- 15 -
Mode 01 A input:Setting the scaling factor
A B C D
0 1
E F G H
1 0 0 0
EFGH→Scaling factor
0001 - 9999 (Do not specify 0000.)
〔EFGH:Scaling factor〕
Input scaling is performed for A input. By specifying the scaling factor and the
exponential value(a minus power of 10), the scaling ratio per pulse can be set.
The exponential value(a minus power of 10)is set in Mode 02.
〔Ex.〕Using a flow meter which emits 2.5mL per pulse, the instant flux in
“
L
”
can be
expressed using the following conversion.
2.5mL → 0.0025L → 2500 × 10
-6
Scaled to the desired unit(L) ↑ ↑
4 digits Exp. value
↓ (exponent)
E F G H ↓ ↓
Mode 01 2 5 0 0 ← ← ← ┘ ↓
E F G H ↓
Mode 02 6 * * * ← ← ← ← ← ← ┘