![Tyco DV-5A Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/tyco/dv-5a/dv-5a_manual_1185740016.webp)
TFP1466
Page 16 of 18
Step 8.
Ensure that the unions and flare
fittings are securely tightened.
Step 9.
With the Diaphragm Supply
Valve (P) closed, fully open the Inverted
Flare Shut-Off Valve (R) stainless steel
screw (approximately 1/2 in.) until resis-
tance is met so as not to break the
internal roll-pin. The internal roll-pin
stops the removal of the Inverted Flare
Shut-Off Valve (R) stainless steel screw.
Step 10.
Proceed with Step 5 of the
Valve Setting Procedures section in this
data sheet.
NOTICE
If the water supply contains chemicals
which tend to attack a polyester fabric-
reinforced, EPDM rubber or the five year
inspection indicates a build-up of debris
within the
DV-5
a
Valve
that could affect
its proper operation, then the frequency
of the internal valve inspection procedure
must be appropriately increased.
With reference to Figure 1, make
certain that the Diaphragm is correctly
oriented; otherwise, the DV-5
a
Valve
cannot be properly set.
Under-tightening the Diaphragm Cover
Bolts can result in internal and external
leakage.
Use only TYCO replacement fasteners
as specified in Figure 1.
Do not apply adhesives, lubricants, or
other substances to the Diaphragm
Valve Body.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Order the TYCO DV-5
a
Automatic
Water Control Valves as follows:
Pre-Assembled Valves
with Trim
DV-5
A
Valves with Galvanized Trim
and Butterfly Valve
Specify: Size (specify), DV-5
a
Auto-
matic Water Control Valve, G x G con-
nections with assembled galvanized
Americas Double Interlock Preac-
tion with Electric/Electric Actuation
Trim, complete with assembled Model
BFV-300 Butterfly Valve, P/N (specify):
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 551011515
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 551011520
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 551011530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 551011540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 551011560
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 551011580
Notes:
Americas pressure switches, P/N 52-287-
1-124 Solenoid Valve, and psi/kPa water
pressure gauges are provided.
This arrangement is available for EMEA
and APAC upon request. Contact your
local distributor.
AMERICAS
DV-5
A
Valves with Galvanized Trim
Specify: Size (specify), DV-5
a
Auto-
matic Water Control Valve, (specify)
end connection with assembled galva-
nized Americas, Double Interlock Pre-
action Electric/Electric Actuation Trim,
P/N (specify):
Grooved x Grooved
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550011515
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550011520
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550011530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550011540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550011560
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550011580
Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550021540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550021560
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550021580
Flange x Grooved ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550031530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550031540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550031560
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550031580
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550061515
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550061520
Note:
Pressure switches, P/N 52-287-1-124
solenoid valve, and psi/kPa water pressure
gauges are provided.
Separate DV-5
A
Valves without Trim
See Table A for flange drilling
specifications.
Specify: Size (specify), DV-5
a
Auto-
matic Water Control Valve, (specify)
end connection, P/N (specify):
Groove x Groove
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530010015
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 530010040
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 530010060
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . .530020030
4 in. (DN100). . . . . . . . . . . . . . . . . . . .530020040
6 in. (DN150). . . . . . . . . . . . . . . . . . . .530020060
8 in. (DN200) . . . . . . . . . . . . . . . . . . .530020080
Flange x Groove ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . .530030030
4 in. (DN100). . . . . . . . . . . . . . . . . . . .530030040
6 in. (DN150). . . . . . . . . . . . . . . . . . . .530030060
8 in. (DN200) . . . . . . . . . . . . . . . . . . .530020080
T x T NPT
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 530060015
2 in. (DN50) . . . . . . . . . . . . . . . . . . . .530060020
Notes:
Valves are typically provided with flange
drilling per ANSI B16.1 (Class 125) or ISO
(7005-2 PN16).
Upon request, valves can be provided with
flange drilling per JIS B 2210 or AS 2129. In
which case part numbers are not assigned.
DV-5
A
Valve Trim
Specify: Size (specify), finish (specify),
Electric/Electric Actuation Trim for
DV-5
a
Automatic Water Control Valves
used in Double Interlock Preaction Fire
Protection System, P/N (specify):
Galvanized
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 540001520
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001520
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 540001540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 540001560
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 540001580
Black
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 542001520
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 542001520
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 542001530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 542001540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 542001560
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 542001580
Note:
Pressure switches and/or solenoid
valves for electric actuation are separately
ordered.
EMEA
DV-5
A
Valves with Galvanized Trim
Specify: Size (specify), DV-5
a
Auto-
matic Water Control Valve, (specify)
end connection with assembled gal-
vanized EMEA, Double Interlock Pre-
action Electric/Electric Actuation Trim,
P/N (specify):
Grooved x Grooved
1 1/2 in. (DN40) . . . . . . . . . . . . . . . . . 550111515
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550111520
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550111530
4 in. (DN100). . . . . . . . . . . . . . . . . . . . 550111540
6 in. (DN150). . . . . . . . . . . . . . . . . . . . 550111560
165,1 mm . . . . . . . . . . . . . . . . . . . . . . 550111566
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 550111580
Nominal
Valve Sizes
ANSI
Inches
(DN)
Torque
lb-ft
(N∙m)
Nuts
Short
Hex
Bolts
1 1/2
(40)
44
(59,7)
35
(47,5)
2
(50)
44
(59,7)
35
(47,5)
3
(80)
125
(169,5)
125
(169,5)
4
(100)
150
(203,4)
150
(203,4)
6
1
(150)
150
(203,4)
150
(203,4)
8
(200)
188
(254,9)
188
(254,9)
NOTES
1. Also applicable to metric 165,1 mm size.
TABLE B
DIAPHRAGM COVER BOLTS
MINIMUM TORQUE