background image

IMP120-14

www.ueonline.com

WIRING

fIelD WIrIng MuST be rATeD 75°C MInIIMuM. for AMbIenT 

TeMPerATureS beloW -10°C, uSe SuITAble fIelD WIrIng.

DISConneCT  All  SuPPlY  CIrCuITS  before  WIrIng  unIT. 

WIre  unITS  ACCorDIng  To  nATIonAl  AnD  loCAl  eleCTrI-

CAl CoDeS. MAxIMuM reCoMMenDeD WIre SIze IS 14 AWg.   

 

    THe reCoMMenDeD TIgHTenIng Torque for fIelD WIrIng  

 

    TerMInAlS IS 7 To 17 In-lbS.

eleCTrICAl rATIngS STATeD In lITerATure AnD on nAMe-

PlATeS MuST noT be exCeeDeD—overloAD on A SWITCH 

CAn CAuSe fAIlure on THe fIrST CYCle. 

To  PrevenT  SeIzure  of  enCloSure  Cover,  Do  noT 

reMove  lubrICAnT.  THreADS  SHoulD  AlSo  be  free  of 

DIrT, eTC. 

THe  exTernAl  grounDIng  TerMInAl  IS  noT  To  be  uSeD 

AS  THe  PrIMArY  equIPMenT  grounDIng  TerMInAl.    THe 

InTernAl  grounDIng  TerMInAl  SHAll  be  uSeD  AS  THe 

PrIMArY  equIPMenT  grounDIng  MeAnS  AnD  THe  exTernAl 

grounDIng TerMInAl IS onlY for A SuPPleMenTAl (SeConDArY) 

grounDIng  ConneCTIon  WHere  loCAl  AuTHorITIeS  PerMIT  or 

requIre SuCH A ConneCTIon.

remove cover and wire control (See figure 3).  replace cover and 

hand tighten to fully engage cover o-ring.

Types J120,  J120K, H121, H121K, H122, H122K, H122P

Mount controls vertically (pressure connection facing down, see figure 

1a) or horizontally (see figure 1b). Control may be surface mounted via  

the four 1/4” screw holes on the enclosure or mounting bracket.  It can 

also be mounted directly to a rigid pipe using the pressure connection.

Controls with Breather Drain  (Option M450)

Type J120, J120K  Models 455-559

Mount with breather drain facing down (See figure 1b).  The conduit 

connection must be “potted” for this type of installation.  

Types H121, H122 & H122P, All Models

Mount in vertical position with pressure assembly and breather drain 

facing down (See figure 1a). 

Differential Pressure Types J120K, H121K, H122K 

Opposed Sensor Models 36-39, (S)147(B)-(S)157(B), 367

“opposed  sensor”  differential  pressure  switches  should  be  mounted 

with their pressure connection in the horizontal position (See figure 2).  

This will properly orient the 1/4” nPT venting conduit at the bottom of 

the third compartment (standardly supplied with plastic plug).

Figure 2 

Opposed Sensor Models

Figure 1b

J120, J120K

Figure 1a:

H121, H121K, H122, H122K, H122P 

Figure 3

use 75°C copper 
conductors only. 
recommended 
tightening torque for 
field wiring terminals 
is 7-17 in-lbs.

Figure 4a 

Содержание 120 Series

Страница 1: ... or both can be used during installation A 3 4 explosion proof plug is provided for properly sealing the unused conduit opening thE explosion proof plug must be properly sealed during product installation GENERAL Misuse of this product may cause explosion and personal injury These instructions must be thoroughly read and understood before unit is installed This equipment is suitable for use in Cla...

Страница 2: ... engage cover O ring Types J120 J120K H121 H121K H122 H122K H122P Mount controls vertically pressure connection facing down see Figure 1a or horizontally see Figure 1b Control may be surface mounted via the four 1 4 screw holes on the enclosure or mounting bracket It can also be mounted directly to a rigid pipe using the pressure connection Controls with Breather Drain Option M450 Type J120 J120K ...

Страница 3: ...ront switch is set by turning the internal calibrating screw to the right for lower set point and turning to the left for higher set point When not set together the front switch should never be set higher than the rear switch Turning the external knob will increase or decrease both switch settings simultaneously without disturbing their relationship Controls with Options Option 1519 and other mode...

Страница 4: ...71 174 521 525 531 535 and 540 548 Turn hex IN an additional 1 1 2 flats from this point This will provide a 5 9 mil gap Models 680 701 705 356 376 612 616 270 274 Turn hex IN 3 flats from this point approximately 1 2 turn This will provide a 14 16 mil gap Models 183 189 190 194 483 489 490 494 565 567 Turn hex IN 1 flat from this point This will provide a 4 7 mil gap CONTACT FACTORY FOR ASSISTANC...

Страница 5: ...35 0 1 2 530 535 8 84 224 5 1 2 550 552 8 81 223 8 1 4 551 553 555 8 34 211 8 1 4 560 564 7 53 191 3 2 Sanitary 565 567 7 53 191 3 1 1 2 Sanitary 612 616 7 88 200 2 1 4 680 8 13 206 5 1 4 701 705 15622 15834 15839 7 44 189 0 1 4 Differential Pressure 36 39 147 157 367 7 59 192 8 1 4 S147B S157B 7 59 192 8 1 2 455 457 559 8 44 214 4 1 4 540 543 9 34 237 2 1 8 544 548 9 41 239 0 1 8 Types H121 H122 ...

Страница 6: ...sonnel For all applications a factory set unit should be tested before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANT...

Отзывы: