Ultra-Aire SD12 Installer’s & Owner’s Manual

FOR HVAC INSTALLER ONLY

Note

 – Check the drain hole in the dehumidifier to verify the opening 

and that it is free of any debris before installing the drain line.

Condensate drains by gravity via the dehumidifier drain port. Often 
the Ultra-Aire SD12 can be connected to the existing air handler 
drain. Use a 3/4” male NPT PVC pipe or adapter to connect to the 
drain port. Route drain pipe to an approved drain. Install a trap in the 
drain line as shown below. Use an adjustable wrench to secure the 
NPT fitting to the drain port. The drain pipe should slope towards the 
drain at least 1 inch for every 10 feet of run.

When installing the drain hose, make sure the dehumidifier feet are 
extended to raise the dehumidifier 2 1/2” above the ground. Coil the 
drain hose under itself or position a spacer to lift the hose 1” off the 
ground after the hose has touched the ground. This procedure will 
create a trap that ensures your dehumidifier drains correctly. Keep 
the hose as flat to the floor as possible. Excessive humps or kinks 
will prevent proper drainage.

An optional condensate pump kit may be installed if a lift is re-
quired to dispose of the condensate. The condensate pump kit can 
be ordered directly from the factory. See the optional parts list for 
information on the kit.

3.9 Ducting 

3.9A Installing Duct Collars 

The Ultra-Aire SD12 is equipped with 10” and 6” round inlet collars 
and a 10” round (ovaled) exhaust collar. Follow instructions included 
with collars.

3.9B Ducting for Dehumidification 

For the ideal installation, draw air from the central part of the home 
and return it to the isolated areas of the home like the bedrooms, 
den, utility room, or family room. The ductwork of the existing HVAC 
system can be used to supply air to the home. If the existing supply 
goes to isolated areas of the home, discharge the supply of the 
Ultra-Aire SD12 into the supply of the existing HVAC system. If the 
existing heating system incorporates a central supply, installation 
of a separate supply duct from the Ultra-Aire SD12 to each isolated 
area is recommended. DO NOT draw air directly from the kitchen, 
laundry, or isolated basement. You may draw air from a basement 
that is open to the home. All flexible ducting connected to the Ultra-
Aire SD12 should be UL listed. 

The inlet of the Ultra-Aire SD12 is the 10” diameter hole in the filter 
enclosure of the unit. A 10” round collar is supplied with the unit to 
attach to round duct. The duct may be permanently attached to the 
collar. A 6” round collar is provided with the unit to attach to the 6” 
hole in the filter enclosure. The 6” collar should be capped if fresh 
make-up air is not desired. If fresh make-up air is desired, see Sec-
tion 3.9C. 

A 10” round (ovaled) collar is supplied with the unit for the outlet of 
the Ultra-Aire SD12.  

A length of flexible ducting on all Ultra-Aire SD12 duct connections 
is recommended to reduce noise and vibration transmitted to rigid 
ductwork in the structure. 

Ducting the Ultra-Aire SD12 as mentioned in Sections 3.9A-3.9G 
requires consideration of the following points: 

Duct Sizing: 

For total duct lengths up to 25’, use a minimum 10” 

diameter round or equivalent rectangular. For longer lengths, use a 
minimum 12” diameter or equivalent. Grills or diffusers on the duct 
ends must not excessively restrict airflow. 

Isolated Areas:

 Effective dehumidification may require that ducting 

be branched to isolated, stagnant areas. Use 8” or larger diameter 
branch ducting to each of two or three areas, use 6” or larger to 
each of four or more areas. 

Connecting to existing HVAC systems: 

An optional 10” check 

damper is available from the factory to prevent reverse flow through 
the Ultra-Aire SD12. If the Ultra-Aire SD12 is ducted to the sup-
ply ducting of the HVAC system, it is recommended that the check 
damper be placed in the Ultra-Aire SD12 supply duct. Contact the 
factory when connecting to a static pressure of greater than or equal 
to +.5” WG. 

VENT MUST EXTEND ABOVE THE HEIGHT 
OF THE DRAIN BY 2 INCHES.

TRAP MUST BE DEEP ENOUGH TO 
OFFSET MAXIMUM STATIC DIFFERENCE 
(GENERALLY, 2 INCHES).

DRAIN LINE SHOULD SLOPE A 
MINIMUM 1 INCH PER 10 FEET 

TO APPROVED DRAIN

DEHUMIDIFIER

VENT

FIGURE 13A: HARD PIPE DRAIN

FIGURE 13B: FLEXIBLE PIPE DRAIN

Содержание SD12

Страница 1: ...her temperature to provide additional cooling if needed By eliminating the HVAC system s need to control latent load the Ultra Aire SD12 allows the system to work more efficiently Fresh Air Ventilatio...

Страница 2: ...tallation in an Attic with an Existing Forced Air HVAC System 13 3 9F Installation in a Structure with Two Forced Air HVAC Systems 13 3 9G Installation in a Structure with No Existing Forced Air HVAC...

Страница 3: ...y before installing and operating this device Proper adherence to these instructions is essential to obtain maximum benefit from your Ultra Aire SD12 indoor air quality system WARNING IMPROPER INSTALL...

Страница 4: ...ed living area or above an area where water leakage could cause damage Place the Ultra Aire SD12 on supports that raise the base of the unit 2 5 above the drain pan beneath it Raising the Ultra Aire S...

Страница 5: ...IN DAMAGE TO ROOF SURFACE Mount the base of the condensing unit to a sturdy level pad or bracket using 3 8 10mm bolts The condensing unit may be mounted to a wall with brackets or placed on a roof En...

Страница 6: ...sunlight or near a pool or spa The installer must supply the control wiring between the Ultra Aire SD12 dehumidifier the condensing unit the remote control and any electrical accessories Carefully rou...

Страница 7: ...er use either metal strapping material or anchored heavy nylon wire ties ANCHORED HEAVY NYLON WIRE TIRE OR AUTOMOTIVE MUFFLER TYPE HANGER AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD STRAP LIQUID LINE TO...

Страница 8: ...stub tubes of condensing unit These service ports can be used to introduce and release nitrogen during brazing Use the following procedure to connect the line set to the Dehumidifier CAUTION THE DEHU...

Страница 9: ...COVERED RESPONSIBLY FAILURE TO FOLLOW THIS WARNING MAY RESULT IN PERSONAL INJURY OR DEATH 1 Connect the HFC 410A manifold gage set high pressure hose to the service port on the suction gas line Note C...

Страница 10: ...to charge the system FOR HVAC INSTALLER ONLY 3 7 Charging the System The condensing unit is pre charged with 42 oz of HFC 410A refrigerant The installer will add HFC 410A refrigerant for the dehumidif...

Страница 11: ...parate supply duct from the Ultra Aire SD12 to each isolated area is recommended DO NOT draw air directly from the kitchen laundry or isolated basement You may draw air from a basement that is open to...

Страница 12: ...ter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on the...

Страница 13: ...the struc ture such as bedrooms den etc By ducting this way the air inside the structure will circulate through the Ultra Aire SD12 to be filtered and dehumidified Avoid discharging all the air from...

Страница 14: ...AMAGE the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green wires Accessory power 24volt AC power supply available for HVAC accessories between yellow and...

Страница 15: ...t 35 min 70 max Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 F Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n Fan Filt...

Страница 16: ...during the seasons when there are many particles in the outdoor air 6 5 Condensing Unit Maintenance The compressor and fan motor inside the condensing unit are permanently lubricated for many years o...

Страница 17: ...nplugged or no power to outlet 2 Loose connection in dehumidifier fan circuit 3 Obstruction prevents fan impeller rotation 4 Defective fan 5 Defective fan relay 6 Defective impeller run capacitor Low...

Страница 18: ...t be replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 FOR HVAC INSTALLER ONLY scale the capacitor is open and must be replaced 4 Mar...

Страница 19: ...or and an over sized liquid line filter In a running burn out install an oversized suction line filter drier be tween the accumulator and compressor Thoroughly flush the accumu lator with refrigerant...

Страница 20: ...ng is correct and that voltage is present at the damper motor 2 Check for any obstruction inside the damper If the electric ventilation damper fails to operate after performing these checks it must be...

Страница 21: ...CE PARTS LIST Condensing Unit Item Part No Qty Description 2 4033211 1 Nut 3 4033212 1 Fan Axial 16 4033213 1 Compressor 20 4033214 1 Capacitor 23 4033216 1 Capacitor Fan Motor 30 4033215 1 Motor 31 4...

Страница 22: ...mounting hardware from inside the rectangle opening Mount the duct collars to the front of the dehumidifier using screws provided Collars and hardware are located here Door Install Insert tab on the...

Страница 23: ...osts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibil...

Страница 24: ......

Отзывы: