background image

2

111241-01 - 3/21

1.  Instructions to safely light and shut down this boiler is shown on page 5, as well as on a label affixed to the 

boiler. When the boiler is working properly, this boiler will light and shut down automatically in response to the 

building thermostats(s). If it does not, the boiler must be inspected by a qualified installer, service agency or  

gas supplier.

2.  All boilers are equipped with a means of preventing the boiler from firing if there is an excessive blockage in the 

vent system. Boilers designed for chimney venting are equipped with a blocked vent switch located as shown in 

Figure 1 or 2, depending on the specific boiler design. If this switch opens, the boiler will not fire. Call a qualified  

installer, service agency or gas supplier to diagnose and the problem and reset this switch if necessary.

3.  All boilers are equipped with a flame rollout switch located as shown in Figure 3 or 4, depending on specific 

boiler design. This switch will shut the burners down in the event that flames exit the burner compartment 

through the front opening. If this happens, the flame rollout switch must be replaced. If the boiler fails to fire, call 

a qualified installer, service agency or gas supplier to diagnose and correct the problem.

Basic Operation

  WARNING

•  A shutdown of the burners due to the blocked vent switch is an indication that there is a problem with 

the vent system, such as a blockage, or the combustion air supply. The blocked vent switch should 
only be reset after a qualified installer, service agency or gas supplier has diagnosed and corrected the 
venting/combustion air problem that caused the blocked vent switch to open.

   

 

 In the event that the flame rollout switch opens, the cause of the flame rollout must be diagnosed and 

corrected by a qualified gas service technician before the boiler is restarted.

•  A “tripped” flame rollout switch must be replaced by an identical switch having the same 

temperature setting.

•  Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical 

supply to the pump. Instead, shut off the gas supply at a location external to the appliance.

•  Do not use this boiler if any part has been under water. Immediately call a qualified installer, service 

agency or gas supplier to inspect the boiler and to replace any part of the control system and any gas 
control which has been under water.

•  This boiler is equipped with safety devices, which could cause it to shutdown, requiring service to 

restore normal operation. Where such a shutdown could result in damage from low temperatures (such 
as frozen pipes), do not leave the heating system unattended during cold weather unless alarms or 
other safeguards are in place to prevent damage. 

!

Отзывы: