25
www.ubisys.de
u
0x0007
enum8,
read-only
PowerSource
Always set to mains-powered, single phase (regardless of the connected supply voltage)
0x0010
string,
persistent
LocationDescription
Empty string by default. Might be set by commissioning software during installation
0x0011
unsigned8,
persistent
PhysicalEnvironment
“Unspecified” by default. Might be set by commissioning software during installation
Cluster commands supported:
Command
Description
0x00
Reset to factory defaults.
Restores the values of all attributes of all clusters across all endpoints to their factory fresh default
settings. Does not affect network settings or bindings.
Notice: In earlier versions, up to and including version 1.05, the command did actually behave like a leave
command with factory reset.
This command has been deprecated and is no longer supported since
version 1.06. Use mgmt_leave_req, instead.
7.7.2.
Identify Cluster (Client)
The client side of the identify cluster on this endpoint is used for push-button commissioning.
Cluster commands transmitted:
Command
Description
0x01
Query Identify
This command is broadcast during push-button commissioning to identify suitable binding targets.
Once target devices are selected, they will be queried for matching descriptors.
7.7.3.
Commissioning Cluster (Server)
This implementation supports all attributes and most commands. However, the cluster has limited
value. It is rarely used and might be removed in the future.
7.7.4.
Over-the-Air Upgrade Cluster (Client)
The image type for S1 is 0x7B02, for S1-R it is 0x7B05. You may request the latest firmware in ZigBee
OTA image format to upgrade devices in the field using your own OTA server and back-end. If you
operate the power switch S1 together with the ZigBee/Ethernet Gateway ubisys G1, the latest
firmware for S1 and S1-R will always be available automatically and you do not need to request it
explicitly.
7.7.5.
Device Setup Cluster (Server)
This cluster is manufacturer-specific and allows to change advanced device setup options, which are
not covered by standard clusters defined in the ZigBee Cluster Library.
Attributes supported: