24
VI: SYSTEM START-UP (continued)
failure re-occurs, call your heating contractor
immediately before pressing the reset button.
WARNING
DO NOT attempt to start the burner when excess
oil has accumulated, when the boiler is full of
vapor, or when the combustion chamber is very
hot.
5. CAD CELL LOCATION AND SERVICE
The burner is supplied with a cadmium sulfide flame
detector mounted at the factory, mounted on the
bottom of the electronic ignitor. See Figure 20. To
service cad cell or to replace the plug in portion,
swing open the ignitor. After service is complete, be
sure to fasten down the ignitor.
Figure 20 Cad Cell Location
H.
CHECK FOR CLEAN CUT OFF OF BURNER.
1. AIR IN THE OIL LINE between fuel unit and
nozzle will compress when burner is on and will
expand when burner stops, causing oil to squirt from
nozzle at low pressure as burner slows down and
causing nozzle to drip after burner stops. Usually
cycling the burner operation about 5 to 10 times will
rid oil line of this air.
2. IF NOZZLE CONTINUES TO DRIP, repeat
Paragraph H, Step 1 above. If this does not stop the
dripping, remove cut-off valve and seat, and wipe
both with a clean cloth until clean, then replace
and readjust oil pressure. If dripping or after burn
persist replace fuel pump.
I.
TEST CONTROLS.
1. Check thermostat operation. Raise and lower
thermostat setting as required to start and stop
burner.
WARNING
Before installation of the boiler is considered
complete, the operation of all boiler controls must
be checked, particularly the primary control and
high limit control.
2.
VERIFY OIL PRIMARY CONTROL
FEATURES
using procedures outlined in
Instructions furnished with control or instructions as
follows:
a.
GeniSys 7505 Control Features
, see Figure 21.
i.
The GeniSys 7505 is a microprocessor-
based control. The indicator light provides
diagnostic information for lockout, recycling
and cad cell status. There is a manual reset
button to exit the Lockout Mode.
ii.
Pump Priming Cycle: To facilitate purging
air from the oil lines and filters, the 7505 can
be placed in a purge routine by:
• After the burner starts, press and hold
the reset button for 15 seconds until the
yellow light turns on. This indicates that
the button has been held long enough.
• Release the reset button. The yellow light
will turn off and the burner will start up
again.
• At burner start up, click the reset button
while the igniter is till on. This will
Figure 21: GeniSys 7505 Oil Primary Terminals,
LED's and Reset Button
Содержание V13A RO/FO
Страница 5: ...5 SECTION I GENERAL INFORMATION Figure 1 VI RO FO Water Boiler with Tankless Heater Beckett AFG Burner...
Страница 40: ...40 XI REPAIR PARTS continued Figure 25 Flush Jacket Components...
Страница 42: ...42 XI REPAIR PARTS continued Figure 26 V1 RO FO Trim and Controls...
Страница 48: ...48 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...