EAGLE & EAGLE X

 

O

vErviEw

Infrared Printer Port

Worklight

On/Off Button

Navigation “

s

“UP

and Backlight

Navigation “

t

“DOWN

and PUMP
SEND/ENTER
to Select and Print

Rotary Test Selector Dial

Battery Compartments

in back under boot

AC Power/Charge

Indicator Light

4 Line Backlit Display

Display Line Lights

Particle Filter
Inside Water Trap

Water Trap

Protective Rubber Boot
w/ built-in Magnets

Flue Probe Temperature Plug
(Plugs into T1)

Narrow Pin MUST be on the 
Right hand side.

Flue Probe 

Gas Inlet Plug

Temperature 

Connections

Flue Probe Temp: T1

Inlet Temp: T2

Pressure Connections

• Single Input (Draft): P1

• Differential Input Testing

  (Pressure drop test) P2

Flue Gas 

Inlet Connection

 Water Trap 

Drain

Battery Charge

AC Adapter

Содержание EagleX

Страница 1: ...1 Eagle Eagle X Owners Manual...

Страница 2: ...Charge Indicator Light 4 Line Backlit Display Display Line Lights Particle Filter Inside Water Trap Water Trap Protective Rubber Boot w built in Magnets Flue Probe Temperature Plug Plugs into T1 Narr...

Страница 3: ...ulated heat lost turning the Carbon in the fuel to Carbon Dioxide CO2 Wet Calculated heat lost turning the Hydrogen in the fuel into water H2O CO Loss Calculated loss due to partially burnt Carbon Any...

Страница 4: ...as soon as possible Use the GAS ZERO function Eagle X only to purge the analyzer of excess gases To do this on a standard Eagle remove the probe from the flue and turn ON the pump Always allow the rea...

Страница 5: ...ng testing Connect flue probe thermocouple connector to T1 and connect flue probe to water trap as shown above Use optional probe with T2 for inlet temperature Insert Flue Probe in stack Adjust the co...

Страница 6: ...raft probe for measuring pressure Press and hold t DOWN button to zero pressure sensor Rotate test selector to Temp Connect flue probe thermocouple or accessory thermocouple connector to T1 Connect ac...

Страница 7: ...ss Air O2 and CO readings both before and after the blower turns on If the heat exchanger is sealed your O2 and CO readings should remain fairly stable A breach in the heat exchanger may allow fresh a...

Страница 8: ...inch mmHg Millimeters of mercury hPa Hecto pascals EXIT Return to main menu REPORT COMB N VIEW When viewing reports PRESSURE DEL ALL Press s UP or t DOWN to select report EXCH Press and hold s UP or t...

Страница 9: ...04 to 06wc Overfire Draft Water Column Inches 02wc Carbon Monoxide parts per million 100ppm Smoke 0 or manufacturer s recommendation Positive Overfire Gas Oil Oxygen 3 to 9 O2 Stack Draft Water Colum...

Страница 10: ...Verify proper combustion O2 CO Stack Temp Efficiency Hi Low fire Gas Pressure Send and Return Water temp 80 Furnace Verify proper combustion O2 CO Stack Temp Vent Pressure Efficiency Verify Set Up Gas...

Страница 11: ...mperature Rise AC side Static Pressure Drop across coils Oil Furnace Verify proper combustion O2 CO Stack Temp Stack Draft Efficiency Test Verify Smoke Set Up Over Fire Draft Verify proper Static Duct...

Страница 12: ...ce between the ambient pressure level and the pressure level in the flue This is created either by the natural buoyancy of the hot gases created in combustion lifting or by an inducer fan that assists...

Страница 13: ...product of combustion and from wet fuel is recovered and the wet loss term is zero Gross efficiency calculations assume that the energy contained in the water vapor is not recovered Since the fuel air...