TFP317
Page 3 of 4
Installation
TYCO Model ESFR-17 Early Suppres-
sion, Fast Response 16.8K Pendent
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using
only the Frame arms to handle the
sprinkler (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 3/4 inch NPT sprinkler
joint should be obtained by apply-
ing a minimum-to-maximum torque of
10 to 20 lbs.-ft. (13,4 to 26,8 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Note:
Install the Model ESFR-17
Pendent Sprinkler in the pendent posi-
tion (Ref. Figures 3 and 4).
Step 1.
With pipe-thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
the Model ESFR-17 Sprinkler only by
the Frame arms.
Step 2.
Wrench-tighten the Model
ESFR-17 Sprinkler using only the
W-Type 2 Sprinkler Wrench or the
W-Type 30 Sprinkler Wrench (Ref.
Figures 3 and 4), and by fully engag-
ing (seating) the wrench on the sprin-
kler wrench flats (Ref. Figures 1 and 2).
Step 3.
After installation, inspect the
Link Assembly of each Model ESFR-17
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook
are positioned as illustrated in Figures
1 and 2, and that the Link Assembly
is not bent, creased, or forced out of
normal position in any way.
Replace
damaged sprinklers.
Storage Type
NFPA
Open Frame (i.e., no solid shelves)
Single, Double, Multiple-Row, or Portable Rack
Storage of Class I-IV and Group A or B Plastics
Refer to NFPA 13
Chapters 16 & 17
Solid Pile or Palletized
Storage of Class I-IV and Group A or B Plastics
Refer to NFPA 13
Chapters 14 & 15
Idle Pallet Storage
Refer to NFPA 13
Chapter 12
Rubber Tire Storage
Refer to NFPA 13
Chapter 18
Rolled Paper Storage
(Refer to the standard)
Refer to NFPA 13
Chapter 19
Flammable Liquid Storage
(Refer to the standard)
Refer to NFPA 30
Aerosol Storage
(Refer to the standard)
Refer to NFPA 30B
Automotive Components in Portable Racks
(Control mode only; refer to the standard)
N/A
N/A – Not Applicable
WRENCH
RECESS
"FITTING SIDE"
TOWARD SPRINKLER
FITTING
1" WRENCH
ACCEPTS
WRENCH
RECESS
1/2" DRIVE
ACCEPTS
SOCKET
HEX
FLATS
WRENCH
FIGURE 4
W-TYPE 30
SPRINKLER WRENCH
FIGURE 3
W-TYPE 2
SPRINKLER WRENCH
TABLE 1
MODEL ESFR-17 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW