Enilit RTU User Manual 16.09
Enilit RTU software
|
Master protocols
Page 155 of 309
Range of values: 0 … 65535
Address
Increment
After adding new point Address will be
automatically incremented by set value.
1
Modbus type
Modbus data type.
Values:
Write single coil
Write single register
Write multiple coil
Write multiple register
Write single coil
Data subtype
Available only if Modbus type is Write single
register or Write multiple register.
Available data subtypes:
16 bits unsigned (B1B2),
16 bits unsigned (B2B1),
16 bits signed (B1B2),
16 bits signed (B2B1)
Offset 1
New value = (Old value + Offset1) * Scale +
Offset2
0
Scale
1
Offset 2
0
Invert
Inversion of command.
Values: No, Yes
No
Commands window
In the Command points window Value, Time will show last transmitted command data. Result will show
response from controlled device.