OPERATION CHECK
MONITORING SOFTWARE
Figure 6 - location of the USB port
To verify the correct functioning of ZHERO use the
UneSrlCommunication
software.
The USB type B port for ZHERO monitoring is located in the upper left
part, under the main panel, as indicated in the Figure 6.
The UneSrlCommunication software and the relative instruction
manual with le legend of each alarm
"Manual - UneSrlCommunication"
can be downloaded from the site
https: \\ unesrl.com in the
"DOWNLOAD AREA".
The reading of the bits
through UneSrlCommunication must be carried out from the bottom right to the left
upwards.
DETAIL: STATUSCYCLE ALARMS
VERIFY
Figure 7 - Detail of machine states "STATUSCYCLE "
If only those bits are active, the system is working correctly:
Agen0 -
Bit 3
will always be active (not relevant)
Agen8 -
bit 10
will be active until the system has finished
warmup;
Agen8 -
bit 15
will be active if the irradiation sensor is absent;
Agen16 -
bit 18
will always be active for machine status;
Agen16
- bit 22
could be active (not relevant).
DETAIL: WATTMETRO COMMUNICATION
VERIFY
Figure 8 - Wattmeter led light indication
To check the communication between the wattmeter and UNE ZHERO:
Check that the indicator light indicated in Figure 8 on the side is
flashing intermittently.