Configuration Guide
Leviton Dimensions 4000 Series Architectural Lighting Controller
Page 66
OPERATION
SETUP
QUICK START
OV
ERVI
EW
CONFIGURATION
•
MAX
•
OFF
Step 7:
For the following types, Scene, Max and OFF, you must
also set a delay time. Press the
Left
and
Right
buttons to highlight a Delay time.
Step 8:
Press the
Up
and
Down
buttons to change
the value.
Step 9:
Press
Select/Save
to save the value.
Step 10:
Repeat Steps 4-9 for each Sequence you wish to
program.
Step 11:
Press the
Menu/Cancel
button to exit this menu.
The “SKIP” control command is a way to insert a
“place holder” or “no operation” when you want to
temporarily exclude some other scene or control
command... then put it back at a later time.
Enabling the Sequencer
The sequence can be started and stopped either from the
operational level menus, “Enabling the Sequencer” on page 50,
or, from a sequencer command station for which information can
be found on our product data sheets.
Viewing the Sequence
The sequencer causes Scenes to be activated in a timed
sequence. The sequence may be programmed to run once or
continuously in a loop. The sequence can be activated manually
(preset/scene buttons) or by the event timer (scheduler). The
sequence can be sub-divided into groups of events simply by the
use of commands that start it (GOTO a specific step).
To view the sequencer:
Step 1:
Press the
Menu/Cancel
button.
Step 2:
Press the
Up
and
Down
buttons until
VIEW
SEQUENCER?
flashes on the LCD display.