22
Setting the Valve
NOTE
It is normal for the control panel to indicate various supervisory conditions related to supervised
valve position and system air pressure while the valve is being set. These may be silenced by
pressing on the “Buzzer Silence” button.
Deluge Valve Setting Procedure
Perform Steps 1 through 13 when initially setting the TYCO DV-5A Valve, after an operational test
of the fire protection system, or after system operation due to a fire. Refer to Figures 7, 8, or 9,
as applicable.
Refer to Tyco Fire Products technical data sheet TFP1306 for complete maintenance, testing and
compliance requirements. For electrically actuated releases, make sure to replace any heat detectors
that may have been affected by heat, clean or replace any smoke detector heads affected by smoke
and to clear all smoke prior to resetting the control panel. Follow the instructions in the Installation,
Operation and Instruction Manual for the Potter PFC-4410RC
f
or complete resetting instructions.
1
DV-5A Valve
Auto.
2
System Main Control Valve
N.O.
3
Automatic Drain Valve
Auto.
4
Main Drain Valve
N.C.
5
Diaphragm Supply Valve
N.O.
6
Manual Reset Actuator
7
Wet Pilot Line Connection
8
Manual Control Station
N.C.
9
Alarm Test Valve
N.C.
10
Drip Funnel Drain
11
Water Supply Gauge
12
Gauge Test Valve
N.O.
13
Diaphragm Supply Strainer
14
Diaphragm Supply Check Valve
Auto.
15
Diaphragm Gauge
16
System Riser
17
Drain Header
18
Supply Header
19
Waterflow Pressure Switch
20
Water Motor Alarm Connection
21
Downstream Shut Off Valve
N.O
22
Funnel Drain Check Valve
Auto.
23
System Drain Valve
OP 1 Alarm Control Valve (Optional)
N.O.
Figure 4
Deluge Wet Pilot Schematic Piping Diagram
Содержание Deluge Red-E
Страница 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...
Страница 2: ......
Страница 5: ......
Страница 36: ...31 Figure 9 DV 5A Valve Remote Resetting Pressure Reducing Trim System Outlet Pressure Pilot Valve Adjustment...
Страница 79: ...74 Single Interlock Wiring Schematic Non Integrated Releasing Panel NOT USED ON WET OR DRY PILOT MODELS...
Страница 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...
Страница 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...
Страница 82: ...77 END...