IMP120-14

www.ueonline.com

RE-GAPPING PROCEDURE

 

Tools Needed

5/8” open end Wrench

3/16” open end Wrench (2)

gAPPIng  IS  fACTorY-SeT  AnD  CrITICAl  To  THe  funCTIon 

of  THe  SWITCH.    THIS  ProCeDure  SHoulD  onlY  be 

PerforMeD  If  THe  Plunger  HAS  ACCIDenTAllY  been 

ADJuSTeD.

1)  loosen adjustment lock.

2)  Turn 5/8” hex adjustment screw In, to approximately midrange.  

 

This puts a load on the sensor and exposes the plunger flats. 

 

(See figure 6).

3)  using a 3/16” wrench on the plunger flats and a 3/16” wrench on 

 

the plunger hex screw, turn hex ouT from plunger until micro-

 

switch actuates.  If microswitch has already actuated, turn plunger 

 

hex screw In until microswitch deactuates.

4)   Continue per following instructions, depending on model. 

Models 171-174, 521-525, 531-535, and 540-548

Turn hex (In) an additional 1-1/2 flats from this point. This will provide 

a 5-9 mil gap.

Models 680, 701-705, 356-376, 612, 616, 270, 274

Turn hex (In) 3 flats from this point (approximately 1/2 turn).  This will 

provide a 14-16 mil gap.

Models 183-189, 190-194, 483-489, 490-494,565-567

Turn hex (In) 1 flat from this point.  This will provide a 4-7 mil gap.

ConTACT fACTorY for ASSISTAnCe WITH MoDelS 

noT SHoWn Above.

Re-Gapping Procedure for J120/J120K

Figure 6

zONE HAzARDOUS LOCATIONS FLAMEPROOF 

GAP AND JOINT DETAILS

Activation Plunger to adjustment screw hole gap joints: 1.140” min. 

length by 0.0030” max. annular gap

Activation Plunger to guide through hole gap joints: 1.105” min. 

length by 0.0030” max. annular gap

reset pivot to pivot guide through hole gap joints: 1.080” min. 

length by 0.0040” max. annular gap

Adjustment shaft to shaft through hole gap joints: 1.060” min. 

length by 0.0030” max. annular gap

Содержание 120 Series

Страница 1: ... or both can be used during installation A 3 4 explosion proof plug is provided for properly sealing the unused conduit opening thE explosion proof plug must be properly sealed during product installation GENERAL Misuse of this product may cause explosion and personal injury These instructions must be thoroughly read and understood before unit is installed This equipment is suitable for use in Cla...

Страница 2: ... engage cover O ring Types J120 J120K H121 H121K H122 H122K H122P Mount controls vertically pressure connection facing down see Figure 1a or horizontally see Figure 1b Control may be surface mounted via the four 1 4 screw holes on the enclosure or mounting bracket It can also be mounted directly to a rigid pipe using the pressure connection Controls with Breather Drain Option M450 Type J120 J120K ...

Страница 3: ...ront switch is set by turning the internal calibrating screw to the right for lower set point and turning to the left for higher set point When not set together the front switch should never be set higher than the rear switch Turning the external knob will increase or decrease both switch settings simultaneously without disturbing their relationship Controls with Options Option 1519 and other mode...

Страница 4: ...71 174 521 525 531 535 and 540 548 Turn hex IN an additional 1 1 2 flats from this point This will provide a 5 9 mil gap Models 680 701 705 356 376 612 616 270 274 Turn hex IN 3 flats from this point approximately 1 2 turn This will provide a 14 16 mil gap Models 183 189 190 194 483 489 490 494 565 567 Turn hex IN 1 flat from this point This will provide a 4 7 mil gap CONTACT FACTORY FOR ASSISTANC...

Страница 5: ...35 0 1 2 530 535 8 84 224 5 1 2 550 552 8 81 223 8 1 4 551 553 555 8 34 211 8 1 4 560 564 7 53 191 3 2 Sanitary 565 567 7 53 191 3 1 1 2 Sanitary 612 616 7 88 200 2 1 4 680 8 13 206 5 1 4 701 705 15622 15834 15839 7 44 189 0 1 4 Differential Pressure 36 39 147 157 367 7 59 192 8 1 4 S147B S157B 7 59 192 8 1 2 455 457 559 8 44 214 4 1 4 540 543 9 34 237 2 1 8 544 548 9 41 239 0 1 8 Types H121 H122 ...

Страница 6: ...sonnel For all applications a factory set unit should be tested before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANT...

Отзывы: