Enilit RTU software
|
Slave protocols
Page 205 of 309
Measured value, short floating point value
IOA
Here, the information address can be specified.
Range of information address depends from
Application layer parameter Information object
address length.
Range of values: 0 … 16777215
1
IOA Increment
After adding new data point address will be
automatically incremented by set value. It is
used only for configuration.
1
Time type
Timestamp of data point.
Range of values:
No time,
Short time (3 bytes)
Long time (7 bytes)
Long Time (7 bytes)
Interrogation
Assign data point to the specific interrogation
group.
Range of values:
General Interrogation,
Interrogation Group1 … 16.
General Interrogation
Change
You can specify data point class or cause of
transmission. If you choose to be Class1 Event
or Class2 Event, data point will be marked with
Spontaneous cause of transmission.
Range of values:
Class1 Event,
Class1 Event, not buffered when no link,
Class2 Event,
Class2 Event, not buffered when no link,
Send only on general interrogation request,
Periodic.
Class1 Event
Background
Data point is included in background scan.
Values: No, Yes
No
Offset 1
New value = (Old value + Offset1) * Scale +
Offset2
0
Scale
1