PART I: SPECIFICATIONS
9
How to read the burner “Performance curve”
To check if the burner is suitable for the boiler to which it must be instal-
lled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h/860);
backpressure (data are available on the boiler ID plate or in the
user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4 mbar
In the “Performance curve” diagram, draw a vertical line matching the
furnace input value and an horizontal line matching the backpressure
value. The burner is suitable if the intersection point A is inside the per-
formance curve.
Data are referred to standard conditions: atmospheric pressure at 1013
mbar, ambient temperature at 15° C.
Performance Curves
To get the input in kcal/h, multiply value in kW by 860.
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15° C
NOTE:
The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests, but does not
represent the regulation range of the machine. On this diagram the maximum output point is usually reached by adjsuting the combustion head to its
“MAX” position (see paragraph “Adjusting the combustion head”); the minimum output point is reached setting the combustion head to its “MIN” position.
During the first ignition, the combustion head is set in order to find a compromise between the burner output and the generator specifications, that is why
the minimum output may be different from the Performance curve minimum
PRESSURE IN
COMBUSTION
CH
AMBER
(mb
ar)
K750A
kW
K890A
kW
PRESS
URE IN
COMB
USTION CHAMBER (m
bar)
K990A
kW
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
-1
0
1
2
3
4
5
6
7
8
100
200
300
400
500
600
700
800
900
Potenza kW
Contropressione in camera di
combustione mbar
A
ba
ckpr
essu
re in
co
m
bu
st
ion
ch
am
b
e
r
(m
b
ar
)
Power kW
Содержание K890A
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023 ...
Страница 56: ...8 Parameters level heating engineer ...
Страница 98: ...50 ERROR CODE TABLE ...
Страница 99: ...51 ...
Страница 100: ...52 ...
Страница 101: ...53 ...
Страница 102: ...54 ...
Страница 103: ...55 ...
Страница 104: ...56 ...
Страница 105: ...57 ...
Страница 106: ...58 ...
Страница 107: ...59 ...
Страница 108: ...60 ...
Страница 109: ...61 ...
Страница 110: ...62 ...
Страница 111: ...63 ...
Страница 112: ...64 ...
Страница 114: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax ...
Страница 117: ......
Страница 118: ......
Страница 119: ......
Страница 121: ...WB1 QF B QF A ...
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 128: ......
Страница 129: ...QF A QF B ...
Страница 130: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......