5
CPBatMan080212
UNIVERSAL FLOW MONITORS, INC.
GENERAL SPECIFICATIONS
Maximum Operating Pressure:
300 PSIG (20.4 Bar)
Minimum Operating Pressure:
10 PSI of back pressure is required for the formation of
vortices. See
INSTALLATION
and
PRESSURE DROP CHARTS
Maximum Operating Temperature: 130 °F (54 ºC). Rating applies to both fluid & ambient temp.
Minimum Operating Temperature: 35 °F (2 ºC). Rating applies to both fluid & ambient temp.
Maximum Flow:
Meters may occasionally be over-ranged up to 125% of
capacity without damaging the meter (display reads up to
125% of max flow)..
Flow Capacities:
3/4" = 25 GPM (95 LPM)
1" = 50 GPM (190 LPM)
1 1/2" = 100 GPM (380 LPM)
2" = 200 GPM (750 LPM)
Turndown Ratio (max to min flow): 10:1 standard.
Process Connections:
Female NPT with BSPP and BSPT optional
Wetted Parts:
Body is brass or 316 Stainless Steel. Sensor is PVDF or PEEK.
Seals are Viton
®
Display:
3-digit LCD
6-digit LCD (Totalizer mode only)
Displays in GPM, LPM and CMH
Digit height = 0.3"
Power:
3 AA Alkaline batteries. Provides 45 days of continuous
operation (longer if flow measurement is intermittent – up to 1
year)
Low Battery:
“Mode” LED blinks red.
Enclosure rating:
Designed to meet the requirements of IP67
Accuracy:
2% Full scale
Response Time:
450 ms.
Repeatability:
.25% of indicated
*Viton
®
is a registered trademark for DuPont Performance Elastomers.