Red backlight as warning indication:
Incorrect wire connection will cause negative active power and cause the red backlight to flash.
The red backlight flashes when the measured voltage is >1000VAC and current >1000A.
The red backlight flashes if the phase sequence is inverse.
Analyzing fixed-frequency harmonic:
Long press RANGE button to power on the clamp to HARM position, then the clamp enters
the fixed-frequency harmonic setting interface, as shown below:
Press “MAX MIN” to select ones place, tens place, hundreds place and thousands place of
the value in auxiliary display. Press “ ” or “ ” to change partial values.
When “HOLD” is pressed after the setting is completed, the clamp enters fixed-frequency
harmonic analysis mode, “SET” in auxiliary display and fixed frequency are displayed
alternately for one second, as shown below, other displayed values are same with harmonic
sweeping analysis mode.
To reset fixed-frequency mode of other frequencies, please switch to other positions and
then return to HARM position.
XII. Technical Specifications
Accuracy: ± (a% of r b digits), one-year warranty period
Ambient temperature: 23°C±5°C (73.4°F±9°F); relative humidity:
≤
75%
Note:
The temperature condition of accuracy is 18°C~28°C, the fluctuation range of ambient
temperature keeps within ±1°C. If the temperature is 18°C or >28°C, the additional error of
temperature coefficient is “0.1 × (specified accuracy)/°C”.
To ensure measurement accuracy, please place the measured conductor at the center of the
clamp jaws. Error of ±1.0% of reading will be produced if the measured conductor is not
placed at the center of the clamp jaws.
UT219P User Manual
UT219P User Manual
Note: Other positions are also in fixed-frequency mode.
1. AC current
60.00A
600.0A
1000A
0.01A
0.1A
1A
15Hz~40Hz
±(2.5%+5)
40Hz~70Hz
±(1.5%+3)
±(2.0%+3)
70Hz~1000Hz
±(2.5%+5)
1000A AC
Range
Resolution
Accuracy
Overload
protection
ACA frequency response: 15~1kHz
ACA displayed true RMS, measurement range:
60.00A range: 0.30A~62.00A
600.0A range: 3A~620.00A
1000A range: 30A~1100A
Range to ensure accuracy: 5~100% of Range
PEAK measurement range:
60.00A range: 0.3A~120.0A
600.0A range: 3A~1200A
1000A range: 30A~1500A
PEAK accuracy:
60A position:
40Hz~70Hz: ±(5.0%+15)
70Hz~1kHz: ±(6.5%+15)
600A/1000A position:
40Hz~70Hz: ±(5.0%+5)
70Hz~1kHz: ±(6.5%+5)
PEAK coefficient: <2.0
2. AC voltage
999.9
0.1V
±(2.0%+5)
±(0.7%+3)
±(2.0%+5)
15Hz 40Hz
~
40Hz 70Hz
~
70Hz 1000Hz
~
1000Vrms
Range
Range
Resolution
Resolution
Accuracy
Accuracy
Overload
protection
Overload
protection
ACV input impedance:
≥
2MΩ
ACV frequency response: 15~1kHz
ACV displayed true RMS, measurement range: 30.0V~999.9V
PEAK measurement range: ± (30.0V~1500V)
PEAK accuracy:
40Hz~70Hz: ±(2.5%+5)
15Hz~40Hz; 70~1000Hz: ±(4.0%+5)
PEAK coefficient: <1.5
3. Power
3.1 Active power
±
(
2
.
5
%+
5
)
±(
1
.
7
%+
5
)
±(
2
.
0
%+
5
)
±(
2
.
5
%+
5
)
1000A AC
1000Vrms
60.00kW
600.0kW
1000kW
0.01kW
0.1kW
1kW
15Hz~40Hz
Power factor: 1
40Hz~70Hz
Power factor: 1
70Hz~1000Hz
Power factor: 1