Tyco DV-5A Скачать руководство пользователя страница 13

TFP1466

Page 13 of 18

Care and 

Maintenance

The following procedures and inspec-

tions must be performed as indicated, 

in addition to any specific require-

ments of the NFPA and any applicable 

standards recognized by the Approval 

agency. Any impairment must be imme-

diately corrected. See Figure 8.

NOTICE

If the water supply needs to be shut off 

to the DV-5

a

 valve and trim and cannot 

be shut off upstream of the system, 

close the System Main Control Valve 

(B), the Diaphragm Supply Valve (P),  

and the Water Supply Shut-Off Valve 

(R). This will allow any trim above the 

System Main Control Valve (B) to be 

taken apart for service if necessary.
The frequency at which the following 

procedures and inspections are to be 

performed are to be in accordance with 

the NFPA and any applicable specific 

requirements of the standards recog-

nized by the Approval agency.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system that 

it controls, permission to shut down 

the affected fire protection systems 

must first be obtained from the proper 

authorities and all personnel who may 

be affected by this action must be 

notified.
The owner is responsible for the 

inspection, testing, and maintenance 

of their fire protection system and 

devices in compliance with this docu-

ment, as well as with the NFPA and any 

applicable standards recognized by the 

Approval agency. Contact the install-

ing contractor or product manufacturer 

with any questions.
Some procedures in this section result 

in the operation of the associated 

alarms. Notify the owner and the fire 

department, central station, or other 

signal station to which the alarms are 

connected before performing the tests.
It is recommended that automatic 

sprinkler systems be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with the 

NFPA and any applicable standards 

recognized by the Approval agency.

It is recommended that the System 

Inspection Procedure be performed 

at least semi-annually by a quali-

fied Inspection Service. The Double 

Interlock Preaction System Inspec-

tion Procedure may be followed in lieu 

of performing any of the operational 

tests recommended in the Technical 

Data Sheets for the 24 VDC Solenoid 

Valve and Model MC-1 Manual Control 

Station.
It is recommended that the individuals 

responsible for the care and mainte-

nance of the Double Interlock Preaction 

System develop a working understand-

ing of the system, in general, prior to 

performing inspection and/or mainte-

nance procedures. These instructions, 

as well as individual instructions for 

the solenoid valve, dry pilot actuator, 

manual control station, switches, and 

pressure maintenance device should 

be reviewed.
The following procedures pertain to 

the automatic control valve portion of 

the Double Interlock Preaction System. 

Refer to the manufacturer’s instructions 

and NFPA 25 for care and maintenance 

procedures for all other devices (e.g., 

electric detection, main control and 

system shut-off valves, supervisory 

devices, sprinklers, etc.).
Before performing the System Inspec-

tion Procedure or Waterflow Alarm 

Test Procedure, which will result in 

operation of alarms, notify the proper 

authorities and all personnel who may 

be affected.

Drop in Water Supply Pressure 

Below Normal Range

NOTICE

If the water supply pressure is signif-

icantly reduced below the normally 

expected static pressure range (as 

could occur in the case of a water main 

break or repair), and there is a subse-

quent drop in the diaphragm chamber 

water pressure below its normal range 

(for example, due to a leak in a piping 

connection to or from the diaphragm 

chamber or, a leak in the diaphragm 

chamber check valve caused by dirt or 

debris in the check valve seal area), a 

deluge valve such as the DV-5

a

 could 

inadvertently trip, if its water supply 

pressure is quickly restored.

A drop in the water supply pressure 

to below its normal range (as in the 

case of an interrupted water supply 

condition) constitutes an emergency 

impairment.
Should this condition occur, immedi-

ately close the System Main Control 

Valve (B) and use the following proce-

dure to reset the system:

Step 1.

 Prior to the water supply pres-

sure being restored to the closed 

System Main Control Valve (B), note the 

pressure indicated by the Diaphragm 

Gauge (K) and determine if the pres-

sure is within the normally expected 

range.

Step 2.

 If the diaphragm chamber pres-

sure is below the normal range, check 

for and correct any source of leakage 

from the diaphragm chamber prior to 

resetting the system.

Step 3.

 After the water supply pres-

sure is restored to the System Main 

Control Valve (B), reset the DV-5

a

 Valve 

in accordance with the Valve Setting 

Procedure section.

NOTICE

For fire protection systems subject to 

an emergency impairment caused by 

an interrupted water supply condition, 

it is recommended that consideration 

be given to installing a low water supply 

pressure switch with the appropriate 

alarm/indications to monitor the water 

supply pressure.

Waterflow Alarm Test Procedure

To test the waterflow alarm, open the 

Alarm Test Valve (G), which will allow a 

flow of water to the Waterflow Pressure 

Switch (C) and/or Water Motor Alarm. 

Upon satisfactory completion of the 

test, close the Alarm Test Valve (G).
To ensure drainage of the alarm line, 

depress the plunger on the Automatic 

Drain Valve (F).

Содержание DV-5A

Страница 1: ...llations The DV 5a Valves are offered with the DV 5a Valve and separately ordered semi assembled trim shown in Figures 6 and 7 or for ease of installation with DV 5a Valve completely trimmed with or w...

Страница 2: ...Numbers given do not replace Hex Bolt Hex Nut Lift Washer or Hoist Ring with common hardware parts e Also applicabale to metric 165 1 mm size 1 1 2 AND 2 INCH VALVES ONLY 6 AND 8 INCH VALVES ONLY 7 9...

Страница 3: ...TEM OPEN TO ATMOSPHERE ALARM PORT WATERFLOW TO ALARM WATER SUPPLY PRESSURE ALARM TEST SYSTEM DRAIN OPEN SYSTEM DRAIN OPEN MAIN DRAIN CLOSED MAIN DRAIN OPEN DIAPHRAGM CHAMBER SUPPLY FROM UPSTREAM SIDE...

Страница 4: ...es are pressure rated to 16 bar Valve Trim The maximum pressure rating for the Electric Electric Double Interlock Pre action Trim is dependent on separately ordered solenoid valve per Technical Data S...

Страница 5: ...ed below the valve trip point The water supply pressure then forces the Diaphragm open permitting water to flow into the system piping as well as through the Alarm Port to actuate the system alarms se...

Страница 6: ...s that may be used with this trim package is given in Technical Data Sheet TFP2180 Nominal installation dimensions for the Double Interlock Preaction System With Electric Electric Actuation Trim are s...

Страница 7: ...uired when the valve is exposed to such supplies and other corrosive conditions or chemicals that could impact valve materials or the operation of the assembly The system and all components must be de...

Страница 8: ...ating lever by pushing it up Do not close the hinged cover at this time Step 11 After allowing water to flow out of the Manual Reset Actuator N drain tube until aerated water ceases to dis charge rese...

Страница 9: ...e and Item A7 is provided as P N 52 287 1 124 described in Technical Data Sheet TFP2180 4 When ordering DV 5A Trim separately from the DV 5A Valve Items A1 through A10 are separately ordered as applic...

Страница 10: ...CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003 10 1 1 2 SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007 11 1 1 2 Y STRAINER 523531006 523531006 5...

Страница 11: ...x 5 1 2 x 5 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 5 1 2 1 2 x 6 1 2 52 1 PIPE NIPPLE 1 2 x 5 1 2 x 5 1 2 x 4 1 2 1 2 x 5 1 2 x 7 1 2 1 2 x 9 1 2 53 1 PIPE NIPPLE 3 4 x 5 3 4 x 5 3 4 x 6 3 4 x 7 3 4 x 9 3 4 x...

Страница 12: ...3 6 91 4 100 4 5 114 11 9 302 12 6 320 16 5 419 21 0 533 5 5 140 16 8 427 4 54 115 4 3 109 63 150 5 7 145 13 4 340 14 5 368 18 4 467 24 8 630 3 8 97 22 4 569 5 83 148 5 7 145 8 200 6 8 174 16 1 409 16...

Страница 13: ...ividual instructions for the solenoid valve dry pilot actuator manual control station switches and pressure maintenance device should be reviewed The following procedures pertain to the automatic cont...

Страница 14: ...matic Drain Valve Alarm Test Valve Alarm Control Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Item Description N P Q R S T U V W X Manual Reset Actuator Diaphr...

Страница 15: ...ed to the Model MRA 1 Manual Reset Actuator N That the Waterflow Pressure Switch C and its associated alarms prop erly operate That the Water Motor Alarm if appli cable properly operates NOTE Thisproc...

Страница 16: ...4 in DN100 550011540 6 in DN150 550011560 8 in DN200 550011580 Flange x Flange ANSI 3 in DN80 550021530 4 in DN100 550021540 6 in DN150 550021560 8 in DN200 550021580 Flange x Grooved ANSI 3 in DN80...

Страница 17: ...External Trim Connections drains pressure switches water motor alarms etc APAC DV 5A Valves with Galvanized Trim Specify Size specify DV 5a Auto matic Water Control Valve specify end connection with a...

Страница 18: ...DV 5a Valve Trim P N See Figure 6 DV 5A Valve Trim Accessories for separately ordered valve trim Specify Specify Accessory Descrip tion P N specify Model QRS Quick Refer to Technical Release Switch Q1...

Страница 19: ...Valve Optional Water Supply Gauge Diaphragm Gauge System Gauge Manual Control Station Manual Reset Actuator A B C J K D E F G N P Q V X Y M W S T R L Z U H AA W H General Description The appendix fou...

Страница 20: ...ure is within normally expected range 2 If below normal range correct any leakage from diaphragm chamber prior to resetting the system 3 When water supply pressure is restored reset DV 5a Valve in acc...

Отзывы: