background image

3

111241-01 - 3/21

  WARNING

    The following should be done on a continuous basis:

• Safe reliable operation of this boiler depends on proper periodic service by a qualified installer, service 

agency or gas supplier.

• Proper air is essential for safe boiler operation. Do not block any fresh air opening.
•  Keep area around boiler free of objects which are flammable or which could obstruct flow of air into 

and around the boiler.

• Do not store or use sources of halogens such as bleaches, fabric softeners, paints, cleaners, 

refrigerants and cat boxes near the boiler. Traces of these chemicals can be drawn into the boiler 
causing severe corrosion damage to boiler and/or objectionable odors.

• Any damage caused by improper fuels, fuel additives or contaminated combustion air that may cause 

fireside corrosion and/or clogging of burners or heat exchanger is not covered by the product warranty.

• Do not expose boiler to large amounts of dust such as generated by dry wall construction, fiberglass 

insulation or woodworking.

1.  A qualified installer, service agency or gas supplier must perform maintenance procedures shown in the 

Installation, Operating, and Service Instructions on an 

annual basis

.

2.  Owner should visually inspect venting system on a 

monthly basis

. If any of the following conditions are found, 

the boiler should be shut down and a qualified installer, service agency or gas supplier called to correct the 

problem before boiler is placed back in service: 

 

•  Loose joints, corrosion or other deterioration

 

•  Condensate leakage

 

•  Sags in horizontal runs of vent pipe

 

•  (Chimney vent boilers only) Blocked vent switch not surely attached as shown in Figure 1 or 2, as  

 

 applicable

3.  Owner should also perform a 

monthly

 visual inspection of boiler and surrounding system piping. To do this, 

remove boiler jacket door. If any of the following are found, a qualified installer, service agency or gas supplier 

should be consulted immediately:

 

•  Deterioration of  the visible controls, wiring, and sheet metal components

 

•  Heating system water leaks

 

•  Black carbon (“soot”) in or near the burner compartment area. See Figure 3 or 4

4.  Steam Boilers – Steam boilers require 

occasional

 additions of makeup water to replace the small amount of 

water lost through radiator and system vents. If an automatic water feeder is installed, this device should add 

enough water on its own for boiler to operate. If there is no feeder and boiler needs more water, the red or yellow 

"Low Water" light will be illuminated on the low water cut-off located on side of boiler. Wait at least 15 minutes 

for all water in system to return to boiler and then open manual feed valve to add water. Stop adding water 

when water level in gage glass reaches Boiler's Nominal Water Level (NWL). Consult Installation, Operating and 

Service Instructions for NWL. Consult a qualified installer, service agency  or gas supplier if you are not sure of 

the location of the manual feed valve or cannot see the water level in the glass. 

5.  Auxiliary Controls – Many boilers are installed with equipment not supplied with the boiler, but which is critical for 

safe, reliable operation of the boiler. Some examples of this type of equipment include zone controls and boiler 

feed pumps. Make sure that this equipment is maintained in accordance with its manufacturer’s instructions.

Maintenance

  WARNING

      Black carbon (“soot”) in or near the burner compartment area is an indication of a potential carbon 

monoxide hazard. If carbon is found, the boiler should be shut down immediately and inspected by 
a qualified installer, service agency or gas supplier. The cause of the sooting should be found and 
corrected before the boiler is restarted.

CAUTION

      If it is necessary to either manually or automatically add water to a boiler more than once a month, a 

qualified installer, service agency or gas supplier should inspect the system for leaks or defective vents. 
Frequent additions of fresh water can result in severe damage to boiler.

!

!

!

Отзывы: