FIGURE 5
MODEL EC-HS RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
13 MM TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
80 K-FACTOR, 1/2 INCH NPT
TFP288
Page 4 of 6
Installation
The Model EC-HS Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1,6 mm.
A 1/2 in. NPT sprinkler joint should be
obtained with a minimum to maximum
torque of 9,5 to 19,0 N
·
m. Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuf-
ficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Re-adjust the position of the
sprinkler fitting to suit.
Series Model EC-HS Sidewall
Sprinklers
The Series Model EC-HS Sidewall
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1.
Horizontal sidewall sprinklers
are to be installed with their center-
line perpendicular to the back wall and
parallel to the ceiling. The word “TOP”
on the deflector is to face towards the
ceiling.
Step 2.
With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3.
Tighten the sprinkler into the
sprinkler fitting using only the W-Type 6
Sprinkler Wrench (Ref. Figure 2).
With reference to Figures 1, the W-Type
6 Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Series Model EC-HS Recessed
Sidewall Sprinklers
The Model EC-HS Recessed Sidewall
Sprinklers must be installed in accor-
dance with the following instructions.
Step A.
Horizontal sidewall sprinklers
are to be installed with their center-
line perpendicular to the back wall and
parallel to the ceiling. The word “TOP”
on the deflector is to face towards the
ceiling.
Step B.
After installing the Style 10
or 20 Mounting Plate, as applicable,
over the sprinkler threads and with
pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step C.
Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 3). With reference to Figure
1, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprin-
kler wrench flats.
Step D.
After the wall has been
installed or the finish coat has been
applied, slide on the Style 10 or 20
Closure over the Model EC-HS Sprin-
kler and push the Closure over the
Mounting Plate until its flange comes
in contact with the wall.
Care and
Maintenance
The Model EC-HS Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent oper-
ation may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
19 mm
32 mm
CLOSURE
6 mm
19 mm
3 mm
16±6 mm
MOUNTING
PLATE
57 mm
DIA.
73 mm
DIA.
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
MODEL
EC-HS
CLOSURE
32 mm
25 mm
MOUNTING
PLATE
13 mm
6 mm
3 mm
57 mm
DIA.
73 mm
DIA.
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
13±3 mm
MODEL
EC-HS
FIGURE 4
MODEL EC-HS RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
19 MM TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
80 K-FACTOR, 1/2 INCH NPT