Ultra-Aire SD12 Скачать руководство пользователя страница 5

5

Ultra-Aire SD12 Installer’s & Owner’s Manual

FOR HVAC INSTALLER ONLY

3.1B Condensing Unit Location

The condensing unit should be located outside of the conditioned 
space, but as close as possible to the dehumidifier to minimize the 
length of the connecting lines. The maximum line set length is 50 feet. 
In all cases keep the following cautions in mind:
• Install the condensing unit with space to access the top and side pan-
els for maintenance and service. DO NOT INSTALL CONDENSING UNIT 
WITH THE TOP PANEL OR SIDE PANELS INACCESSIBLE (See FIGURE 2 for 
diagram).
• Avoid discharging air directly at people, or over the water near pool 
areas.
• If used near a pool or spa, be certain there is NO chance the  
condensing unit could fall into the water or be splashed and that it is  
supplied by a GROUND FAULT INTERRUPTER. 
• Place the condensing unit where it is protected from extreme outdoor 
weather (rain, wind, etc…)
• Place the condensing unit on a level pad (or bracket) where the unit 
can be securely attached by the base.
• Place the condensing unit at least 1” above ground level
• Place the condensing unit where there is adequate space for the unit 
and the air required by the unit
• DO NOT place the condensing unit where the sound and vibration 
caused by the running unit will cause a nuisance.
• DO NOT use the condensing unit as a bench or table. 
• DO NOT place the condensing unit in direct sunlight.
• The minimum installation clearances for the condensing unit are  
shown below.

 

 ROOF DAMAGE!

 

THIS SYSTEM CONTAINS 

BOTH REFRIGERANT AND OIL. SOME RUBBER ROOFING MATERIAL 
MAY ABSORB OIL AND CAUSE THE RUBBER TO SWELL WHEN IT 
COMES INTO CONTACT WITH OIL. THE RUBBER WILL THEN BUBBLE 
AND COULD CAUSE LEAKS. PROTECT THE ROOF SURFACE TO 
AVOID EXPOSURE TO REFRIGERANT AND OIL DURING SERVICE AND 
INSTALLATION. FAILURE TO FOLLOW THIS NOTICE COULD RESULT  
IN DAMAGE TO ROOF SURFACE.

Mount the base of the condensing unit to a sturdy level pad (or bracket) 
using 3/8” (10mm) bolts. The condensing unit may be mounted to a 
wall (with brackets) or placed on a roof. Ensure the mounting of the 
condensing unit can withstand strong winds and earthquakes when 
mounting above ground level. Vibration dampening material may be 
installed between the condensing unit base and the mounting pad if 
required. The base dimensions of the condensing unit are shown in 
FIGURE 2.

3.2 Electrical Requirements 

 WARNING!

 

ELECTRIC SHOCK HAZARD. CAN CAUSE 

INJURY OR DEATH. UNIT MUST BE GROUNDED IN ACCORDANCE 
WITH NATIONAL AND LOCAL CODES. DISCONNECT ALL REMOTE 
ELECTRIC POWER SUPPLIES BEFORE OPENING ACCESS PANEL.  
UNIT MAY HAVE MULTIPLE POWER SUPPLIES.

Field wiring must comply with the National Electric Code (C.E.C. in 
Canada) and any applicable local codes or ordinances.

 WARNING!

 

DO NOT ALLOW THE YELLOW LEAD TO 

CONTACT THE RED LEAD OR WHITE LEAD FROM THE ULTRA-AIRE 
DEHUMIDIFIER OR THE TRANSFORMER WILL BE DAMAGED.

3.2A Dehumidifier Electrical Power Connections

The Ultra-Aire SD12 Dehumidifier unit plugs into a common 120Vac 
grounded outlet. The Dehumidifier draws less than 2A and can be 
plugged into a shared branch circuit. If installed in a wet area (or 
basement prone to flooding), a ground fault interrupter protected 
circuit is required (See FIGURE 3 for schematic).

4033178

LINE

NEUTRAL

DEHU.

RELAY

BLOWER

RELAY

BLOWER

XFMR

DEHU.

RELAY

COIL

BLOWER

RELAY

COIL

DEFROST

T-STAT

L. PRESS

SWITCH

RUN

CAP.

NC

NO

YEL-6

BLU-7

GRN-5

PNK

-3

WHT

-4

RED-1

YEL-2

BLK-9

BLK-8

BLK

BLK

BLK-3

WHT

-5

BLK-2

BL

U-2

115V

24V

COM

COM

BRN-3

BLK-1

BLK

-1

+24VAC

DEHU

FAN

COM

CUSTOMER

CONTROL

WIRING

BLU

YEL

GRN

RED

BLK

BLK

24VAC TO

COND.

GRN-4

NO

BLK-5

VIO-6

MIN

5.88 IN

MIN

7.88 IN

MIN

23.63 IN

MIN

9.88 IN

10.06

5.62

19.69

5.62

GRAPHIC SHOWS MINIMUM DISTANCE REQUIRED FOR 
CONDENSING UNIT AND THE FOOTING DIMENSIONS

FIGURE 2: MINIMUM DISTANCE REQUIRED FOR CONDENSING 
UNIT AND THE FOOTING DIMENSIONS

FIGURE 3: DEHUMIDIFIER WIRING DIAGRAM

Содержание SD12

Страница 1: ...her temperature to provide additional cooling if needed By eliminating the HVAC system s need to control latent load the Ultra Aire SD12 allows the system to work more efficiently Fresh Air Ventilatio...

Страница 2: ...tallation in an Attic with an Existing Forced Air HVAC System 13 3 9F Installation in a Structure with Two Forced Air HVAC Systems 13 3 9G Installation in a Structure with No Existing Forced Air HVAC...

Страница 3: ...y before installing and operating this device Proper adherence to these instructions is essential to obtain maximum benefit from your Ultra Aire SD12 indoor air quality system WARNING IMPROPER INSTALL...

Страница 4: ...ed living area or above an area where water leakage could cause damage Place the Ultra Aire SD12 on supports that raise the base of the unit 2 5 above the drain pan beneath it Raising the Ultra Aire S...

Страница 5: ...IN DAMAGE TO ROOF SURFACE Mount the base of the condensing unit to a sturdy level pad or bracket using 3 8 10mm bolts The condensing unit may be mounted to a wall with brackets or placed on a roof En...

Страница 6: ...sunlight or near a pool or spa The installer must supply the control wiring between the Ultra Aire SD12 dehumidifier the condensing unit the remote control and any electrical accessories Carefully rou...

Страница 7: ...er use either metal strapping material or anchored heavy nylon wire ties ANCHORED HEAVY NYLON WIRE TIRE OR AUTOMOTIVE MUFFLER TYPE HANGER AUTOMOTIVE MUFFLER TYPE HANGER WALL STUD STRAP LIQUID LINE TO...

Страница 8: ...stub tubes of condensing unit These service ports can be used to introduce and release nitrogen during brazing Use the following procedure to connect the line set to the Dehumidifier CAUTION THE DEHU...

Страница 9: ...COVERED RESPONSIBLY FAILURE TO FOLLOW THIS WARNING MAY RESULT IN PERSONAL INJURY OR DEATH 1 Connect the HFC 410A manifold gage set high pressure hose to the service port on the suction gas line Note C...

Страница 10: ...to charge the system FOR HVAC INSTALLER ONLY 3 7 Charging the System The condensing unit is pre charged with 42 oz of HFC 410A refrigerant The installer will add HFC 410A refrigerant for the dehumidif...

Страница 11: ...parate supply duct from the Ultra Aire SD12 to each isolated area is recommended DO NOT draw air directly from the kitchen laundry or isolated basement You may draw air from a basement that is open to...

Страница 12: ...ter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on the...

Страница 13: ...the struc ture such as bedrooms den etc By ducting this way the air inside the structure will circulate through the Ultra Aire SD12 to be filtered and dehumidified Avoid discharging all the air from...

Страница 14: ...AMAGE the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green wires Accessory power 24volt AC power supply available for HVAC accessories between yellow and...

Страница 15: ...t 35 min 70 max Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 F Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n Fan Filt...

Страница 16: ...during the seasons when there are many particles in the outdoor air 6 5 Condensing Unit Maintenance The compressor and fan motor inside the condensing unit are permanently lubricated for many years o...

Страница 17: ...nplugged or no power to outlet 2 Loose connection in dehumidifier fan circuit 3 Obstruction prevents fan impeller rotation 4 Defective fan 5 Defective fan relay 6 Defective impeller run capacitor Low...

Страница 18: ...t be replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 FOR HVAC INSTALLER ONLY scale the capacitor is open and must be replaced 4 Mar...

Страница 19: ...or and an over sized liquid line filter In a running burn out install an oversized suction line filter drier be tween the accumulator and compressor Thoroughly flush the accumu lator with refrigerant...

Страница 20: ...ng is correct and that voltage is present at the damper motor 2 Check for any obstruction inside the damper If the electric ventilation damper fails to operate after performing these checks it must be...

Страница 21: ...CE PARTS LIST Condensing Unit Item Part No Qty Description 2 4033211 1 Nut 3 4033212 1 Fan Axial 16 4033213 1 Compressor 20 4033214 1 Capacitor 23 4033216 1 Capacitor Fan Motor 30 4033215 1 Motor 31 4...

Страница 22: ...mounting hardware from inside the rectangle opening Mount the duct collars to the front of the dehumidifier using screws provided Collars and hardware are located here Door Install Insert tab on the...

Страница 23: ...osts related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibil...

Страница 24: ......

Отзывы: