Model UT233: OPERATING MANUAL
36
Negative phase sequence is shown as below figure.
When V1 input terminal, V2 input terminal and V3
input terminal base on the below table connecting
A phase, B phase and C phase, all three phases
voltage are over 100V, LCD displays negative phase
sequence result, as figure 36.
3.
A, B, C phases
V1
A
B
C
V2
C
A
B
V3
B
C
A
Input Terminal
Checking Result
Negative phase sequence
A
B
C
V2 input terminal
corresponding voltage
V1 input terminal
corresponding voltage.
V3 input terminal
corresponding voltage
Figure 36
When any one phaseís voltage has no singal or less
than 100V at 3 phases 4 wires overload mode, the
LCD display missing phase result.
USB interface feature is not valid at this measurement
mode.
4.
5.
Note
Postive and negative phase sequence
checking
voltage range is 100V ~500V.
When testing has been completed, disconnect the
connection between the testing leads and the circuit
under test and remove testing leads from the input
terminals.
Negative phase sequence