PS4000/PS5000 Touchscreen Programmable Thermostat
Table 3. Installer Set-up Menu. (CONTINUED)
Installer
Set-up
Number
Installer Set-up
Name
s
e
t
o
N
s
g
n
it
t
e
S
Initial
Setting
Record
0360
Heat Pump
Auxiliary Lockout
0-no auxiliary heat lockout.
40°F (4.5°C)
45°F (7°C)
50°F (10°C)
55°F (13°C)
60°F (15.5°C)
Shown if electric is chosen for
PS5000 ONLY.
PS5000 ONLY.
back-up heat source and outdoor
temperature sensor for control is
selected. (See Advanced
Features section for more
information.)
0380
Indoor
Dehumidification
Control
0-No indoor dehumidification control.
1-Dehumidification control activated.
Available on select models. If
dehumidification control is
activated and auto changeover
is selected in Installer Set-up
Number 0300, the deadband
minimum is defaulted to 5°F
(3°C) in Number 0310.
0500
Filter Change
Reminder
0-furnace filter reminder off.
1-10 run time days.
2-30 run time days.
3-60 run time days.
4-90 run time days.
5-120 run time days.
6-365 run time days.
Run time based on call for fan.