General Service Conditions.

The Star Galaxy SG-RES

must only be utilized in wet pipe sprinkler systems.

Hydraulic Design Criteria.

The minimum required flow

rates for residential applications are given in Table A as a
function of the maximum allowable coverage areas. The
NFPA 13D/13R single sprinkler flow rate is the minimum
required discharge from the most hydraulically demand-
ing single sprinkler and the NFPA 13D/13R multiple sprin-
kler flow rate is the minimum required discharge from
each of the total number of “design sprinklers” as speci-
fied in NFPA 13D or 13R.

TIA 99-1 (Tentative Interim Amendment) with an effective
date of May 22, 2000 states that the minimum required
discharge from each of the “design sprinklers” for sys-
tems designed to NFPA 13 must be calculated based on
delivering a minimum design density of 0.1 gpm/sq. ft. for
each of the listed coverage areas shown in Table A. Con-
sult with the Authority Having Jurisdiction regarding the
application of this TIA to the currently adopted NFPA 13.

Spray Coverage Criteria.

Each Star Galaxy SG-RES

must only be used in accordance with one of the desig-
nated width by length (W x L) coverage criteria specified
in Table A.

Ceiling mounted obstructions such as heating or air condi-
tioning diffusers, overhangs, and light fixtures must be lo-
cated above an elevation, as shown in Figure 3, where
they will not interfere with the proper distribution of water
by the sprinkler.

The Star Galaxy SG-RES may be installed along over-
hangs or soffits that are a maximum of 8 inches wide (dis-
tance from wall); with a maximum vertical distance of 4
inches from the centerline of the sprinkler waterway to
the bottom of the overhang/soffit; and, with a deflector-
to-soffit surface distance of 1-1/2 to 3 inches, or with
the #2084 Recessed Escutcheon as shown in Figure 2.

NOTE

Use of overhangs or soffits with dimensions exceed-
ing the above specified criteria is permitted if addi-
tional sprinkler protection is provided for the area be-
low the overhang/soffit.

The Star Galaxy SG-RES must NOT be located

1. Along a wall/partition having a recessed range oven,

countertop, or alcove.

2. Along a wall/partition having an adjoining wood or coal

burning stove.

3. Along a wall/partition containing a fireplace or wall oven.

Operational Sensitivity Criteria.

The Star Galaxy SG-

RES must only be installed

1. Beneath level ceilings.

2. Beneath solid ceilings having a smooth or textured sur-

face.

3. With a deflector-to-wall surface distance of 1-1/2 to

6 inches or a deflector-to soffit surface distance of 1-1/2
to 3 inches, unless the #2084 Recessed Escutcheon is
being utilized as shown in Figure 2.

4. With a deflector-to-ceiling distance per Table A.

5. At least 4 inches away from an inside or outside corner.

The Star Galaxy SG-RES must NOT be used

1. Beneath soffits or overhangs, unless they are only pro-

viding protection for the area underneath the soffit/over-
hang and additional sprinkler protection is provided for
the area in front of the soffit/overhang.

STAR SPRINKLER

Page 4

1-3.3.10

FIGURE 3

ALLOWABLE ELEVATION FOR NON-CONTINUOUS CEILING MOUNTED OBSTRUCTIONS

SUCH AS HEATING OR AIR CONDITIONING DIFFUSER, OVERHANGS, AND LIGHT FIXTURES