STAR SPRINKLER

Page 2

1-3.3.10

(a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next

highest coverage area for which hydraulic design criteria are stated.

(b) Requirement is based on minimum flow in GPM from each sprinkler. The associated residual pressures are calculated using the

nominal K-factor. Refer to

Hydraulic Design Criteria

section for details.

(c) To meet this requirement, the centerline of sprinkler waterway (Ref. Fig. 1) must be 4-3/8 to 6-3/8 inches below the ceiling for a

deflector-to-ceiling distance of 4 to 6 inches, or 4-3/8 to 12-3/8 inches below the ceiling for a deflector-to ceiling distance of
4 to 12 inches.

TABLE A

HYDRAULIC DESIGN CRITERIA

12 x 12

COVERAGE

AREA

W x  L

(a)

FT x FT

NFPA 13D/13R

MINIMUM

MULTIPLE

SPRINKLER

FLOW

(b)

14 x 14

16 x 16

16 x 18

16 GPM

(13.8 PSI)

14 GPM

(10.6 PSI)

18 GPM

(17.5 PSI)

14 GPM

(10.6 PSI)

21 GPM

(23.9 PSI)

19 GPM

(19.5 PSI)

15 GPM

(12.2 PSI)

12 GPM

(7.8 PSI)

NFPA 13D/13R

MINIMUM

SINGLE

SPRINKLER

FLOW

(b)

16 x 18

K-FACTOR

28 GPM

(23.3 PSI)

23 GPM

(15.7 PSI)

4.3

4.3

4.3

4.3

5.8

A

(c)

INCHES

4 to 6

4 to 6

4 to 6

4 to 6

4 to 6

B

FEET

6

7

8

8

8

16 x 20

12 x 12

5.8

4.3

12 x 12

5.8

14 x 14

4.3

29 GPM

(25.0 PSI)

26 GPM

(20.1 PSI)

4 to 6

12 GPM

(7.8 PSI)

17 GPM

(15.6 PSI)

18 GPM

(9.6 PSI)

15.3 GPM

(7.0 PSI)

4 to 12

4 to 12

6

6

8

7

4 to 12

15 GPM

(12.2 PSI)

19 GPM

(19.5 PSI)

†