background image

TECHNICAL DATA

Approvals

UL and C-UL Listed. FM Approved.
(Listings and approvals only apply to the service condi-
tions in the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1 inch NPT or ISO 7-R1

Discharge Coefficient

K = 25.2 GPM/psi

1/2

(362,9 LPM/bar

1/2

)

Temperature Ratings

165°F/74°C or 214°F/101°C

Finish

Natural Brass

Physical Characteristics (Ref. Figure 1)

The Pulsar ESFR-25 utilizes a dezincification resistant
bronze alloy frame. The strut and hook are monel; the but-
ton, deflector, and compression screw are bronze. The
gasketed spring plate consists of a beryllium nickel disc
spring that is sealed on both its inside and outside edges
with a Teflon

†

gasket, and the two halves of the fusible

link assembly are nickel.

Patents

U.S.A. Patent Number 4,580,729, 5,829,532, and
6,059,044 are applicable to the Pulsar ESFR-25. Other
patents are pending.

DESIGN CRITERIA

UL and C-UL Listing Criteria

The Pulsar ESFR-25 (SIN S8010) Sprinklers are UL and
C-UL Listed as “Early Suppression Fast Response Sprin-
klers” for installation per NFPA 13 or other applicable
NFPA standards.

UL and C-UL Specific Application Listing Criteria

The Pulsar ESFR-25 (SIN S8010) Sprinklers are UL and
C-UL Listed as “Specific Application Early Suppression
Fast Response Sprinklers” for use in in accordance with
NFPA 13 to protect single-, double-, and multiple row rack
storage and palletized and solid pile storage (no open
containers or solid shelves) of Class I, II, III, and IV com-
modities encapsulated or unencapsulated and cartoned
Group A unexpanded plastics when installed with the fol-
lowing storage and ceiling heights and minimum design
pressures:

Maximum

Maximum

Minimum

Storage

Ceiling

Flowing

Height,

Height,

Pressure,

Ft. (m)

Ft. (m)

psi (bar)

40 (12,2)

45 (13,7)

40 (2,7)

35 (10,7)

40 (12,2)

25 (1,7)

30 (9,1)

35 (10,7)

20 (1,4)

25 (7,6)

30 (9,1)

15 (1,0)

When applying the specific application listing criteria, the
Pulsar ESFR-25 Sprinklers should be installed using the
same installation obstruction and construction criteria, as
well as deflector-to ceiling distances, as is applicable for
Early Suppression Fast Response Sprinklers having a
nominal K-Factor of 25.2 per NFPA 13.

FM Approval Criteria

The Pulsar ESFR-25 (SIN S8010) Sprinklers are FM Ap-
proved as “Early Suppression Fast Response Sprinklers”
for installation per the applicable FM Loss Prevention
Data Sheets.

STAR SPRINKLER

Page 2

1-4.1.11

FIGURE 1

PULSAR ESFR-25 PENDENT SPRINKLER

1" NPT

(BOTH SIDES)

WRENCH FLAT

(96.8 mm)

3-13/16"

9/16" (14.3 mm)

NOMINAL MAKE-IN

2" (50.8 mm)

TEMPERATURE

RATING

ASSEMBLY

LINK

HOOK

†

DuPon

t

Regi

ste

red

Trad

emar

k

OBSOLETE

Содержание Star Pulsar ESFR-25

Страница 1: ... 0 The Pulsar ESFR 25 Pendent Sprinkler is also Listed by Underwriters Laboratories Inc UL and by UL for use in Canada C UL as a Specific Application Early Suppres sion Fast Response Sprinkler as indicated under the UL and C UL Specific Application Design Criteria section The specific application listing provides for reduced pres sure design for the protection of certain commodities Applications f...

Страница 2: ...s are UL and C UL Listed as Specific Application Early Suppression Fast Response Sprinklers for use in in accordance with NFPA 13 to protect single double and multiple row rack storage and palletized and solid pile storage no open containers or solid shelves of Class I II III and IV com modities encapsulated or unencapsulated and cartoned Group A unexpanded plastics when installed with the fol low...

Страница 3: ...like must be replaced The owner is responsible for the inspection testing and maintainance of their fire protection system and devices in compliance with this document as well as with the ap plicable standards of the National Fire Protection Associa tion e g NFPA 25 in addition to the standards of any other authorities having jurisdiction The installing contrac tor or sprinkler manufacturer should...

Страница 4: ... W Type 1 Sprinkler Wrench 2949 Refer to Price List for for complete listing of Part Num bers with respect to temperature ratings etc STAR SPRINKLER Page 4 1 4 1 11 7071 S 13th Street Suite 103 Oak Creek WI 53154 www starsprinkler com PRINTED IN U S A 3 01 O B S O L E T E ...

Отзывы: