Main Trial for Ignition Period [0:1:15seconds] 

Up to 15 seconds may be configured for main trial for ignition. This time should be selected to meet the 
requirements  of  the  governing  codes  in  the  end  users  jurisdiction.  This  time  will  be  used  in  direct 
ignition  mode,  interrupted  pilot  and  continuous  pilot  if  a  main  flame  detection  source  is  configured. 
During MTFI the main flame must be proven. If not proven, direct ignition systems shall have all outputs 
de-energized,  interrupted  and  continuous  pilot  systems  shall  have  DO2  and  DO3  de-energized.  If  the 
system is not configured to retrial/recycle this results in lock out requiring a reset. 

6.9

 

Main Flame Stabilization Period [0:1:10seconds] 

During MTFI, on detection of a flame the main flame stabilizastion timer shall be executed. On expiry of 
this timer, if the flame remains proven the MTFI is successful.  

6.10

 

Pilot Flame Failure Response Time [0:1:4seconds] 

On  loss  of  pilot  flame  a  flame  failure  response  timer  may  be  configured  during  which  the  IGN output 
shall  re-energize  to  recover  the  pilot  flame.  If  successful  the  DO2  and  DO3  status  outputs  remain 
energized,  if  not  successful  the  module  will  adopt  the  lock-out  state  unless  recycle/retrials  are 
configured. 

6.11

 

Main Flame Failure Response Time [0:1:4 seconds] 

On loss of main flame a flame failure  response  timer may be configured during which the IGN output 
shall  re-energize  to  recover  the  main  flame.  If  successful  the  DO2  and  DO3  status  outputs  remain 
energized,  if  not  successful  the  module  will  adopt  the  lock-out  state  unless  recycle/retrials  are 
configured. 

6.12

 

Pilot Recycle/Retrial Number [0-255] 

If  permitted  by  the  governing  codes  of  the  end-user  jurisdiction  the  module  may  be  configured  to 
recycle/retry  for  ignition  on  a  loss  of  flame.  If  configured  all  outputs  shall  be  de-energized  on  loss  of 
flame and interpurge  timer executed prior to re-attempting ignition. If flame  is successfully recovered 
the  recycle/retrial  counts  reset.  If  not  successful  the  number  of  retrials/recycles  executed  shall 
increment up to the configured maximum before adopting the lock out state. 

6.13

 

Pilot Interpurge Duration [0:1:1800seconds] 

Pilot  interpurge  is executed during recycle/retrial for ignition of the  pilot  flame (or main during direct 
ignition). All outputs are de-energized to allow the purging of combustible mixture from the appliance. 

6.14

 

Main Recycle/Retrial Number [0-255] 

If  permitted  by  the  governing  codes  of  the  end-user  jurisdiction  the  module  may  be  configured  to 
recycle/retry for ignition of the main on a loss of main flame. If configured DO2 and DO3 outputs shall 
be de-energized on loss of flame and the main interpurge timer executed prior to re-attempting ignition. 
If  flame  is  successfully  recovered  the  recycle/retrial  counts  reset.  If  not  successful  the  number  of 
retrials/recycles executed shall increment up to the configured maximum before adopting the lock out 
state.  This  option  is  valid  on  continuous  or  interrupted  pilot  systems  where  a  main  flame  detection 
source has been configured. 

6.15

 

Main Interpurge Duration [0:1:1800seconds] 

Main interpurge is executed during recycle/retrial for ignition of the main flame DO2 and DO3 outputs 
are de-energized to allow the purging of combustible mixture from the appliance. 

Содержание SUPERVISOR I

Страница 1: ...0014_Installation_Operation_Manual A0 www unifire ca support unifire ca Copyright 2017 Unifire SUPERVISOR I Installation and Operation Manual...

Страница 2: ...9 MAIN FLAME STABILIZATION PERIOD 0 1 10SECONDS 9 6 10 PILOT FLAME FAILURE RESPONSE TIME 0 1 4SECONDS 9 6 11 MAIN FLAME FAILURE RESPONSE TIME 0 1 4 SECONDS 9 6 12 PILOT RECYCLE RETRIAL NUMBER 0 255 9...

Страница 3: ...n manuals HAZARD A specific hazard is brought to the attention of the reader Failure to observe these instructions may result in injury or other high severity consequence CAUTION Important information...

Страница 4: ...strict product liability for any losses damages costs inconveniences and expenses direct or indirect arising from the use of the product or from defects in workmanship or materials This warranty appli...

Страница 5: ...lease contact the Unifire support team using your preferred method below Please include the serial number on the label of the Supervisor I module in your communications to allow us to help you as quic...

Страница 6: ...ng light off and once the burner s are in operation the permissive inputs continue to provide a trip mechanism for safe shutdown of the appliance With all permissive inputs proven a factory configured...

Страница 7: ...ure 60 C Power Supply 24VDC Quiescent Current TBD Inputs AI TC DI1 DI2 DI3 DO2 DO3 4 20mA Analogue Process Input Thermocouple Type K 50 C 1200 C 12 24VDC Process Permissive 12 24VDC Start Reset 12 24V...

Страница 8: ...Source TC FR DI3 If not configured for direct ignition the input to use for the pilot flame safeguard is selected from the TC thermocouple FR Flame Rod or DI3 Flame Scanner inputs 6 5 Pilot Trial for...

Страница 9: ...not successful the module will adopt the lock out state unless recycle retrials are configured 6 12 Pilot Recycle Retrial Number 0 255 If permitted by the governing codes of the end user jurisdiction...

Страница 10: ...nsmitter Enable Disable The AI input may be used as a fuel pressure transmitter When enabled the transmitter high and low trip setpoints shall be monitored during light off Typically the transmitter w...

Страница 11: ...s to prevent damage to the enclosure Figure 1 Dimensions Mounting Kit Small Brackets Medium Brackets Large Brackets Unless requested at the point of ordering the module shall not come pre drilled for...

Страница 12: ...s head screws that fasten the baseplate to the enclosure body CAUTION The internal electronics are sensitive to static discharge Care must be taken when handling the electronics to avoid exposure to s...

Страница 13: ...d 3 2 GND4 Appliance Ground 4 For connecting to appliance ground Separated from the 0VDC of the module Reserved Reserved Reserved Reserved Reserved Discrete 24VDC Input for connection to process trips...

Страница 14: ...an be checked with a multi meter without removing the boards from the enclosure Figure 5 Fuse Test Points To replace fuses it is recommended that the electronics assembly is removed from the enclosure...

Страница 15: ...d box Load box field jumper 0VDC FR BRN IGN COM DO2 DO2 COM DO3 DO3 COM DO1 COM COMM1 COMM1 COM COMM2 COMM2 COM DI1 DI2 DI3 24VDC TC TC COM 24VDC max 24mA AI COM reserved 24VDC 24VDC graphic overlay P...

Страница 16: ...at all times Outputs FR IGN DO1 DO2 DO3 2 If the FLAME LED is ON all requests to start the system will be ignored until the flame is removed FR IGN DO1 DO2 DO3 3 If the FAULT LED is ON the system is i...

Страница 17: ...nd the Ignition IGN output is de energized FR IGN DO1 DO2 DO3 8 On expiry of the flame stable timer the DO2 and DO3 outputs are Energized The system now monitors for flame continuously until STANDBY R...

Страница 18: ...me is detected the FLAME LED is held ON and the Ignition IGN output is de energized FR IGN DO1 DO2 DO3 5 On expiry of the flame stable timer the DO2 and DO3 outputs are Energized FR IGN DO1 DO2 DO3 6...

Страница 19: ...tton to reset the system Power cycling the module also resets the system In the lock out state all outputs are de energized except for the Flame Rod FR The FAULT LED will flash a number of times that...

Страница 20: ...Thermocouple input trip TAHH 6 AI PALL Low Pressure Trip on the AI Input 7 AI PAHH High Pressure Trip on the AI Input 8 DI Input failure Internal hardware software diagnostic indicates failure of DI1...

Страница 21: ...0014_Installation_Operation_Manual Draft www unifire ca support unifire ca Page 21 of 22 Copyright 2017 Unifire 10 Troubleshooting To follow...

Страница 22: ...0014_Installation_Operation_Manual Draft www unifire ca support unifire ca Page 22 of 22 Copyright 2017 Unifire END OF MANUAL...

Отзывы: