15
Figure 13: Installation of FO in a Confined Space with Remote Chimney
NOTE:
1. Type L Vent Material generally means stainless steel inner liner and stainless steel outer covering and separated with 1"
thick special high temperature insulation - factory assembled and rated.
2. In a confined space, provide ventilation air to the burner and size such ventilation air openings to provide not less than 28
square inches free area per gallon of fuel input to the burner.
3. Keep right side of boiler accessible for flue cleanout and tankless coil maintenance.
4. Boiler is heavily insulated and is suitable for 1" clearance from jacket surface to combustibles.
5. Boiler is of wet base design and suitable for installation on combustible floors.
6. The original installation may have been under poor or outdated building codes. Replacement boilers are subject to codes
in effect at the time of replacement. Be sure to consult with local code officials before starting replacement.
7. Copies of NFPA 211 are available from National Fire Protection Association, Battery March Park, Quincy, MA 02269 or
at your local fire code officers office.
IV: VENTING (NATURAL VENT - CHIMNEY) (continued)
Содержание V13A RO/FO
Страница 5: ...5 SECTION I GENERAL INFORMATION Figure 1 VI RO FO Water Boiler with Tankless Heater Beckett AFG Burner...
Страница 40: ...40 XI REPAIR PARTS continued Figure 25 Flush Jacket Components...
Страница 42: ...42 XI REPAIR PARTS continued Figure 26 V1 RO FO Trim and Controls...
Страница 48: ...48 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...