Ultra-Aire SD12 Скачать руководство пользователя страница 9

9

Ultra-Aire SD12 Installer’s & Owner’s Manual

FOR HVAC INSTALLER ONLY

9.  Carefully torque the flare nuts to the corresponding flare fittings 

on the condensing unit valves.

• Torque the liquid line flare nut to 13.3 ft-lbs.
• Torque the suction line flare nut to 30.1 ft-lbs.

10. Reinstall service valve cores and caps.

Note

 – Alternately, the stubs with the flare fittings can be connected 

to the condensing unit before brazing the line set. In this case a field 
provided heat shield, such as a wet rag, must be placed over the 
flare fittings and valves on the condensing unit to protect them from 
heat damage. The service valve cap and core should be removed 
before brazing near stub tubes.

3.5 Leak Test Line Set and Dehumidifier

Manifold Gage Set - When checking the system charge, use a  
manifold gage set that features low loss anti-blow back fittings. 

Manifold gage set used with HFC-410A refrigerant systems must 
be capable of handling the higher system operating pressures. The 
gages should be rated for use with high side operating pressures 
of 0 – 800 psig and low side operating pressures of 30 inches of 
vacuum to 250 psig. Dampened gages or anti-flutter gages are 
recommended. Gage hoses must be rated for use at up to 800 psig 
of pressure with a 4000 psig burst rating.

 IMPORTANT!

 

 

THE ENVIRONMENTAL PROTEC-

TION AGENCY (EPA) PROHIBITS THE INTENTIONAL VENTING OF 
HFC REFRIGERANTS DURING MAINTENANCE, SERVICE, REPAIR 
AND DISPOSAL OF APPLIANCE. APPROVED METHODS OF  
RECOVERY, RECYCLING OR RECLAIMING MUST BE FOLLOWED.

 WARNING!

 

 

WHEN USING A HIGH PRESSURE GAS 

SUCH AS DRY NITROGEN TO PRESSURIZE A REFRIGERATION OR 
AIR CONDITIONING SYSTEM, USE A REGULATOR THAT CAN CON-
TROL THE PRESSURE DOWN TO 1 OR 2 PSIG.

 IMPORTANT!

 

 

LEAK DETECTOR MUST BE CA-

PABLE OF SENSING HFC REFRIGERANT.

 WARNING!

 

 

REFRIGERANT CAN BE HARMFUL IF 

IT IS INHALED. REFRIGERANT MUST BE USED AND RECOVERED 
RESPONSIBLY. FAILURE TO FOLLOW THIS WARNING MAY RESULT 
IN PERSONAL INJURY OR DEATH.

1.  Connect the HFC-410A manifold gage set high pressure hose to 

the service port on the suction gas line. 

Note

 – Connecting the high pressure hose to the service port on 

the gas line will protect the manifold gage set from high pressure 
damage during leak testing. Cap liquid line service port.

2.  Make sure all of the valves on the manifold gage set are closed. 

Connect a cylinder of HFC-410A refrigerant to the center port of 
the manifold gage set.

3.  Position the HFC410A refrigerant cylinder to deliver vapor only. 

Open the valve on the HFC-410A refrigerant cylinder.

4.  Open the high pressure side of the manifold gage set to allow 

HFC-410A into the line set and dehumidifier. Weigh in a trace 
amount of HFC-410A [A trace amount is a maximum of two 
ounces (57g) of refrigerant or 3 PSI]. Close the valve on the 
HFC-410A cylinder and the valve on the high pressure side of the 
manifold gage set.

5.  Disconnect the HFC-410A refrigerant cylinder from the manifold 

gage set.

6.  Connect a cylinder of dry nitrogen with a pressure regulating 

valve to the center port of the manifold gage set.

7.  Adjust the dry nitrogen pressure regulator to 150 psig. Open the 

valve on the high pressure side of the manifold gage set to  
pressurize the line set and dehumidifier.

8.  Close the valve on the dry nitrogen cylinder. Close the valve on 

the high pressure side of the manifold gage set. 

9. Allow the system to rest for a few minutes.
10.  Check all (brazed and threaded) joints for leaks using a leak 

detector designed to sense HFC refrigerants.

11.  After leak testing is complete, disconnect the dry nitrogen cylin-

der from the center port of the manifold gage set and discon-
nect the high pressure hose of the manifold gage set from the 
suction gas line service port.

LOW

HIGH

MANIFOLD GAUGE SET

NITROGEN

HFC-410A

TO VAPOR

SERVICE VALVE

OUTDOOR UNIT

3-WAY VALVE

2-WAY VALVE

LIQUID LINE STUB

GAS LINE STUB

SERVICE VALVE CAPS

VALVE ROD CAPS

VALVE STEMS

FIGURE 9

FIGURE 10: LEAK CHECK

Содержание SD12

Страница 1: ...her temperature to provide additional cooling if needed By eliminating the HVAC system s need to control latent load the Ultra Aire SD12 allows the system to work more efficiently Fresh Air Ventilatio...

Страница 2: ...tallation in an Attic with an Existing Forced Air HVAC System 13 3 9F Installation in a Structure with Two Forced Air HVAC Systems 13 3 9G Installation in a Structure with No Existing Forced Air HVAC...

Страница 3: ...y before installing and operating this device Proper adherence to these instructions is essential to obtain maximum benefit from your Ultra Aire SD12 indoor air quality system WARNING IMPROPER INSTALL...

Страница 4: ...ed living area or above an area where water leakage could cause damage Place the Ultra Aire SD12 on supports that raise the base of the unit 2 5 above the drain pan beneath it Raising the Ultra Aire S...

Страница 5: ...IN DAMAGE TO ROOF SURFACE Mount the base of the condensing unit to a sturdy level pad or bracket using 3 8 10mm bolts The condensing unit may be mounted to a wall with brackets or placed on a roof En...

Страница 6: ...sunlight or near a pool or spa The installer must supply the control wiring between the Ultra Aire SD12 dehumidifier the condensing unit the remote control and any electrical accessories Carefully rou...

Страница 7: ...er use either metal strapping material or anchored heavy nylon wire ties ANCHORED HEAVY NYLON WIRE TIRE OR AUTOMOTIVE MUFFLER TYPE HANGER AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD STRAP LIQUID LINE TO...

Страница 8: ...stub tubes of condensing unit These service ports can be used to introduce and release nitrogen during brazing Use the following procedure to connect the line set to the Dehumidifier CAUTION THE DEHU...

Страница 9: ...COVERED RESPONSIBLY FAILURE TO FOLLOW THIS WARNING MAY RESULT IN PERSONAL INJURY OR DEATH 1 Connect the HFC 410A manifold gage set high pressure hose to the service port on the suction gas line Note C...

Страница 10: ...to charge the system FOR HVAC INSTALLER ONLY 3 7 Charging the System The condensing unit is pre charged with 42 oz of HFC 410A refrigerant The installer will add HFC 410A refrigerant for the dehumidif...

Страница 11: ...parate supply duct from the Ultra Aire SD12 to each isolated area is recommended DO NOT draw air directly from the kitchen laundry or isolated basement You may draw air from a basement that is open to...

Страница 12: ...ter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on the...

Страница 13: ...the struc ture such as bedrooms den etc By ducting this way the air inside the structure will circulate through the Ultra Aire SD12 to be filtered and dehumidified Avoid discharging all the air from...

Страница 14: ...AMAGE the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green wires Accessory power 24volt AC power supply available for HVAC accessories between yellow and...

Страница 15: ...t 35 min 70 max Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 F Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n Fan Filt...

Страница 16: ...during the seasons when there are many particles in the outdoor air 6 5 Condensing Unit Maintenance The compressor and fan motor inside the condensing unit are permanently lubricated for many years o...

Страница 17: ...nplugged or no power to outlet 2 Loose connection in dehumidifier fan circuit 3 Obstruction prevents fan impeller rotation 4 Defective fan 5 Defective fan relay 6 Defective impeller run capacitor Low...

Страница 18: ...t be replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 FOR HVAC INSTALLER ONLY scale the capacitor is open and must be replaced 4 Mar...

Страница 19: ...or and an over sized liquid line filter In a running burn out install an oversized suction line filter drier be tween the accumulator and compressor Thoroughly flush the accumu lator with refrigerant...

Страница 20: ...ng is correct and that voltage is present at the damper motor 2 Check for any obstruction inside the damper If the electric ventilation damper fails to operate after performing these checks it must be...

Страница 21: ...CE PARTS LIST Condensing Unit Item Part No Qty Description 2 4033211 1 Nut 3 4033212 1 Fan Axial 16 4033213 1 Compressor 20 4033214 1 Capacitor 23 4033216 1 Capacitor Fan Motor 30 4033215 1 Motor 31 4...

Страница 22: ...mounting hardware from inside the rectangle opening Mount the duct collars to the front of the dehumidifier using screws provided Collars and hardware are located here Door Install Insert tab on the...

Страница 23: ...osts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibil...

Страница 24: ......

Отзывы: