C. Airflow Adjustment

The motor is equipped with a variable pitch pulley to 

allow for minor adjustments in cubic feet per minute 

(cfM) of airflow.

increasing blower speed (rPM) will increase airflow 

(cfM) and current (amps). to increase speed, close the 

variable pitch pulley from “normal Setting” (fig. 11a) 

toward “fully closed” (fig. 11B). Decreasing blower 

speed will decrease airflow and current. to decrease 

speed, open the variable pitch pulley from “normal 

Setting” (fig. 11a) toward “fully open” fig. 11c). 
to adjust the variable pitch pulley: 
1.  Loosen motor base nuts, adjust motor slide base and 

remove the drive belt. 

2.  Loosen set screw “a” to clear the drive key between 

pulley halves. 

3.  remove the key. 
4.  adjust pulley in increments of one turn to the desired 

setting. 

5.  install key and tighten set screw “a.” 
6. install drive belt. 
7.  Loosen set screw “B.” 
8.  align belt centerlines of motor and blower pulleys 

using straight edge and square. 

9. Set belt tension using a belt tension gage.

11. TROUBLESHOOTING

Tools Required:
• Screwdriver 8” (200mm) or longer with plastic handle
•  Volt-Ohm-Meter — used to check low voltage input 

(115 Vac) and continuity (oHMS)

•  High Voltage Probe (optional) — used to check high 

voltage power supply. range: from 0 to 15 KVDc

risk of electrical shock. the high voltage circuits to 

the ionizer and collector should be grounded before 

removing/installing high voltage wires and/or removing 

the ionizer(s)/collector cell(s). Grounding can be 

accomplished by waiting one minute after placing power 

in the off position or refer to figures 4 and 5. the power 

pack total current output is limited to a maximum of 5 

milliamps to ensure personnel safety.

Troubleshooting Procedures 

High voltage issues can generally be isolated by referring 

to the indicator light. 

•  When the light illuminates, high voltage is present from 

the power pack to the ionizer and collector cell circuits. 

•  A flashing indicator light indicates a failure in the high 

voltage circuits. 

there are four conditions which may cause a flashing 

indicator light. 
a)  the high voltages are below specifications to the ionizer 

and/or the collector cell circuit(s). 

b)  there is an arcing condition to the ionizer and or 

collector cell circuit(s). 

c)  there is a dead short condition. 
d)  the power pack has failed.

Figure 11 Motor Pulley Settings

!

  CAUTION

improper Blower Speeds adversely affect System 

Performance. contact uas Before adjusting Motor 

Variable Pulley Settings.

Figure 10

Motor/Blower Schematic

!

  CAUTION

!

 

WARNING

The SHN Series is equipped with an external limit 

switch (120 Vac to the power packs) engaging and 

disengaging by the component access door. the limit 

switch should be engaged manually after placing 

the power in the on position to the SHn unit, and 

disengaged when placing power in the off position 

during the troubleshooting steps. the engagement and 

disengagement of the limit switch is not identified in the 

troubleshooting steps.

!

 

WARNING

Power pack enclosures service voltage can range 

from 120Vac to 460Vac. When servicing the power 

pack enclosure, place power in the off position by the 

disconnect switch supplied by others.

Содержание CLARCOR Smog-Hog SHN-10

Страница 1: ...Model SHN 20 Shown Smog Hog Electrostatic Precipitator l models SHN 10 SHN 20 SHN 40 AND SHN 50 OWNER S MANUAL ...

Страница 2: ... following information available when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL _________________________________________________________________ SYSTEM ACCESSORIES ______________________________________________________________________________ ___________________...

Страница 3: ...efilters 7 B Mist Stop Filter 7 C Ionizing Sections 7 D Collection Cells 7 E Afterfilters 7 F Power Packs 7 G Push to Test Buttons 7 H Blower 7 I Drive 7 J Discharge Grill 7 K Cabinet 7 L Component Access Door Electrostatics 7 M Access Door Drive Set 7 9 MAINTENANCE 8 A Cleaning Instructions 8 B Component Cleaning Methods 9 C Other Cleaning Considerations 9 D When are Components Clean 9 10 PERIODI...

Страница 4: ...explosive Use non flammable cleaners Keep flammable materials and vapors such as gasoline away from unit The unit should be inspected frequently and contaminants removed to prevent excessive accumulation which may result in flash over or fire damage Operate only in a safe and serviceable condition Operating temperature to the air stream should not exceed 120 F 49 C DANGER WARNING WARNING CAUTION C...

Страница 5: ... 4 2 4 2 02 4 2 PTIONAL IST 3TOP ILTER 3 2 2 7 2 5 4 3 4 42 8 4 2 37 4 4 2 37 4 4 2 43 053 4 4 34 544 3 3 2 2 02 4 2 PTIONAL IST 3TOP ILTER 2 4 4 2 4 2 7 2 5 4 3 4 42 8 4 2 37 4 3 2 2 02 4 2 PTIONAL IST 3TOP ILTER 2 4 2 4 2 4 2 43 053 4 4 34 544 3 7 2 5 4 3 4 4 053 4 4 34 544 053 4 4 34 544 3 2 7 42 8 Smog Hog Electrostatic Precipitator Installation and Service ...

Страница 6: ...to the placement of the precipitator to maximize its effectiveness The number of units required to clean the air will depend on the layout of the room and the concentration of pollutants Because it is necessary to develop proper airflow patterns the placement and number of precipitators should be as suggested by UAS or your local representative B Ducted or Source Capture When your Smog Hog is used...

Страница 7: ...ufficiently sloped 1 5 inches 38mm diameter and vented All plumbing should conform with all state and local codes Appropriate design criteria as provided by a plumbing mechanical contractor should be utilized to ensure proper control of drainage from the SHN Unit 5 DISCHARGE GRILL The four way adjustable air discharge grill can be set to any open position desired A Unducted Installation for area c...

Страница 8: ...nd unit is ready for operation Input to the high voltage power pack should not exceed 130 Volts 60 Hertz This is supplied by a power source or the step down transformer as shown in the wiring diagram inside the main electrical junction box on all units Refer to Appendix B Units are factory wired for the voltage requirement indicated to UAS by the customer The electrical box has knockouts Therefore...

Страница 9: ...Revised 09 15 SMOG HOG SHN Series Models 5 SHN 10 Dimensions and Mounting Hole Locations SHN 20 ...

Страница 10: ...Revised 09 15 SMOG HOG SHN Series Models 6 SHN 40 Dimensions and Mounting Hole Locations SHN 50 T ...

Страница 11: ...ng The insulators along with the cell s long plate design assure maximum efficiency and retention of collected contaminant E Afterfilters Heavy duty reusable industrial aluminum mesh filters aid even air distribution across the cells and trap any collected contaminant that could release from the cells during start and stop operations F Power Supply The proprietary design high voltage power supply ...

Страница 12: ...quired for effective cleaning at reasonable detergent cost Typically 20 1 is recommended as a starting point Experimentation is recommended Never mix acid and alkaline detergent for manual cleaning Detergent mixing could cause rapid heat release gel formation or other undesirable conditions Water Temperature Detergents can be up to twice as effective in hot water and hot water alone is very effect...

Страница 13: ...ssure Washer A self contained pressure washer with a spray wand can be an effective cleaning method providing it is used with caution Care should be taken not to expose collection cell plates to close up and prolonged blasts of high temperature or high pressure water Cell plates deform under continuous exposure to such conditions C Other Cleaning Considerations The previous methods address the cle...

Страница 14: ...or of the cabinet 4 The door gasket should be formed to the complete cabinet lip edge before applying silicone sealant Place the trim edge at the top center of the cabinet lip edge and press gasket in place ending at the same location Do not trim excess 5 Remove door gasket and apply silicone sealant to the inside of gasket or on the inside edge of the cabinet lip edge Place the trim edge at the t...

Страница 15: ... can be accomplished by waiting one minute after placing power in the off position or refer to Figures 4 and 5 The power pack total current output is limited to a maximum of 5 milliamps to ensure personnel safety Troubleshooting Procedures High voltage issues can generally be isolated by referring to the indicator light When the light illuminates high voltage is present from the power pack to the ...

Страница 16: ...ER PACK The power should be placed in the off position to the power pack Carefully disconnect both high voltage wires Ionizer 8 and Collector 7 from the power pack The high voltage wires should carefully be placed away from the ionizer and collector cell power pack connectors eliminating the high voltage wires from contacting the power pack connectors Place the power to the unit in the on position...

Страница 17: ...CATOR LIGHT Sometimes removing the collector cell s and installing the collector cell s into the unit will clear a flashing indicator light condition If not check the causes below Dirty collector cell s contaminant build up requiring manual cleaning Wet collector cell s not properly dried after a wash cycle or manual cleaning procedure Use compressed air to accelerate the drying time Deformed coll...

Страница 18: ...llector cell circuit high voltage wire 7 refer to Figure 13 Fluctuating high voltage during a measurement will indicate an arcing circuit 12 Bench Test Procedure TOOLS REQUIRED One power pack Two high voltage wires 6 ft 1829mm in length with test clips at each end of the wire High voltage probe Refer to operating instructions by the manufacturer If a high voltage probe is not available install a U...

Страница 19: ...l will not maintain high voltages above 7 5 KVDC The collector cell will continuously arc Usually this condition is caused by a power pack above the High Voltage Specifications The power pack should be replaced There is a high voltage problem if the indicator light is flashing 7 If there is an arcing condition determine the problem and repair 8 Disconnect AC cable plug from the wall outlet COLLECT...

Страница 20: ...om component access door and part numbers available when ordering Properly Aligned SHN Assembly QUANTITY ITEM NO PART NO DESCRIPTIONS REQUIRED 1 02 2339 S COLLECTION CELL ASSEMBLY 2 2 02 0037 S IONIZER ASSEMBLY 2 3 37 0027 COLLECTION CELL FEED THRU INSULATOR 1 4 37 0026 IONIZER FEED THRU INSULATOR 1 5 36 0014 CELL IONIZER INSULATOR SPRING 2 6 36 0077 GROUND SPRING 4 7 30 0387 COLLECTION CELL CONTA...

Страница 21: ...MIT SWITCH CABINET DOOR INTERLOCK 20 0005 GASKET EDGE BUNA N 42 0168 BLOWER BELT DRIVE 3 4 SGL 9 7 SHN 10 32 0059 BLOWER BELT DRIVE 3 4 DBL 9 7 SHN 20 32 0036 BLOWER BELT DRIVE 1 SGL 15 15 SHN 40 50 T 32 0063 MOTOR 7 1 2HP 208 230 460 3 60 22 0288 MOTOR 5HP 208 230 460 3 60 22 0023 MOTOR 3HP 190 208 230 460 3 50 60 22 0022 MOTOR 1HP 208 3 60 22 0012 MOTOR 2HP 208 230 460 3 60 22 0039 MOTOR 1 2HP 1...

Страница 22: ... 1 0 0 6 1 0 0 5 1 0 0 4 1 0 0 3 1 0 0 2 1 0 0 1 1 0 0 0 1 0 0 9 0 0 8 0 0 7 P H 2 P H 1 P H 2 1 SHN 20 3 5 0 0 4 4 0 1 H S 1 0 5 2 1 S S C s l x s e v r u c n a f 0 1 H S H S E V R U C W O L F R I A N 3 5 0 0 4 4 0 1 0 0 5 0 0 1 5 1 0 2 5 2 0 3 0 0 0 2 0 5 7 1 0 0 5 1 0 5 2 1 0 0 0 1 0 5 7 0 0 5 0 5 2 0 M F C w o l F r i A External Static Pressure WG 0 0 0 2 0 0 9 1 0 0 8 1 0 0 7 1 0 0 6 1 0 0 5 ...

Страница 23: ... c n a f T 0 5 0 4 H S H S E V R U C W O L F R I A N 5 0 7 0 4 4 T 0 5 0 1 2 3 4 0 0 0 0 1 0 0 0 2 0 0 0 3 0 0 0 4 0 0 0 5 M F C w o l F r i A External Static Pressure WG 0 0 4 1 0 0 3 1 0 0 2 1 0 0 1 1 0 0 0 1 0 0 9 0 0 8 0 0 7 P H 5 P H 3 0 0 6 SHN 50 T SHN 40 SHN SERIES AIRFLOW CURVES ...

Страница 24: ...Revised 09 15 SMOG HOG SHN Series Models 20 SHN 10 20 XB SHN 10 20 APPENDIX B WIRING DIAGRAMS ...

Страница 25: ...Revised 09 15 SMOG HOG SHN Series Models 21 SHN 40 SHN 10 20 M WIRING DIAGRAMS ...

Страница 26: ...Revised 09 15 SMOG HOG SHN Series Models 22 SHN 40 M SHN 40 XB WIRING DIAGRAMS ...

Страница 27: ...Revised 09 15 SMOG HOG SHN Series Models 23 SHN 50 T WIRING DIAGRAMS ...

Страница 28: ...ods manufactured or supplied by others This warranty is subject to any limitations in UAS quotation and may not be modified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORALOR IMPLIED INCLUDINGANYIMPLIED WARRANTYOF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR NONINFRING...

Отзывы: