33
Technical features and dimensions
3.16 - STANDARD PANEL BOARD
fig. 28
11 Main switch with indicator light
12Burner switch
13System pump switch
31Safety thermostat
32Working thermostat
41General fuse
42Boiler thermometer
Ta Room thermostat
Te1 Working thermostat stage 1
(60°C÷90°C)
Te2 Working thermostat stage 2
(54°C÷84°C)
Tm Minimum thermostat (50°C)
PhFase (230V ~50Hz)
N Neutral
F1General fuse (max 4A)
Ib Burner switch
IG Main switch with indicator light
Ipi System pump switch
fig. 29
Ts Safety thermostat (100°C)
Pi System pump
A Possible repetition of burner block
B Possible working hour counter stage 1
C Possible working hour counter stage 2
If the Room thermostat is mounted, remove
the bridge 11-12
The main switch 11 powers the board and the equipment
connected to it.
The switches 12 and 13 in turn cut power to the burner and to
the system pump.
The thermostat 32 adjusts the working temperature of the
boiler.
The working thermostat is provided with two switching con-
tacts to control the two-stage burners.
The differential between the two contacts is 6°C (not adjusta-
ble).
The minimum thermostat, which can only be accessed after
having lifted the cover of the electric control board, stops the
system pump until the boiler reaches the temperature of 50°C.
The electric power line of the boiler's control board must have
a switch with protective fuses.
For use of the panel board, see the system manager instruction booklet
7-pole plug
Plug stage 2 (optional)
Содержание TRISTAR 3G
Страница 1: ...INSTALLATION AND MAINTENANCE INSTRUCTIONS 00334572 09 15 rev 1 TRISTAR 3G ...
Страница 28: ...28 Technical features and dimensions TRISTAR 3G 1100 1600 fig 24 2 5 3b 3c 9 10 11 7 4a 5 1 4c 4b 3a ...
Страница 45: ...45 Inspections and maintenance ...
Страница 46: ...46 Inspections and maintenance ...
Страница 47: ...47 Inspections and maintenance ...