CARE AND MAINTENANCE
The Model S190 must be maintained and serviced in ac-
cordance with the following instructions:
NOTES
Absence of an escutcheon, which is used to cover a clear-
ance hole, may delay the time to operation in a fire situ-
ation.
Before closing a fire protection system main control valve
for maintenance work on the fire protection system which
it controls, permission to shut down the affected fire pro-
tection systems must be obtained from the proper authori-
ties and all personnel who may be affected by this action
must be notified.
Sprinkler which are found to be leaking or exhibiting vis-
ible signs of corrosion must be replaced.
Automatic sprinklers must never be shipped or stored
where their temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified sprinklers must
be replaced. Sprinklers that have been exposed to corro-
sive products of combustion, but have not operated,
should be completely cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft bristle brush.
Care must be exercised to avoid damage - before, dur-
ing, and after installation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced. Also, replace any sprinkler that has a cracked
bulb or that has lost liquid from its bulb (Ref. Installation
Section).
Frequent visual inspections are to be initially performed
for lead coated sprinklers, after the installation has been
completed, to verify the long term potential integrity of the
sprinkler coating. Thereafter, annual inspections per
NFPA 25 should suffice; however, instead of inspecting
from the floor level, a random sampling of close-up visual
inspections should be made, so as to better determine
the exact sprinkler condition and the long term integrity of
the lead coating, as it may be affected by the corrosive
conditions present.
The owner is responsible for the inspection, testing, and
maintenance of their fire protection system and devices in
compliance with this document, as well as the applicable
standards of the National Fire Protection Association
(e.g., NFPA 25), in addition to the standards of any other
authorities having jurisdiction. The installing contractor or
sprinkler manufacturer should be contacted relative to
any questions.
It is recommended that automatic sprinkler systems be in-
spected, tested, and maintained by a qualified Inspection
Service.
LIMITED WARRANTY
Products manufactured by Tyco Fire Products are war-
ranted solely to the original Buyer for ten (10) years
against defects in material and workmanship when paid
for and properly installed and maintained under normal
use and service. This warranty will expire ten (10) years
from date of shipment by Tyco Fire Products. No warranty
is given for products or components manufactured by
companies not affiliated by ownership with Tyco Fire Prod-
ucts or for products and components which have been
subject to misuse, improper installation, corrosion, or
which have not been installed, maintained, modified or re-
paired in accordance with applicable Standards of the Na-
tional Fire Protection Association, and/or the standards of
any other Authorities Having Jurisdiction. Materials found
by Tyco Fire Products to be defective shall be either re-
paired or replaced, at Tyco Fire Products’ sole option.
Tyco Fire Products neither assumes, nor authorizes any
person to assume for it, any other obligation in connec-
tion with the sale of products or parts of products. Tyco
Fire Products shall not be responsible for sprinkler sys-
tem design errors or inaccurate or incomplete information
supplied by Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LI-
ABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UN-
DER ANY OTHER LEGAL THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES,
INCLUDING BUT NOT LIMITED TO LABOR CHARGES,
REGARDLESS OF WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT SHALL TYCO FIRE
PRODUCTS’ LIABILITY EXCEED AN AMOUNT EQUAL
TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF
ANY AND ALL OTHER WARRANTIES EXPRESS OR IM-
PLIED, INCLUDING WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE.
ORDERING PROCEDURE
Please Specify:
1 Model S190, ECOH Sprinkler
K=11.2 Pendent (#2511)
K=14.0 Pendent (#2611)
K=11.2 Upright (#2510)
K=14.0 Upright (#2610)
2. Recessed Escutcheon (#2088)
3. W-Type 3 Sprinkler Wrench (#2948)
W-Type 4 Recessed Sprinkler Wrench (#3211)
Refer to Price List for for complete listing of Part Num-
bers with respect to temperature ratings, finishes, etc.
STAR SPRINKLER
1-2.2.40
Page 5
OBSOLETE