Enilit RTU User Manual 16.09
Enilit RTU software
|
Slave protocols
Page 211 of 309
ADPU’s.
Range of values: 1...32767
w
After how many I frame APDU’s
acknowledgment is needed.
Range of values: 1...32767
8
COT size
Cause of transmission size.
Values: 1, 2 bytes
2
CAA size
Common ASDU address size.
Values: 1, 2 bytes
2
Frame size
Maximum frame size. All start, stop, checksum
and other bytes are included.
Range of values: 50 … 261 bytes
255
StartTD
Action taken when got second StartTD from
other client.
Values: Ignore, Connect new client.
Ignore
No ACK
On disconnect keep in buffer all sent, but not
acknowledged I frames. On new client connect
all not acknowledged frames will be transmitted.
Values: No, Yes
No
Clients Nr. 1 …
9 IP
Access list of clients IPs.
Range of values: xxx.xxx.xxx.xxx
127.0.0.1
Log header
Enables to log ACPI header values.
Values: No, Yes