW 0 18 Total power consumption kW 0 48 Protection IP40 Regulation Single stage Double stage Single stage Double stage Approx weight kg 18 18 19 19 Operating temperature C 10 50 Storage temperature C 20 60 Working service Intermittent Light oil net calorific value Hi 10210 kcal kg NOTE ON THE BURNER WORKING SERVICE Burners prov...

Страница 7: ...min max min max min max LO140 560 660 80 170 80 270 390 475 390 575 373 108 128 108 188 244 M8 188 108 158 133 32 338 LO200 560 660 65 170 65 270 390 475 390 575 373 108 128 108 188 244 M8 188 108 158 133 32 338 AS BS CS measures referred to burner with standard blast tube AL BL CL measures referred to burner with extended blast tube ...

Страница 8: ...es not represent the regulation range of the machine On this diagram the maximum output point is usually reached by adjsuting the combustion head to its MAX position see paragraph Adjusting the combustion head the minimum output point is reached setting the combustion head to its MIN position During the first ignition the combustion head is set in order to find a compromise between the burner outp...

Страница 9: ...he burner use means suitable to support its weight see paragraph Technical specifications The burner is designed to work positioned according to the picture below For different installations please contact the Technical Department Montaggio del bruciatore alla caldaia To install the burner into the boiler proceed as follows 1 on the boiler s door hole fix the 4 stud bolts according to the drilling...

Страница 10: ...t be revised consulting the burner manufacturer To choose the blast tube lenght follow the instructions of the boiler manufacturer In absence of these consider the following Cast iron boilers three pass flue boilers with the first pass in the rear part the blast tube must protrude no more than 100 mm values between 0 and 100mm into the combustion chamber Pressurised boilers with flame reversal in ...

Страница 11: ...ircuit Ring circuit Suction circuit Keys 1 Manual valve 2 Light oil filter 3 Light oil feeding pump 4 One way valve 5 Flexible hoses 6 Relief valve NOTE in plants where gravity or ring feed systems are provided install an automatic interception device see n 4 Fig 4 ...

Страница 12: ...en to the nozzle a part comes out from the nozzle while the othe part goes back to the pump In this system the by pass plug if provided must be removed and the optional return port on the pump s body must be sealed by steel plug and washer Double pipe system as for the single pipe system a pipe that connects the tank to the pump s inlet is used besides another pipe that connects the pump s return ...

Страница 13: ...ding the gears Pipes should not contain air pockets Rapid attachment joint should therefore be avoided and threaded or mechanical seal junctions preferred Junction threads elbow joints and couplings should be sealed with removable sg component The number of junctions should be kept to a minimum as they are a possible source of leakage Do not use PTFE tape on the suction and return line pipes to av...

Страница 14: ...he pump proceed as follows 1 remove the burner cover unscrewing the fixing screws 2 remove the closing nuts A and B on the inlet and return connections of the pump 3 screw the rotating nut of the two flexible hoses on the pump being careful to avoid exchanging the inlet and return lines see the arrows marked on the pump that show the inlet and the return see paragraph l see Double stage burnersLig...

Страница 15: ... the mains be sure that its switch is on Off position and find the burner s connectors WARNING The burner is provided with a jumper between terminals 6 and 7 in the event of connecting the high low flame thermostat remove this jumper before connecting the thermostat IMPORTANT while connecting electric supply wires to burner s teminal block be sure that ground wire should be longer than phase and n...

Страница 16: ...2 Light oil 11 5 13 2 9 4 9 Priming the pump and Oil rate adjustment Before starting with the adjustments it is necessary to prime the oil pump as follows 1 Remove the burner cover 2 start up the burner with double stage models turn the burner main switch A to On Fig 5 3 make the ST thermostat contacts close see chapter WIRING DIAGRAMS 4 wait until the EVG solenoid valve opens 5 remove the photore...

Страница 17: ...4 56 148 750 173 15 74 160 700 186 9 4 00 15 20 155 200 180 4 16 65 170 000 197 7 17 99 183 700 213 6 4 50 17 10 174 600 203 18 73 191 250 222 4 20 24 206 650 240 3 Tab 1 Double stage burners The oil flow rate is adusted by choosing the correct nozze spill back type whose size matches the boiler utilisation input and by setting the delivery and return pressure according to the values on diagram in...

Страница 18: ...01 2 25 7 64 8 11 8 55 8 96 9 36 9 74 10 11 10 47 10 81 11 14 11 47 11 78 12 09 12 39 12 68 12 96 13 24 13 51 2 50 8 49 9 01 9 50 9 96 10 40 10 83 11 24 11 63 12 01 12 38 12 74 13 09 13 43 13 76 14 09 14 40 14 71 15 02 2 75 9 34 9 91 10 45 10 96 11 44 11 91 12 36 12 79 13 21 13 62 14 01 14 40 14 77 15 14 15 49 15 84 16 18 16 52 3 00 10 19 10 81 11 40 11 95 12 48 12 99 13 48 13 96 14 41 14 86 15 29...

Страница 19: ...vided with key for cams I and IV with scerws for the other cams The Berger actuator is not provided with the manual control for the air damper The Siemens actuator is provided with AUTO MAN mode see pictures above Berger STA Siemens SQN72 High flame position I I red Stand by ignition and Low flame position II II blue EVG2 opening III IV black Combustion head adjustment To adjust the combustion hea...

Страница 20: ...SHUT DOWN TAKES PLACE CALL THE TECHNICAL SERVICE WITHOUT TRYING TO RESET FURTHER WARNING DURING NORMAL OPERATION THE PARTS OF THE BURNER NEAREST TO THE GENERATOR COUPLING FLANGE CAN BECOME VERY HOT AVOID TOUCHING THEM SO AS NOT TO GET BURNT OPERATION CAUTION before starting the burner up be sure that the manual cutoff valves on the feeding line and on the return are open Be that the mains switch i...

Страница 21: ... respective ceramic insulators clean adjust and replace if necessary disassemble and clean the light oil nozzle see Pulizia della testa di combustione e dell ugelloCleaning the combustion head and the nozzle on page 22 Important cleaning must be performed using solvent and not metal tools At the end of maintenance operations after first reassembling the burner light the flame and check its shape r...

Страница 22: ... the head from the nozzle holder Fig 10 3 Unscrew the VE screw that fastens the electrodes remove and clean or replace them In order to remove the nozzle it is important to use two wrenches as shown in Fig 10 to avoid damaging the burner component plate 4 clean or replace the nozzle 5 reassemble tall the elements remember to fasten the V and VE screws and re connect the cables CV Fig 10 respecting...

Страница 23: ...combustion head and the position of the photoelectric cell and replace it if required Fig 12 LOA24 LMO24 LMO44 Minimum current intensity with flame 45µA Maximun current intensity without flame 5 5µA Maximum possible current intensity with flame 45µA 100µA 100µA Seasonal stop To stop the burner in the seasonal stop proceed as follows turn the burner main switch to 0 Off position disconnect the powe...

Страница 24: ...NTROL BOX FAULT SERVOCONTROL FAULT SMOKY FLAME IGNITION TRANSFORMER FAULT IGNITION ELECTRODES DIRTY OR BAD POSITION DIRTY NOZZLE FUEL SOLENOID VALVE DEFECTIVE PHORESISTANCE DIRTY OR DEFECTIVE HIGH LOW FLAME THERMOSTAT DEFECTIVE BAD POSITION OF SERVOCONTROL CAMS FUEL LOW PRESSURE FUEL FILTERS DIRTY WIRING DIAGRAMS WARNING 1 Electrical supply 230V 50Hz 1N a c 2 Don t reverse phase with neutral 3 Ens...

Страница 25: ...ING SHAFT 3 2 COVER 11 5 PHOTORESISTOR 3 3 RUBBER COVER FOR UNLOCKING PUSHBUTTON 12 1 SWIRL VANE 4 1 INDEX FIXING SCREW 12 2 IGNITION ELECTRODE 5 FAIRLEAD 12 3 NOZZLE 6 CONTROL BOX 12 4 NOZZLE HOLDER 7 1 HOUSING 13 2 SOCKET FOR CONTROL BOX 7 2 AIR INLET 13 3 TRANSFORMER 7 3 FAIRLEAD 14 IGNITION CABLES 7 4 AIR DAMPER 7 5 AIR FLAP 7 6 BUSH 7 7 BUSH 7 8 AIR DAMPER SHAFT 7 9 PLATE SHAFT 8 GASKET 9 PUM...

Страница 26: ...26 ...

Страница 27: ...2 2 FAN WHEEL 4 FAIRLEAD 12 3 MOTOR 5 CONTROL BOX 12 4 SHAFT 6 1 HOUSING 12 5 PHOTORESISTOR 6 2 AIR INLET 13 1 NOZZLE HOLDER 6 3 FAIRLEAD 13 2 SWIRL VANE 6 4 AIR DAMPER 13 3 IGNITION ELECTRODE 6 5 AIR FLAP 13 4 NOZZLE 6 6 BUSH 14 CONTROL PANEL ASS Y 6 7 BUSH 15 2 SOCKET FOR CONTROL BOX 6 8 AIR DAMPER SHAFT 15 3 TRANSFORMER 6 9 PLATE SHAFT 15 4 GROUND FIXING 6 10 BUSH 15 5 PRINTED CIRCUIT BOARD 7 G...

Страница 28: ...28 ...

Страница 29: ...TSA the burner will be reignited but not later than at the end of TSAmax This means that several ignition attempts can be made during TSA refer to Program sequence Limitation of repetitions If the flame is lost during operation a maximum of 3 repetitions can be made If the flame is lost for the 4th time during operation the burner will initiate lock out The repetition count is restarted each time ...

Страница 30: ...nal primary fuse W Limit thermostat or pressure switch Z Ignition transformer t4 Interval from flame signal to release BV2 TSA Ignition safety time tw Waiting time for oil pre heating B Time of flame establishment C Operating position D Controlled shut down by R µC1 Microcontroller 1 µC2 Microcontroller 2 General unit data Mains voltageAC 230 V 10 15 AC 120 V 10 15 Mains frequency 50 60 Hz 6 Exter...

Страница 31: ...31 Measurement circuit for detector current Key µA DC DC microamperometer with an internal resistance of 5 kW max bl Blue sw Black br Brown ...

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...Note Specifications and and data subject to change Errors and omissions excepted ...

Отзывы: