Tyco DV-5A Скачать руководство пользователя страница 15

TFP1466

Page 15 of 18

Electric/Electric Actuation  

System Operation Procedure

Proper operation of the DV-5

a

 Valve for 

both opening of the DV-5

a

 Valve in a 

fire condition, or not opening the DV-5

a

 

Valve in a non-fire condition, must be 

verified as follows:

Step 1.

 Close the System Main Control 

Valve (B) and then open the Main Drain 

Valve (D).

Step 2.

 Manually operate Zone 1 of 

the Releasing Panel, and verify the 

following:
•  The operation of the Releasing Panel 

and its associated alarms

•  That there is no leakage from the 

Solenoid Valve (V)

NOTE:

 During this procedure, the Solenoid 

Valve (V) should remain closed and the 

DV-5

a

 Deluge Valve Diaphragm Chamber 

should remain pressurized.
This procedure is used to verify that the 

DV-5

a

 Deluge Valve will remain set if the 

electric detection system (Zone 1) operates 

but the sprinkler system (Zone 2) remains 

in its normally pressurized condition.

Step 3.

 Restore the electric fire detec-

tion system to a normal condition in 

accordance with the manufacturer’s 

instructions.

Step 4.

 Open the Inspector’s Test Con-

nection to relieve system air pressure, 

and verify the following:
•  That the Low Air Pressure Alarm 

Switch (U) and Zone 2 of the Releas-

ing Panel, as well as its associated 

alarms, operate properly. The Low 

Air Pressure Alarm Switch (U) should 

operate at the previously established 

pressure (see Installation section, 

Step 9).

•  That there is no leakage from the 

Solenoid Valve (V).

Step 5.

 Close the Inspector’s Test 

Connection.

NOTE:

 During this procedure, the Solenoid 

Valve (V) should remain closed and the 

DV-5

a

 Valve Diaphragm Chamber should 

remain pressurized.
This procedure is used to verify that the 

DV-5

a

 Valve will remain set if the Low 

Air Pressure Alarm Switch (U) (Zone 2) 

operates due to loss of system air pressure 

and the electric detection system (Zone 1) 

remains in a normal condition.

Step 6.

 Restore the electric fire detec-

tion system to a normal condition in 

accordance with the manufacturer’s 

instructions after the system air pres-

sure has automatically been restored 

to normal.

Step 7.

 Close the System Shut-Off 

Valve (W) after the system air pressure 

has been restored to normal.

Step 8.

 Open the System Main Control 

Valve (B) one turn beyond the position 

at which water just begins to flow from 

the Main Drain Valve (D).

Step 9.

 Close the Main Drain Valve (D).

Step 10.

 Close the Air Supply Valve (S).

Step 11.

 Manually operate Zone 1 of 

the Releasing Panel, and then operate 

Zone 2 of the Releasing Panel by par-

tially opening the System Drain Valve 

(E) to relieve air pressure at the Low Air 

Pressure Alarm Switch (U), and verify 

the following:
•  That the DV-5

a

 Valve operates as is 

indicated by a discharge of water 

from the System Drain Valve (E) and 

the Automatic Drain Valve (F). The 

Automatic Drain Valve (F) may or may 

not close depending on the flow past 

the partially open System Main Con-

trol Valve (B)

•  That the Model MRA-1 Manual Reset 

Actuator (N) has operated as is indi-

cated by water discharging into the 

Drip Funnel from the 1/2 in. drain 

tube connected to the Model MRA-1 

Manual Reset Actuator (N)

•  That the Waterflow Pressure Switch 

(C) and its associated alarms prop-

erly operate

•  That the Water Motor Alarm, if appli-

cable, properly operates

NOTE:

 This procedure simulates automatic 

system operation upon both electric 

detection and loss of system air pressure.

Internal Valve Inspection

Once every five years during the annual 

operational test procedure and prior 

to the DV-5

a

 Valve being reset and 

with the DV-5

a

 

Valve de-pressurized, 

the interior of the DV-5

a

 

Valve must 

be cleaned and inspected for wear 

and damage. Damaged or worn parts 

must be replaced. (Replacement of the 

Diaphragm every ten years is recom-

mended, or more frequently if inspec-

tions and/or wear and tear warrant 

more frequent replacement.)

NOTICE

The Diaphragm Cover may be removed 

between Steps 4 and 5 of the reset-

ting instructions, since at that point the 

DV-5

a

 

Valve should be de-pressurized 

as evident by a zero gauge reading on 

the Diaphragm Gauge (K) and Water 

Supply Gauge (J), as well as no water 

discharging from the Automatic Drain 

Valve (F).

To perform internal valve inspection 

between Steps 4 and 5 of the Valve 

Setting Procedure remove the Dia-

phragm cover as follows:

Step 1.

 Close the Inverted Flare Shut-

Off Valve (R).

Step 2.

 Remove the Copper Tube 

Fitting between the Diaphragm Supply 

Valve (P) and the Inverted Flare Shut-

Off Valve (R).

Step 3.

 Loosen the union securing the 

Electric/Electric Actuation Trim and 

remove the Electric/Electric Actuation 

Trim.

Step 4.

 Loosen and remove the union 

between the Diaphragm Cover and the 

MRA-1 Manual Reset Actuator (N) and 

remove the MRA-1 Manual Reset Actu-

ator (N) subassembly.

Step 5.

 Remove the Diaphragm Valve 

Cover hardware, then slowly remove 

the Diaphragm Cover and perform 

internal valve inspection. Clean the 

valve interior and replace parts as 

necessary.
After cleaning and inspecting valve 

interior, and replacing parts as nec-

essary, reinstall the Diaphragm Cover 

by completing the following steps to 

assure the Diaphragm Cover Fasteners 

are uniformly and securely tightened.

Step 1.

 With reference to Figure 1, 

ensure that the Diaphragm is properly 

oriented and that the proper hardware 

arrangement is utilized when assem-

bling the Diaphragm Covers. The hard-

ware arrangements differ depending on 

the size of the DV-5

a

 Valve.

Step 2.

 By first using the Long Hex 

Bolts, support of the Diaphragm Cover 

will be provided before installing the 

Short Hex Bolts. Align Diaphragm in 

proper orientation with Valve Body, and 

then align Diaphragm Cover in proper 

orientation with Valve Body. Hand-

tighten all fasteners.

Step 3.

 Using crossdraw sequence 

to assure uniformity, wrench-tighten 

Long Hex Bolts and Short Hex Bolts 

to appropriate torque values. Repeat 

crossdraw sequence two to three 

times at incremental torque valves 

until reaching the torque valves found 

in Table B.

Step 4.

 Inspect to assure all Hex Bolts 

are securely tightened.

Step 5.

 Using the union, secure the 

MRA-1 Manual Reset Actuator (N) to 

the Diaphragm Cover.

Step 6.

 Using the union, secure the 

Electric/Electric Actuation Trim.

Step 7.

 Replace the Copper Tube 

Fitting between the Diaphragm Supply 

Valve (P) and the Inverted Flare Shut-

Off Valve (R).

Содержание DV-5A

Страница 1: ...llations The DV 5a Valves are offered with the DV 5a Valve and separately ordered semi assembled trim shown in Figures 6 and 7 or for ease of installation with DV 5a Valve completely trimmed with or w...

Страница 2: ...Numbers given do not replace Hex Bolt Hex Nut Lift Washer or Hoist Ring with common hardware parts e Also applicabale to metric 165 1 mm size 1 1 2 AND 2 INCH VALVES ONLY 6 AND 8 INCH VALVES ONLY 7 9...

Страница 3: ...TEM OPEN TO ATMOSPHERE ALARM PORT WATERFLOW TO ALARM WATER SUPPLY PRESSURE ALARM TEST SYSTEM DRAIN OPEN SYSTEM DRAIN OPEN MAIN DRAIN CLOSED MAIN DRAIN OPEN DIAPHRAGM CHAMBER SUPPLY FROM UPSTREAM SIDE...

Страница 4: ...es are pressure rated to 16 bar Valve Trim The maximum pressure rating for the Electric Electric Double Interlock Pre action Trim is dependent on separately ordered solenoid valve per Technical Data S...

Страница 5: ...ed below the valve trip point The water supply pressure then forces the Diaphragm open permitting water to flow into the system piping as well as through the Alarm Port to actuate the system alarms se...

Страница 6: ...s that may be used with this trim package is given in Technical Data Sheet TFP2180 Nominal installation dimensions for the Double Interlock Preaction System With Electric Electric Actuation Trim are s...

Страница 7: ...uired when the valve is exposed to such supplies and other corrosive conditions or chemicals that could impact valve materials or the operation of the assembly The system and all components must be de...

Страница 8: ...ating lever by pushing it up Do not close the hinged cover at this time Step 11 After allowing water to flow out of the Manual Reset Actuator N drain tube until aerated water ceases to dis charge rese...

Страница 9: ...e and Item A7 is provided as P N 52 287 1 124 described in Technical Data Sheet TFP2180 4 When ordering DV 5A Trim separately from the DV 5A Valve Items A1 through A10 are separately ordered as applic...

Страница 10: ...CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003 10 1 1 2 SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007 11 1 1 2 Y STRAINER 523531006 523531006 5...

Страница 11: ...x 5 1 2 x 5 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 6 1 2 52 1 PIPE NIPPLE 1 2 x 5 1 2 x 5 1 2 x 4 1 2 1 2 x 5 1 2 x 7 1 2 1 2 x 9 1 2 53 1 PIPE NIPPLE 3 4 x 5 3 4 x 5 3 4 x 6 3 4 x 7 3 4 x 9 3 4 x...

Страница 12: ...3 6 91 4 100 4 5 114 11 9 302 12 6 320 16 5 419 21 0 533 5 5 140 16 8 427 4 54 115 4 3 109 63 150 5 7 145 13 4 340 14 5 368 18 4 467 24 8 630 3 8 97 22 4 569 5 83 148 5 7 145 8 200 6 8 174 16 1 409 16...

Страница 13: ...ividual instructions for the solenoid valve dry pilot actuator manual control station switches and pressure maintenance device should be reviewed The following procedures pertain to the automatic cont...

Страница 14: ...matic Drain Valve Alarm Test Valve Alarm Control Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Item Description N P Q R S T U V W X Manual Reset Actuator Diaphr...

Страница 15: ...ed to the Model MRA 1 Manual Reset Actuator N That the Waterflow Pressure Switch C and its associated alarms prop erly operate That the Water Motor Alarm if appli cable properly operates NOTE Thisproc...

Страница 16: ...4 in DN100 550011540 6 in DN150 550011560 8 in DN200 550011580 Flange x Flange ANSI 3 in DN80 550021530 4 in DN100 550021540 6 in DN150 550021560 8 in DN200 550021580 Flange x Grooved ANSI 3 in DN80...

Страница 17: ...External Trim Connections drains pressure switches water motor alarms etc APAC DV 5A Valves with Galvanized Trim Specify Size specify DV 5a Auto matic Water Control Valve specify end connection with a...

Страница 18: ...DV 5a Valve Trim P N See Figure 6 DV 5A Valve Trim Accessories for separately ordered valve trim Specify Specify Accessory Descrip tion P N specify Model QRS Quick Refer to Technical Release Switch Q1...

Страница 19: ...Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Manual Reset Actuator A B C J K D E F G N P Q V X Y M W S T R L Z U H AA W H General Description The appendix fou...

Страница 20: ...ure is within normally expected range 2 If below normal range correct any leakage from diaphragm chamber prior to resetting the system 3 When water supply pressure is restored reset DV 5a Valve in acc...

Отзывы: