Page 51
24.0
APPENDIX J – 2001, 2002 ANCILLARY LOGGER CONNECTIONS
24.1
Ancillary Logger Setup
The NRT/NRM can use its internal Micrologger component for logging, and it can also
address an ancillary logger. The procedure is detailed below
This setup is an advanced configuration and we strongly suggest you contact the
support team at Unidata if you wish to use this feature to confirm the setup
requirements.
In Neon update internal logger with a dummy scheme and a 1minute FPO file.
In Starlog V4 initialise the NRT/NRM.
Then once the NRT/NRM is correctly running, standalone, connect it to an ancillary logger
via a NRT/NRM cable (2602C) joined to a PC communications cable.
In Neon update ancillary logger with scheme.
Wait…
Within a couple of minutes on next communications the ancillary logger will be initialised
with the new scheme.
24.2
Ancillary Logger Cable
An ancillary data logger can also be connected to an NRT/NRM via a 2602A cable as
shown on the next page.
The cable is connected from the computer communication port of the external logger to
the RS232 serial port on the FTS.