PAGE 6
3330 Earhart Drive, Suite 208
|
Carrollton, TX 75006
|
Office: 972.556.0916
|
Fax: 972.910.8384
OPM1
EXAMPLE 3:
SINGLEMODE FIBER, PAIRED, LOOPBACK JUMPER
Fiber Type
Connectors Used
Test Jumper Setup
OPM Used
OLS Used
Singlemode
LC
Loopback
OPM1
LSSM
Page 7
M-UM038-01 RP 460 Reference and Test
DMT
Example 3: Singlemode Fiber, Paired, Loopback Jumper
Fiber Type
Singlemode
Connectors Used
LC
Test Jumper Setup
Loopback
OPM Used
RP 460
OLS Used
DLS 355
Fiber-Under-Test
The fiber-under-test is paired singlemode
with paired LC connectors on each end. The
fiber-under-test may be up to 250 kilometers long.
In this example, the fiber-under-test is 400 meters
long.
Test Jumper
The test jumper is paired for loopback testing. One
end has an SC connector and an LC connector,
and the other end has two LC connectors clipped
together. This method also uses a singlemode
loopback adapter. It should be blue and have a
duplex bulkhead on the end.
Power Meter
The RP 460 power meter is set to the
1550nm wavelength. The 1310nm
wavelength may also be used. Always
match the wavelength on the RP 460
to the wavelength on the DLS 355. The
adapter on the RP 460 is the AC 029 LC
adapter.
Light Source
The DLS 355 laser source is set to the
1550nm wavelength. The 1310nm
wavelength may also be used. The
adapter is the default AC 022B SC adapter.
Page 3
M-UM038-01 RP 460 Reference and Test
DMT
Example 1: Singlemode Fiber, Point-to-Point, 1 Jumper
Fiber Type
Singlemode
Connectors Used
LC
Test Jumper Setup
Single
OPM Used
RP 460
OLS Used
DLS 355
Fiber-Under-Test
The fiber-under-test is singlemode with LC
connectors on each end. The fiber-under-test may
be up to 250 kilometers long. In this example, the
fiber-under-test is 400 meters long.
Test Jumper
The test jumper is a one-meter singlemode fiber
with SC and LC connectors. The SC connector will
be plugged into the DLS 355 laser source and the
LC connector will be used to interface with the
fiber-under-test.
Power Meter
The RP 460 power meter is set to the
1550nm wavelength. The 1310nm
wavelength may also be used. Always
match the wavelength on the RP 460
to the wavelength on the DLS 355. The
adapter on the RP 460 is the AC 029 LC
adapter.
Light Source
The DLS 355 laser source is set to the
1550nm wavelength. The 1310nm
wavelength may also be used. The
adapter is the default AC 022B SC adapter.
400m Fiber
1m Jumper
The fiber-under-test is paired singlemode with paired LC
connectors on each end. The fiber-under-test may be up
to 250 kilometers long. In this example, the
fiber-under-test is 400 meters long.
TEST JUMPER
The test jumper is paired for loopback testing. One end
has an SC connector and an LC connector, and the other
end has two LC connectors clipped together. This
method also uses a singlemode loopback adapter. It
should be blue and have a duplex bulkhead on the end.
POWER METER
The OPM1 power meter is set to the 1550nm
wavelength. The 1310nm wavelength may also be
used. Always match the wavelength on the OPM1 to
the wavelength on the LSSM. The adapter on the OPM1
is the OPAL LC adapter.
LIGHT SOURCE
The LSSM laser source is set to the 1550nm
wavelength. The 1310nm wavelength may also be used.
The adapter is the default OPAS SC adapter.
FIBER-UNDER-TEST
400m Paired Fiber
1m Paired Jumper
Singlemode Loopback
Содержание TEK-3
Страница 2: ...SECTION ONE LSMM LED LIGHT SOURCE QUICK START GUIDE NORTH AMERICA ...
Страница 8: ...SECTION TWO LSMM LED LIGHT SOURCE TECHNICAL GUIDE NORTH AMERICA ...
Страница 11: ...SECTION THREE OPM1 OPTICAL POWER METER QUICK START GUIDE NORTH AMERICA ...
Страница 18: ...SECTION FOUR OPM1 OPTICAL POWER METER REFERENCE TEST GUIDE NORTH AMERICA ...