23
EN
RAPID INSTALLATION
1. Press the <PG> button, the display will go to the first “INST” Installation
menu.
2. Enter the INST menu.
3. Check the BOOM parameter is correct: 3-5 for DIVA.3.
4. Set the position of the barrier in the POS menu, by default it is set as the
RIGHT barrier.
If you want to invert the barriers, consult the “RIGHT/LEFT BARRIER AR-
RANGEMENT paragraph
Once the position is configured of the barrier on the POS menu, the control
unit automatically enters the AUTOSET menu [6].
5. Enter the AUTO menu, confirm with PG.
6. The message UNLK is displayed, release the barrier and manually move
the shaft to bring it to the opening position, the display shows WAIT.
7. After a few seconds, the LOCK message is displayed to relock the barrier.
8. The control unit slowly brings the shaft to the closure position.
9. Two complete manoeuvres are automatically carried out of opening and
closure, at reduced and normal speed, at the end of which the autoset pro-
cedure has terminated.
10. In the PAR and LOG menus, select the operating parameters and logic
required based on the type of installation.
IMPORTANT
:
After each variation in the FSTS, FSTC, SLDO, SLDC, TSMO,
TSMC parameters, the barrier executes a complete opening and closure
manoeuvre to acquire the new current and torque values, the display will
show the “PRG” message
.
Repeat the autoset procedure after each maintenance intervention.