3
STEP 6:
Insert the battery platform
in the bottom of the enclosure. The
battery platform has cutouts so
wires can be routed under the bat-
tery as needed.
STEP 7:
Attach the Black DIN Rail adapters to the charge controller
using the screws provided. Use 3 screws per adapter. Clip the control-
ler to the DIN rail by hooking the bottom under the DIN rail then lifting
the controller up and over the top lip of the DIN Rail.
STEP 8:
Install 1 or 2 or 4 batteries in a 12V or 24V configuration, de-
pending on which system you purchased. Remove the battery cable
fuse before connecting the batteries to avoid any accidental shorting.
Connect battery cables and PowerVent fan cables to the Solar Control-
ler battery input (BAT+ & BAT-), then to battery terminals. Observe
proper polarity. Red wire is always V+. If two battery cables are sup-
plied with the system you must use both cables. If batteries are mount-
ed on their side use a rubber bumper on each terminal to prevent
shorts.
STEP 9:
Connect the 600W 48V battery charger to the Solar Controller
PV input (PV+ & PV-). Make sure to observe proper polarity. Brown
wire is V+. The controller has a pluggable 3 wire AC cord. You can cut
this cord to hardwire into the mains. You can also mount conduit to the
enclosure if local codes require it. During operation the charger fan may
run. This is normal.
STEP 10:
Mount any customer electronics to the inside of the enclo-
sure. Connect any loads to the Solar Controller LOAD output. (LOAD+
& LOAD-). Press red SET button to turn on/off the LOAD output.
Note:
There are multiple cable gland feedthrough in the bottom of the
enclosure. If you are not using any of the feedthrough you can cut a
short piece of wire, put it through the cable gland and tighten the cable
gland on the wire to seal it.
STEP 11:
Double check wiring and then re-install the battery cable fuse
to energize the system, The solar controller display shows battery volt-
age, charging voltage, charging current, load current and temperature.
CAUTION:
Reverse polarity will damage the equipment.
STEP 12:
Make sure lid gasket is clean and free from any particles,
then close the cover, making sure that wires are clear of the seam and
hinge area.
STEP 13:
The UPSPro
®
is Solar Ready™ so a solar panel can be add-
ed to provide supplemental or full time power. The solar panel will be
connected to PV input (PV+ & PV-) in parallel with AC Battery Charger.
The solar panel PV+ must be connected to the solar controller through
an 80V-100V blocking diode (
Tycon PN 5600059
) to prevent reverse
current to the solar panel.