OPERATION: AUTOMATION
OPERATION: AUTOMATION
Your product can be integrated into most control systems using dry contact relays. These instructions are
provided for Automation specialist reference only. Please contact us, or an Automation specialist, before
attempting this change.
If your existing product does not have a DP1U Controller:
•
Unplug and remove the original controller and replace it with a DP1U Controller. DP1U is used to set
the Up
and Down limits in the main control unit.
•
On the DP1U, press the UP arrow to bring to the desired height. Press the DOWN arrow to stop.
Press the S button and within 2 seconds press the 1 button. Memory 1 is now set.
•
Repeat procedure for other Memory positions.
TO AUTOMATE:
Plug in a standard CAT category LAN cable between the Control unit port A1 (or A2) and external relays. Use
the pinouts below to activate the desired action. Note: The lift will only travel to the memory position while the
relay is held. To stop the lift release the relay contact.
CONTROL BOX PINOUT:
Function
Pins
Colour (T568A)
Colour (T568B)
Up
4 & 5
Blue & Blue/White
Blue & Blue/White
Down
4 & 8
Blue & Brown
Blue & Brown
Store
2 & 8
Green & Brown
Orange & Brown
Memory 1
3 & 5
Orange/White &
Blue/White
Green/White & Blue/White
Memory 2
3 & 8
Orange/White & Brown
Green/White & Brown
Memory 3
2 & 5
Green & Blue/White
Orange & Blue/White
DPU1 CONTROLLER
STANDARS CAT LAN CABLE