Installation

TYCO Model ESFR-17 Early Suppres-

sion, Fast Response 16.8K Pendent 

Sprinklers must be installed in accor-

dance with this section.

General Instructions

Avoid damage to the fusible Link 

Assembly during installation by using 

only the Frame arms to handle the 

sprinkler (i.e., do not apply pressure 

to the fusible Link Assembly), and by 

using the appropriate sprinkler wrench. 

Failure to do so can lead to an unstable 

link assembly and premature activation 

of the sprinkler. Damaged sprinklers 

must be replaced.
A leak-tight 3/4 inch NPT sprinkler 

joint should be obtained by apply-

ing a minimum-to-maximum torque of 

10 to 20 lbs.-ft. (13,4 to 26,8 Nm). 

Higher levels of torque can distort the 

sprinkler inlet with consequent leakage 

or impairment of the sprinkler.

Note:

 Install the Model ESFR-17 

Pendent Sprinkler in the pendent posi-

tion (Ref. Figures 3 and 4).

Step 1.

 With pipe-thread sealant 

applied, hand-tighten the sprinkler into 

the sprinkler fitting. Do not apply pres-

sure to the Link Assembly, and handle 

the Model ESFR-17 Sprinkler only by 

the Frame arms.

Step 2.

 Wrench-tighten the Model 

ESFR-17 Sprinkler using only the 

W-Type 2 Sprinkler Wrench or the 

W-Type 30 Sprinkler Wrench (Ref. 

Figures 3 and 4), and by fully engag-

ing (seating) the wrench on the sprin-

kler wrench flats (Ref. Figures 1 and 2).

Step 3.

 After installation, inspect the 

Link Assembly of each Model ESFR-17 

Sprinkler for damage. In particular, 

verify that the Link Assembly and Hook 

are positioned as illustrated in Figures 

1 and 2, and that the Link Assembly 

is not bent, creased, or forced out of 

normal position in any way. 

Replace 

damaged sprinklers.

Storage Type

NFPA

Open Frame (i.e., no solid shelves)
Single, Double, Multiple-Row, or Portable Rack 

Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 

Chapters 16 & 17

Solid Pile or Palletized 

Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 

Chapters 14 & 15

Idle Pallet Storage

Refer to NFPA 13 

Chapter 12

Rubber Tire Storage

Refer to NFPA 13 

Chapter 18

Rolled Paper Storage 

(Refer to the standard)

Refer to NFPA 13 

Chapter 19

Flammable Liquid Storage 

(Refer to the standard)

Refer to NFPA 30

Aerosol Storage 

(Refer to the standard)

Refer to NFPA 30B

Automotive Components in Portable Racks 

(Control mode only; refer to the standard)

N/A

N/A – Not Applicable

WRENCH

RECESS

"FITTING SIDE"

TOWARD SPRINKLER

FITTING

1" WRENCH

ACCEPTS

WRENCH

RECESS

1/2" DRIVE

ACCEPTS

SOCKET

HEX

FLATS

WRENCH

FIGURE 4 

W-TYPE 30 

SPRINKLER WRENCH

FIGURE 3 

W-TYPE 2 

SPRINKLER WRENCH

TABLE 1 

MODEL ESFR-17 PENDENT SPRINKLER 

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW