UAS CLARCOR SMOG-HOG MSH Series Скачать руководство пользователя страница 10

6

revised 03/15

SMoG-HoG

®

electronic air cleaner

(a) Place the MSH "off", and open power pack lid door. 

Disconnect high voltage wire #8 to the ionizer connector 

with high voltage wire #7 (Collector) connected on the 

power pack and place MSH "on". the indicator light 

should be illuminated. If so, the cell circuit is operational 

proceed to (b). If indicator light is flashing perform the 

following: 
•  Place MSH "off", open component door, and remove 

the unicell(s). 

•  Place MSH "on". The indicator light should be 

illuminated. if the indicator light is illuminated the 

problem is within the collector cell section. if the 

indicator light is flashing the problem is the high 

voltage door feed through insulator (dirty, cracked, 

carbon tracking) and or the high voltage wire (broken 

wire or wire insulation has deteriorated causing a 

dead short condition). 

Parts should be replaced as required. 

Inspect the unicell(s) for the following: 

COLLECTOR CELL CONDITIONS 

CAUSING FAILURE 

•  Dirty collector cell(s) (contaminant build up bridging 

the cell plates and or on cell triangular insulators) 

requiring manual cleaning. 

•  “Wet” collector cell(s), not properly dried after manual 

cleaning, use compressed air to accelerate the drying 

time.   

•  Deformed collector cell contact springs contacting a 

“grounded surface”. 

•  Bent cell plate(s) contacting the opposing cell plate(s). 
•  Carbon tracking to the cell triangular insulators, 

imbedded black streak which cannot be removed by 

cleaning (replace insulator.) 

•  Surface oxidation to unicell component requiring

 

a replacement.

•  Unicell is structurally weak, loose steel rivets, 

deterioration to cell plate spacers or paper thin cell 

plates due to utilizing the improper detergent.

Parts should be replaced as required, install unicell(s). 

Sometimes a flashing indicator light will clear itself 

by removing the unicell(s) from the module and then 

installing the unicell(s) back into the module. 

Place MSH "off"; connect all wires which have been 

disconnected and install unicell(s).  
(b)

 indicator light is illuminated with the high voltage 

wire #7 connected to the collector cell connector on the 

power pack. Place MSH "off" and connect high voltage 

wire #8 to the ionizer connector on the power pack. 

Place the MSH "on". 

The indicator light should be illuminated? If so, the 

unicell(s) are operational. If the indicator light is flashing 

perform the following:     
•  Place MSH "off", open the component door, and 

remove unicell(s). 

•  Place MSH "on". If the indicator light is illuminated the 

problem is within the ionizer section. if the indicator 

light is flashing the problem is the high voltage door 

feed through insulator (dirty, cracked, carbon tracking) 

and or the hv wire (broken wire or wire insulation has 

deteriorated causing a dead short condition). 

Parts should be replaced as required, install unicell(s). 
Inspect the unicell(s) for the following:

IONIZER CONDITIONS CAUSING FAILURE 

•  Dirty ionizer(s) (contaminant build up) requiring 

manual cleaning. 

•  “Wet” ionizer(s), not properly dried after a wash cycle 

or manual cleaning procedure, use compressed air to 

accelerate the drying time.  

•  Deformed ionizer contact springs contacting a 

“grounded surface.” 

• Broken ionizer wires.
•  Contaminant build up and or cracked ionizer stand off 

insulators.  

•  Carbon tracking (black streak) to the ionizer stand off 

insulators (replace insulator). 

•  Ionizer wires not “taut” contacting the ground plates.  
•  Bent ionizer wire support bar contacting a “grounded 

surface.” 

• Bent ground plates contacting the ionizer wires. 
•  Surface oxidation to unicell component requiring

 

a replacement.

•  Unicell is structurally weak or has loose rivets.

Parts should be replaced as required. 
Sometimes a flashing indicator light will clear itself 

by removing the unicell(s) from the module and then 

installing the unicell(s) back into the unit. 

Содержание CLARCOR SMOG-HOG MSH Series

Страница 1: ...Industrial Electrostatic Air Cleaner l SMOG HOG MSH Model OWNER S MANUAL ...

Страница 2: ...ce have the following information available when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL _________________________________________________________________ SYSTEM ACCESSORIES ______________________________________________________________________________ ________...

Страница 3: ...G 2 5 1 Normal Maintenance 2 5 2 Manual Cleaning of SMOG HOG Components 3 5 3 Manual Cleaning Methods 3 5 4 Appearance Of Components After Cleaning 4 5 5 Replacing Damaged Ionizer Wires 4 6 TROUBLESHOOTING 4 6 1 Tools Required 4 6 2 Perform Before Troubleshooting 4 6 3 Troubleshooting Procedures 5 6 4 Troubleshooting Table 8 7 REPLACEMENT PARTS 9 7 1 Replacement Parts List 9 8 FIGURES 10 12 9 WIRI...

Страница 4: ...cessive accumulation which may result in flash over or fire damage The air cleaner should not be used for support of personnel or material Operate only in a safe and serviceable condition DANGER WARNING CAUTION C A U T I O N This is the safety alert symbol This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and th...

Страница 5: ...en using power pack 21 1216 and 5 6mA when using power pack 21 1234 In the event of a short circuit or other overload condition the power supply is designed to cause the high voltage to collapse When the voltage collapses the indicator light will blink When the overload is removed the voltage will automatically build up to normal and the indicator light will illuminate The power supply is self pro...

Страница 6: ...ions Periodically momentary shorts will occur indicated by the flickering indicator light If the light is dim fails to glow or continues to flicker the components may need cleaning or servicing see Cleaning Instructions Section 5 2 and 5 3 5 MAINTENANCE AND MANUAL CLEANING 5 1 Normal Maintenance Once the unit is operational periodic maintenance is necessary to assure proper performance Follow a re...

Страница 7: ...mation or some other undesirable condition Time is necessary for effective cleaning Soaking may seem slower and less effective than high impingement and or hot water above 180 F for cleaning action so personnel should be forewarned about using excessive pressure or temperature to shortcut the cleaning process High pressure or stream spray cleaning until plate edges are shiny is not effective Not o...

Страница 8: ...kets are cleaned and intact 3 Component tracks are free of contaminant build up for unicell grounding 4 Module drain sump is cleaned and free flowing 5 Interior is free of extreme contaminant build up 6 Blower wheel is free of contaminant build up 5 5 REPLACING DAMAGED IONIZER WIRES 1 Remove the damaged wire from each spring Also replace spring if it is damaged 2 Loop one end of the new wire over ...

Страница 9: ...high voltage The grounding procedure statement is not identified within the troubleshooting steps but should be performed The power pack total current output is limited to a maximum of 5 milliamps to assure personnel safety A high voltage probe is required to measure high voltages to the ionizer and collector circuits to the unit As an accessory a high voltage probe can be purchased for a multimet...

Страница 10: ...ar itself by removing the unicell s from the module and then installing the unicell s back into the module Place MSH off connect all wires which have been disconnected and install unicell s b Indicator light is illuminated with the high voltage wire 7 connected to the collector cell connector on the power pack Place MSH off and connect high voltage wire 8 to the ionizer connector on the power pack...

Страница 11: ... 11 8 KVDC If the ionizer voltage is below specifications refer step 2 Ionizer Conditions Causing Failure Low ionizer voltage will decrease the collector cell voltage but low cell voltage will not affect the ionizer voltage 4 Place the tip of the high voltage probe to the collector cell door feed through insulator bolt The high voltage measurement should be 5 0 to 7 3 KVDC If the collector cell vo...

Страница 12: ...fective Unicell dirty Unicell malfunction Unicell installed backwards or upside down High voltage contacts dirty Loss of input voltage Unicell malfunctioning Power supply defective POSSIBLE SOLUTIONS Replace lamp Check connection to lamp Check power supply Replace air mover Clean foreign object from air mover Replace control switch Check connection at control switch Correct wiring Engage safety in...

Страница 13: ...r 33Ͳ10116 33Ͳ10121 2 Unicell 02Ͳ10429Ͳ0001ͲS 02Ͳ1921ͲS 3 Mesh AfterͲFilter 33Ͳ10110 33Ͳ10120 4 Inlet Cone Ring 32Ͳ10053 32Ͳ10067 5 Motorized Impeller Fan 32Ͳ10052 32Ͳ10065 6 Ionizer Spring 36Ͳ0068 36Ͳ0068 7 Cell Spring 36Ͳ0012 36Ͳ0012 8 Cell Ground Spring 36Ͳ0016 36Ͳ0016 9 Interlock Switch 20Ͳ0005 20Ͳ0005 10 Filter Door Latch 39Ͳ10055 39Ͳ10055 11 Feed Through Insulator 37Ͳ0026 37Ͳ0026 12a Power P...

Страница 14: ...10 Revised 03 15 SMOG HOG Electronic Air Cleaner Figure 1 Unit Components ...

Страница 15: ...1 Revised 03 15 SMOG HOG Electronic Air Cleaner Figure 2 Drain Loop Assembly Figure 4 Replacing Ionizer Section Figure 3 Ionizer and Cell Voltage Measurement Figure 5 Grounding The Collector Cell Section ...

Страница 16: ...12 Revised 03 15 SMOG HOG Electronic Air Cleaner Figure 6 Grounding the Ionizing Section Figure 7 Power Pack Input Output Connections ...

Страница 17: ...13 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 ...

Страница 18: ...14 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 M ...

Страница 19: ...15 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 11 ...

Страница 20: ...16 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 11 M ...

Страница 21: ...17 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 11 w Optional ON OFF Switch ...

Страница 22: ...18 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 1PH Interconnect MSH 11 1PH Interconnect ...

Страница 23: ...19 Revised 03 15 SMOG HOG Electronic Air Cleaner MSH 05 3PH Interconnect MSH 11 3PH Interconnect ...

Страница 24: ...dified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORALOR IMPLIED INCLUDINGANYIMPLIED WARRANTYOF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR NONINFRINGEMENT As Purchaser s exclusive remedy for any defects in the equipment UAS will exchange or repair any defective part...

Отзывы: