background image

Duct Sizing: 

For total duct lengths up to 25', use a

minimum 8" diameter round or equivalent rectangular. For longer 
lengths, use a minimum 10" diameter or equivalent. Grills or 
diffusers on the duct ends must not excessively restrict air flow.

Isolated Areas:

 Effective dehumidification may require that ducting 

be branched to isolated, stagnant areas. Use 6" or larger diameter 
branch ducting to each of two or three areas; use 4" or larger to 
each of four or more areas.

3.4C Ducting for Fresh Air

Fresh air can be brought into the structure by connecting a duct 
from outside to the 6" Ultra-Aire inlet and by turning on the fan 
switch or activating the humidity control on units with the humidity 
control panel. Activate the ventilation timer on units with the 
ventilating & humidity control panel to bring in fresh air. Advantages 
of this form of ventilation include:

1. Outside air is filtered before entering the building.
2.  Outside air will be dehumidified before entering if the Ultra-

Aire is running.

3.   Drawing air from outside and blowing inside aids in slightly 

pressurizing the structure. This helps prevent unfiltered and 
undehumidified air from entering elsewhere. It also reduces 
the potential for carcinogenic radon gas to enter and provides 
makeup air for open combustion and exhaust devices like the 
clothes drier, fireplace, and water heater.

4.  The need for an alternate ventilation device may be eliminated.

An insulated 6" diameter duct is generally sufficient to provide up 
to 125 CFM of outside air. Large quantities of outside air will impact 
Ultra-Aire performance positively or negatively, depending upon the 
difference between inside and outside air conditions. Consult the 
factory by calling 1-800-533-7533 for recommendations regarding 
the use of higher flows with your specific application. 

The outside air duct should be connected to the 6" round collar 
on top of the unit. The 6" round collar includes a manual damper. 
Adjust the manual damper to provide the desired amount of fresh air 
for ventilation. The amount of fresh air should be based on the size 
and occupancy of the residence. If you are unsure of your ventilation 
air requirements, consult the factory by calling 1-800-533-7533 for 
assistance. 

3.4D Installation in a Basement or Crawlspace with an 

Existing Forced Air HVAC System.

If the structure in which the Ultra-Aire is to be installed has an 
existing forced air HVAC system, utilize the HVAC system to make 
the Ultra-Aire installation easier. 

If the existing system has multiple returns, select one to disconnect 
from the existing forced air system and use it for the dedicated 
Ultra-Aire return. Always select a return from a central location 
in the structure in an area that is always open to the rest of the 

structure. Do not use a return from a room that may have its door 
closed much of the time.

Basement Installation: 

Locate a separate return for the Ultra-Aire 

in a central area of the structure. Duct the supply of the Ultra-Aire 
to a 8" x 8" x 8" tee/damper that is 30% open to the basement. 
Duct the other side of the tee to the air return of the existing HVAC 
system. If the existing HVAC system has a central return, duct the 
other side of the tee to the air supply of the existing HVAC system. 
Connect a duct from outside to the 6" collar of the Ultra-Aire if you 
wish to provide fresh make-up air.

Crawlspace Installation: 

Locate a separate return for the Ultra-

Aire in a central area of the structure. Duct the supply of the 
Ultra-Aire to a 8" x 8" x 8" tee/damper that is 30% open to the 

FOR HVAC INSTALLER ONLY

4

Ultra-Aire 100V Installer’s & Owner’s Manual

Содержание 100V

Страница 1: ...resh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can be regulated by a variety of dampers and controls Air Filtration The UA 100V includes air filtration to improve indoor air quality A MERV 11 media filter is standard An optional MERV 14 deep pleated 95 ...

Страница 2: ...NEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain there is NO chance the unit could fall into the water splashed and that it is plugged into a GFCI GROUND FAULT CIRCUIT INTERRUPT OUTLET DO NOT use the device as a bench or table DO NOT place the device directly on structural members A drain pan MUST be placed under the...

Страница 3: ... building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end of the drain hose An optional condensate pump may be installed if a lift is required to dispose of the condensate The condensate pump kit can be ordered direct from the factory See item 27 on page 21 ...

Страница 4: ... calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on the size and occupancy of the residenc...

Страница 5: ...By ducting this way the air inside the structure will circulate through the Ultra Aire to be filtered and dehumidified Connect a duct from outside to the 6 collar of the Ultra Aire if you wish to provide fresh make up air 3 5 Quiet Installation A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from the blower A length of flexible ducting o...

Страница 6: ...dity Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n Fan Filter Operation n Programmable Ventilation Timer n Large easy to read backlit LCD display n Easy interaction with air handler fan Interlock Lockout n High Temperature Cut Out n Dryout Cycle ...

Страница 7: ... efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Servicing the Ultra Aire with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qualified service people...

Страница 8: ...n by reversing the above procedure 7 6 Compressor Capacitor Replacement This compressor is equipped with a two terminal external overload and a run capacitor but no start capacitor or relay See Figure 4 CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 7 6A Checking Compressor Motor Circuits Perform ...

Страница 9: ... suction line filter driers will probably clean up the system If sludge is evident in the discharge line it will likely be found in the suction line This indicates the compressor burned out will running Sludge and acid have been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that cause...

Страница 10: ...entilation timer is not activated to prevent over ventilating the structure when the unit is dehumidifying or recirculating the indoor air The electric ventilation timer operates on 24 Vac from the control circuit DO NOT connect high voltage to the damper motor or damage to the motor may result DO NOT force the blade of the damper by hand or damage to the damper motor may result The damper opens i...

Страница 11: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM N O WHT WHT 11 Ultra Aire 100V Installer s Owner s Manual ...

Страница 12: ...ly 9 4029168 1 Compressor 10 4029169 1 Compressor Overload 11 4028226 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4029510 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 ID x 8 15 4022484 1 Relay SPST 24 Vac 30A 16 4020924 1 Relay SPDT 24 Vac 15A 17 4033032 05 1 Run Capacitor 45 MFD 370V 18 4025741 1 Thermostat Defrost 4021648 1 Defrost Control Mounting Clip 19 4022487 1 Transformer 120 24 Va...

Страница 13: ... 90 95 4022220 1 Condensate Pump Kit 4023672 1 Damper Duct 6 Diameter Electrically Actuated not shown 4023647 1 Damper Check 8 Diameter not shown 4021475 1 MERV 11 Filter 16 x 20 x 2 4022489 1 MERV 14 Filter 16 x 20 x 4 4022220 1 Pump Kit 4023484 1 Attic Insulation Kit 4023672 1 6 Motorized Damper 4020656 1 6 Inlet Exhaust Hood 4023647 1 8 Gravity Damper 4020646 1 8 Butterfly Damper ...

Страница 14: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the ap...

Страница 15: ...hermastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved ...

Отзывы: