Design 

Criteria

The Model EC-HS Extended Coverage 

Horizontal Sidewall Sprinklers are to 

be installed per VdS CEA 4001 under 

smooth ceilings in Light or Ordinary 

Hazard 1, as well as in accordance 

with Annex E of VdS CEA 4001. Only 

the Style 10 or 20 Recessed Escutch-

eon, as applicable, is to be used for 

recessed installations.
The following design criteria is pro-

vided as a general guide. Refer to VdS 

CEA4001 for complete installation 

rules.

Maximum Sprinkler Coverage Area

21 m

2

 (separated with F30 fire resis-

tance in accordance to DIN4102)

Maximum Ceiling Height

4,1 m

Maximum Room Depth

•  one sprinkler line: 6,5 m
•  two opposite sprinkler lines: 11 m

Maximum Coverage Width

4,5 m

Sprinkler Spacing Along Wall 

(Sprinkler Coverage Width)

3,0 m to 4,5 m

Minimum Sprinkler to Room Corner 

Distance

0,5 m

Maximum Sprinkler Deflector to 

Wall Distance

0,3 m

Deflector-to-Ceiling Distance

0,10 m to 0,25 m

Minimum Discharge Pressure

•  2,5 bar for less than 2,8 m room 

height

•  3,0 bar for equal to and greater than 

2,8 m room height

K

TYPE

TEMP.

BULB 

LIQUID

Sprinkler Finish

NATURAL 

BRASS

CHROME 

PLATED

POLYESTER

80  

1/2 in. 

NPT

EC-HS  

(TY3330)

57°C

Orange

1

68°C

Red

79°C

Yellow

80  

1/2 in. 

NPT

RECESSED 

EC-HS

a

 

(TY3330)

57°C

Orange

1

68°C

Red

79°C

Yellow

80  

1/2 in. 

NPT

RECESSED 

EC-HS

b

 

(TY3330)

57°C

Orange

1

68°C

Red

79°C

Yellow

NOTES:

1.  VdS Approved 

(For details contact TYCO Fire Protection Products, www.tyco-fire.com)

b.  Installed with Style 10 recessed Escutcheon (Figure 4).
c.  Installed with Style 20 recessed Escutcheon (Figure 5).

WRENCH RECESS

(END "A" USED FOR

MODEL EC-HS)

WRENCH

RECESS

PUSH WRENCH

IN TO ENSURE

ENGAGEMENT

WITH SPRINKLER

WRENCHING AREA

TABLE A 

LABORATORY LISTINGS AND APPROVALS

(Refer to the Design Criteria Section)

FIGURE 2 

W-TYPE 6 SPRINKLER 

WRENCH

FIGURE 3 

W-TYPE 7 RECESSED 

SPRINKLER WRENCH