35
Maintenance instructions
ENGLISH
ATTENTION!
Function reserved for Authorised As-
sistance Centres only.
Some service parameters can be edited
from the control panel:
4.2 - PARAMETERS THAT CAN BE EDITED FROM THE CONTROL PANEL
OK
OK
1
ACTIVATION
By pressing the button (
D
) for 10 seconds, the
function is activated when the key flashes on the
display
NIGHT REDUCTION
VALUES
FROM
TO
TO
DEFAULT
0
(TA -0°)
5
(TA -5°)
30
(TA -30°)
0
(TA -0°)
MAXIMUM HEATING OUTPUT
VALUES
FROM
TO
DEFAULT
0
(Min)
99
(Max)
99
PREHEATING
VALUES
FROM
TO
DEFAULT
0
1
0
EXTERNAL PROBE TEMPERATURE
VALUES
FROM
TO
DEFAULT
0 (
- 20°C)
30 (
+ 10°C)
20
(0°C)
PUMP POST CIRCULATION
VALUES
FROM
TO
DEFAULT
0
(5 min)
1
(ALWAYS)
0
(5 min)
SELECTION
Turn the HEATING knob ‘’B’’
EDITING THE VALUE
Turn the DOMESTIC HOT WATER knob ‘’C’’
The value flashes on the display
CONFIRM SELECTION
Confirm the parameter to be edited by pressing
the unblock key
CONFIRM VALUE
Confirm the value by pressing the unblock key
PARAMETER SELECTION
Go back to section
2
.
2
4
3
5
6