PART I: SPECIFICATIONS
9
How to read the burner “Performance curve”
To check if the burner is suitable for the boiler to which it must be instal-
lled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h/860);
backpressure (data are available on the boiler ID plate or in the
user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4 mbar
In the “Performance curve” diagram, draw a vertical line matching the
furnace input value and an horizontal line matching the backpressure
value. The burner is suitable if the intersection point A is inside the per-
formance curve.
Data are referred to standard conditions: atmospheric pressure at 1013
mbar, ambient temperature at 15° C.
Checking the proper gas train size
Performance Curves
To get the input in kcal/h, multiply value in kW by 860.
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15° C
NOTE:
The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests, but does not
represent the regulation range of the machine. On this diagram the maximum output point is usually reached by adjsuting the combustion head to its
To check the proper gas train size, it is necessary to the available
gas pressure value upstream the burner’s gas valve. Then subtract
the backpressure. The result is called
pgas.
Draw a vertical line
matching the furnace input value (600kW, in the example), quoted
on the x-axis, as far as intercepitng the network pressure curve,
according to the installed gas train (DN65, in the example). From the
interception point, draw an horizontal line as far as matching, on the
y-axis, the value of pressure necessary to get the requested furnace
input. This value must be lower or equal to the
pgas
value, calcula-
ted before.
PRESSURE IN
COMBUSTION CHAMBER
(mba
r)
K750A M-
kW
PRESSURE IN
COMBUSTION CHAMBER (mb
ar)
K890A M-
kW
K990A M-
kW
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
-1
0
1
2
3
4
5
6
7
8
100
200
300
400
500
600
700
800
900
Potenza kW
Contropressione in camera di
combustione mbar
A
ba
ckpr
essu
re in
co
m
bu
st
ion
ch
am
b
e
r
(m
b
ar
)
Power kW
0
5
10
15
20
25
100
200
300
400
500
600
700
800
900
Potenza / Output (kW)
Minima pressione gas in
rete / Minimum inlet gas
pressure (mbar)
Rp 2" (50)
DN65
Power kW
minimu
m
ga
s pr
essur
e
in
the ne
twork mbar
DN65
Содержание K750A
Страница 1: ...M039462NB 0 1 11 2021 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES K750A K890A K990A...
Страница 2: ...2 1 CO 2 a a RESET 3 3a...
Страница 34: ...34...
Страница 35: ......
Страница 37: ...LME73 000Ax PME73 831AxBC LME73 831AxBC M12921NB Rel 1 2 02 2016...
Страница 41: ...5 Info EK LME73 I LED EK LED 1 2 2 LED tw OFF OK OK T Led Led Led Led Led...
Страница 42: ...6 1 515 1 259 01 0...
Страница 43: ...7 2 515 1 259 01 0...
Страница 48: ...12 2x 23 21 23 F A code Service OEM info enter Info Service enter reset ESC...
Страница 49: ...13 Info LME73 Info Service...
Страница 52: ...16...
Страница 57: ...21 41 42 60 123 140 242 243 244 245 259 01 SO OEM LME73 831AxBC...
Страница 58: ......
Страница 59: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......