10.   Reconnect the wires to the compressor and capacitor. Plug 

in and turn on the unit. If the compressor fails to start, 
replace the run capacitor.

11.  If the unit still does not start, adding a hard-start kit (relay & 

capacitor) will provide greater starting torque. If this doesn't 
work, the compressor has an internal mechanical defect and 
must be replaced.

7.6B Replacing a Burned Out Compressor

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, when an 
electrical short occurs in the compressor motor, the resulting high 
temperature arc causes a portion of the refrigerant oil mixture to 
break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise 
even small residues will attack replacement compressor motors and 
cause failures.

The following procedure is effective only if the system is monitored after 
replacing the compressor to insure that the clean up was complete.

1.    This procedure assumes that the previously listed compressor 

motor circuit tests revealed a shorted or open winding. If so, 
cautiously smell the refrigerant from the compressor service 
port for the acid odor of a burn out. WARNING: The gas could 
be toxic and highly acidic. If no acid odor is present, skip down 
to the section on changing a non-burn out compressor.

2.    Remove and properly dispose of the system charge. DO NOT 

vent the refrigerant indoors or allow it to contact your eyes 
or skin.

3.    Remove the burned out compressor. Use rubber gloves if there 

is any possibility of contacting the oil or sludge.

4.    To facilitate subsequent steps, determine the type of burn 

out that occurred. If the discharge line shows no evidence 
of sludge and the suction line is also clean or perhaps has 
some light carbon deposits, the burn out occurred while the 
compressor was not rotating. Contaminants are therefore 
largely confined to the compressor housing. A single 
installation of liquid and suction line filter/driers will probably 
clean up the system. If sludge is evident in the discharge line, 
it will likely be found in the suction line. This indicates the 
compressor burned out will running. Sludge and acid have 
been pumped throughout the system. Several changes of the 
liquid and suction filter/driers will probably be necessary to 
cleanse the system.

5.    Correct the system fault that caused the burn out. Consult the 

factory for advice.

6.    Install the replacement compressor with a new capacitor and 

an oversized liquid line filter. In a running burn out, install an 
oversized suction line filter/drier between the accumulator and 

compressor. Thoroughly flush the accumulator with refrigerant 
to remove all trapped sludge and to prevent the oil hole from 
becoming plugged. A standing burn out does not require a 
suction line filter/drier.

7.    Evacuate the system with a good vacuum pump and 

accurate vacuum gauge. Leave the pump on the system for 
at least an hour. 

8.    Operate the system for a short period of time, monitoring the 

suction pressure to determine that the suction filter is not 
becoming plugged. Replace the suction filter/drier if pressure 
drop occurs. If a severe running burn out has occurred, several 
filter/driers may have to be replaced to remove all of the acid 
and moisture. 

NOTE: NEVER use the compressor to evacuate 

the system or any part of it.

7.6C Replacing a Compressor, Nonburn Out

Remove the refrigerant from the system. Replace the compressor 
and liquid line filter/drier. Charge the system to 50 PSIG and check 
for leaks. Remove the charge and weigh in the refrigerant quantity 
listed on the nameplate. Operate the system to verify performance.

7.7 Remote Controls

The Ultra-Aire dehumidifier must be connected to a wall mounted 
controller. Themastor offers the DEH 3000 proprietary controller.  
If the Ultra-Aire fails to operate as desired, always check the 
settings of the controls to insure that they are correct. Check that 
the controls are receiving 24Vac from the Ultra-Aire. Check the 
connections between the Ultra-Aire, the control panel, and the field 
control wiring.

FOR HVAC INSTALLER AND HOMEOWNER

9

Ultra-Aire 100V Installer’s & Owner’s Manual

Содержание 100V

Страница 1: ...resh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can be regulated by a variety of dampers and controls Air Filtration The UA 100V includes air filtration to improve indoor air quality A MERV 11 media filter is standard An optional MERV 14 deep pleated 95 ...

Страница 2: ...NEL INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain there is NO chance the unit could fall into the water splashed and that it is plugged into a GFCI GROUND FAULT CIRCUIT INTERRUPT OUTLET DO NOT use the device as a bench or table DO NOT place the device directly on structural members A drain pan MUST be placed under the...

Страница 3: ... building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end of the drain hose An optional condensate pump may be installed if a lift is required to dispose of the condensate The condensate pump kit can be ordered direct from the factory See item 27 on page 21 ...

Страница 4: ... calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on the size and occupancy of the residenc...

Страница 5: ...By ducting this way the air inside the structure will circulate through the Ultra Aire to be filtered and dehumidified Connect a duct from outside to the 6 collar of the Ultra Aire if you wish to provide fresh make up air 3 5 Quiet Installation A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from the blower A length of flexible ducting o...

Страница 6: ...dity Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n Fan Filter Operation n Programmable Ventilation Timer n Large easy to read backlit LCD display n Easy interaction with air handler fan Interlock Lockout n High Temperature Cut Out n Dryout Cycle ...

Страница 7: ... efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Servicing the Ultra Aire with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qualified service people...

Страница 8: ...n by reversing the above procedure 7 6 Compressor Capacitor Replacement This compressor is equipped with a two terminal external overload and a run capacitor but no start capacitor or relay See Figure 4 CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests These tests should be performed by a qualified service person 7 6A Checking Compressor Motor Circuits Perform ...

Страница 9: ... suction line filter driers will probably clean up the system If sludge is evident in the discharge line it will likely be found in the suction line This indicates the compressor burned out will running Sludge and acid have been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that cause...

Страница 10: ...entilation timer is not activated to prevent over ventilating the structure when the unit is dehumidifying or recirculating the indoor air The electric ventilation timer operates on 24 Vac from the control circuit DO NOT connect high voltage to the damper motor or damage to the motor may result DO NOT force the blade of the damper by hand or damage to the damper motor may result The damper opens i...

Страница 11: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM N O WHT WHT 11 Ultra Aire 100V Installer s Owner s Manual ...

Страница 12: ...ly 9 4029168 1 Compressor 10 4029169 1 Compressor Overload 11 4028226 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4029510 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 ID x 8 15 4022484 1 Relay SPST 24 Vac 30A 16 4020924 1 Relay SPDT 24 Vac 15A 17 4033032 05 1 Run Capacitor 45 MFD 370V 18 4025741 1 Thermostat Defrost 4021648 1 Defrost Control Mounting Clip 19 4022487 1 Transformer 120 24 Va...

Страница 13: ... 90 95 4022220 1 Condensate Pump Kit 4023672 1 Damper Duct 6 Diameter Electrically Actuated not shown 4023647 1 Damper Check 8 Diameter not shown 4021475 1 MERV 11 Filter 16 x 20 x 2 4022489 1 MERV 14 Filter 16 x 20 x 4 4022220 1 Pump Kit 4023484 1 Attic Insulation Kit 4023672 1 6 Motorized Damper 4020656 1 6 Inlet Exhaust Hood 4023647 1 8 Gravity Damper 4020646 1 8 Butterfly Damper ...

Страница 14: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the ap...

Страница 15: ...hermastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved ...

Отзывы: