Tyco DV-5A Скачать руководство пользователя страница 5

TFP1466

Page 5 of 18

Operation

The TYCO DV-5

a

 Valve is a diaphragm 

style valve that depends upon water 

pressure in the Diaphragm Chamber 

(see Figure 2A) to hold the Diaphragm 

closed against the water supply 

pressure.
When the DV-5

a

 Valve is set for service, 

the Diaphragm Chamber is pressurized 

through the trim connections from the 

inlet side of the system’s main control 

valve.

Opening of a solenoid valve for Electric/

Electric Actuation (see Figure 4) trips the 

Model MRA-1 Manual Reset Actuator. 

Tripping the MRA-1 releases water from 

the DV-5

a

 

Diaphragm Chamber faster 

than it can be replenished through the  

1/8 in. (3,2 mm) restriction located in 

the diaphragm chamber supply con-

nection. Release of water through the 

MRA-1 results in a rapid pressure drop 

in the DV-5

a

 

Diaphragm Chamber. The 

force differential applied through the 

Diaphragm to hold the Diaphragm in 

the set position is then reduced below 

the valve trip point. The water supply 

pressure then forces the Diaphragm 

open permitting water to flow into 

the system piping, as well as through 

the Alarm Port to actuate the system 

alarms (see Figure 2B).

Upon opening of the DV-5

a

 Valve, the 

Model MRA-1 Manual Reset Actua-

tor opens to constantly vent the DV-5

a

 

Diaphragm Chamber to "hydraulically 

latch" the DV-5

a

 in the tripped position 

until manually reset.
See Electric/Electric Actuation sub-

section for additional information.

3 INCH (DN80)

2 INCH (DN50)

4 INCH (DN100)

8 INCH (DN200)

1-1/2 INCH (DN40)

6 INCH (DN150), 165,1 mm

200

400

1000

3000

2000

600

100

50

5000

2000

3000

10000

7000

1000

600

400

200

4000

15000

9.0
8.0

4.0

6.0

5.0

7.0

3.0

2.0

1.0

0.7

0.9
0.8

0.5

0.4

0.6

0.3

NOMINAL PRESSURE DROP IN BAR

(1 PSI = 0,06895 BAR)

FLOW RATE IN LITERS PER MINUTE (LPM)

(1 GPM = 3,785 LPM)

NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

FLOW RATE IN GALLONS PER MINUTE (GPM)

0,022

0,080

0,030

0,040

0,060

0,050

0,070

0,100
0,090

0,200

0,300

0,400

0,500

0,600

GRAPH A 

DV-5

a

 VALVE 

NOMINAL PRESSURE LOSS VERSUS FLOW

Содержание DV-5A

Страница 1: ...llations The DV 5a Valves are offered with the DV 5a Valve and separately ordered semi assembled trim shown in Figures 6 and 7 or for ease of installation with DV 5a Valve completely trimmed with or w...

Страница 2: ...Numbers given do not replace Hex Bolt Hex Nut Lift Washer or Hoist Ring with common hardware parts e Also applicabale to metric 165 1 mm size 1 1 2 AND 2 INCH VALVES ONLY 6 AND 8 INCH VALVES ONLY 7 9...

Страница 3: ...TEM OPEN TO ATMOSPHERE ALARM PORT WATERFLOW TO ALARM WATER SUPPLY PRESSURE ALARM TEST SYSTEM DRAIN OPEN SYSTEM DRAIN OPEN MAIN DRAIN CLOSED MAIN DRAIN OPEN DIAPHRAGM CHAMBER SUPPLY FROM UPSTREAM SIDE...

Страница 4: ...es are pressure rated to 16 bar Valve Trim The maximum pressure rating for the Electric Electric Double Interlock Pre action Trim is dependent on separately ordered solenoid valve per Technical Data S...

Страница 5: ...ed below the valve trip point The water supply pressure then forces the Diaphragm open permitting water to flow into the system piping as well as through the Alarm Port to actuate the system alarms se...

Страница 6: ...s that may be used with this trim package is given in Technical Data Sheet TFP2180 Nominal installation dimensions for the Double Interlock Preaction System With Electric Electric Actuation Trim are s...

Страница 7: ...uired when the valve is exposed to such supplies and other corrosive conditions or chemicals that could impact valve materials or the operation of the assembly The system and all components must be de...

Страница 8: ...ating lever by pushing it up Do not close the hinged cover at this time Step 11 After allowing water to flow out of the Manual Reset Actuator N drain tube until aerated water ceases to dis charge rese...

Страница 9: ...e and Item A7 is provided as P N 52 287 1 124 described in Technical Data Sheet TFP2180 4 When ordering DV 5A Trim separately from the DV 5A Valve Items A1 through A10 are separately ordered as applic...

Страница 10: ...CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003 10 1 1 2 SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007 11 1 1 2 Y STRAINER 523531006 523531006 5...

Страница 11: ...x 5 1 2 x 5 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 6 1 2 52 1 PIPE NIPPLE 1 2 x 5 1 2 x 5 1 2 x 4 1 2 1 2 x 5 1 2 x 7 1 2 1 2 x 9 1 2 53 1 PIPE NIPPLE 3 4 x 5 3 4 x 5 3 4 x 6 3 4 x 7 3 4 x 9 3 4 x...

Страница 12: ...3 6 91 4 100 4 5 114 11 9 302 12 6 320 16 5 419 21 0 533 5 5 140 16 8 427 4 54 115 4 3 109 63 150 5 7 145 13 4 340 14 5 368 18 4 467 24 8 630 3 8 97 22 4 569 5 83 148 5 7 145 8 200 6 8 174 16 1 409 16...

Страница 13: ...ividual instructions for the solenoid valve dry pilot actuator manual control station switches and pressure maintenance device should be reviewed The following procedures pertain to the automatic cont...

Страница 14: ...matic Drain Valve Alarm Test Valve Alarm Control Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Item Description N P Q R S T U V W X Manual Reset Actuator Diaphr...

Страница 15: ...ed to the Model MRA 1 Manual Reset Actuator N That the Waterflow Pressure Switch C and its associated alarms prop erly operate That the Water Motor Alarm if appli cable properly operates NOTE Thisproc...

Страница 16: ...4 in DN100 550011540 6 in DN150 550011560 8 in DN200 550011580 Flange x Flange ANSI 3 in DN80 550021530 4 in DN100 550021540 6 in DN150 550021560 8 in DN200 550021580 Flange x Grooved ANSI 3 in DN80...

Страница 17: ...External Trim Connections drains pressure switches water motor alarms etc APAC DV 5A Valves with Galvanized Trim Specify Size specify DV 5a Auto matic Water Control Valve specify end connection with a...

Страница 18: ...DV 5a Valve Trim P N See Figure 6 DV 5A Valve Trim Accessories for separately ordered valve trim Specify Specify Accessory Descrip tion P N specify Model QRS Quick Refer to Technical Release Switch Q1...

Страница 19: ...Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Manual Reset Actuator A B C J K D E F G N P Q V X Y M W S T R L Z U H AA W H General Description The appendix fou...

Страница 20: ...ure is within normally expected range 2 If below normal range correct any leakage from diaphragm chamber prior to resetting the system 3 When water supply pressure is restored reset DV 5a Valve in acc...

Отзывы: