![Tyco Deluge Red-E Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/tyco/deluge-red-e/deluge-red-e_installation-manual_1185845020.webp)
15
Double Interlock Preaction (Electric-Electric)
The PFC-4410RC has more than 20 standard programs which are detailed in the
Installation,
Operation and Instruction Manual for the Potter PFC-4410RC
. Red-E Cabinet
Double Interlock
Preaction (Electric-Electric)
configurations are pre-wired to function with standard program
#13.
CAUTION
Selecting a standard program other than #13 can cause unintended results if pre-wired devices are
re-assigned (e.g. supervisory switch assigned as a manual dump).
If the standard program is not acceptable for the installation required, select the custom program #0
then press the SET button. This will allow the user to custom program the panel. Refer to PFC-
4410RC Custom Program Information for Water Based Extinguishing Systems in
Installation,
Operation and Instruction Manual for the Potter PFC-4410RC
for custom program information.
PROGRAM #13 MODE
1. Apply power to panel.
2. Move the program switch to PROGRAM.
3. Press the FUNCTION button until the display reads “PASSWORD = 000”.
4. To enter a password, press the SELECT button until the proper number is displayed above the
symbol, then press the SET button to move to the next digit. After entering the third number the
display will change. (All panels are shipped with a 000 password.)
5. Press the FUNCTION button until the display reads “PROGRAM #”.
6. Press the SELECT button until the display reads “PROGRAM #13”.
7. Press the SET button.
8. The panel is completely programmed except for the custom banner and zone messages.
The panel should now display:
B A N N
E
R
M E S S A G E ?
SET
SELECT
Press the SELECT button to display the current message
FUNCTION
Содержание Deluge Red-E
Страница 1: ...Installation Guide Doc DV5A RED E 001 REV2 06 2019...
Страница 2: ......
Страница 5: ......
Страница 36: ...31 Figure 9 DV 5A Valve Remote Resetting Pressure Reducing Trim System Outlet Pressure Pilot Valve Adjustment...
Страница 79: ...74 Single Interlock Wiring Schematic Non Integrated Releasing Panel NOT USED ON WET OR DRY PILOT MODELS...
Страница 80: ...75 Double Interlock Electric Pneumatic Wiring Schematic Non Integrated Releasing Panel...
Страница 81: ...76 Double Interlock Electric Electric Wiring Schematic Non Integrated Releasing Panel...
Страница 82: ...77 END...